Note:
The faults are automatically acknowledged after half of the waiting time has expired.
p1213
Automatic restart, monitoring time line supply return / WEA t_mon line sup
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Functions
Min
0.0 [s]
Description:
Sets the monitoring time of the automatic restart (AR).
Dependency:
Refer to: p1210, r1214
Cautiont:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note:
The monitoring time starts when the faults are detected. If the automatic acknowledgements are not successful, the
monitoring time runs again. If, after the monitoring time has expired, the drive has still not successfully restarted
(the motor must have been magnetized), then fault F07320 is output.
The monitoring is de-activated with p1213 = 0. If p1213 is set lower than the sum of p1212 and the magnetization
time r346, then fault F07320 is generated at each restart.
r1214
CO/BO: Automatic restart, status / AR status
VECTOR
Can be changed: -
Data type: Unsigned16
P-Group: Functions
Min
-
Description:
Automatic restart (AR) status word.
Bit field:
Bit
Signal name
00
Initialization
01
Wait for alarm
02
Auto restart act.
04
Acknowledge alarms
05
Restart
06
Wait time running
07
Fault
12
Start count. bit 0
13
Start count. bit 1
14
Start count. bit 2
15
Start count. bit 3
p1215
Motor holding brake configuration / Brake config
VECTOR
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Min
0
Description:
Sets the holding brake configuration.
Values:
0:
1:
2:
3:
Dependency:
Refer to: p1216, p1217, p1226, p1227
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
No motor holding brake being used
Motor holding brake acc. to sequential control
Motor holding brake always open
Motor holding braking can be parameterized via BICO just like the sequential control, brake connection
Data set: -
Units group: TIME
Max
1999.0 [s]
Data set: -
Units group: -
Max
-
0 signal
No
No
No
No
No
No
No
Off
Off
Off
Off
Data set: -
Units group: -
Max
3
Parameters
Parameter list
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0.0 [s]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
-
1 signal
FP
Yes
-
Yes
-
Yes
-
Yes
-
Yes
-
Yes
-
Yes
-
On
-
On
-
On
-
On
-
Access level: 2
Function diagram: 2701
Unit selection: -
Factory setting
0
1-159