Remedy:
- stop the trace before parameterization.
- if required, start the trace.
A02075
Trace: Pretrigger time too long
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected pretrigger time must be shorter than the recording time.
Remedy:
Check the pretrigger time setting and change if necessary.
A02099
Trace: Insufficient memory
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory space still available on the control unit is no longer sufficient for the trace function.
Remedy:
Reduce the memory required, e.g. as follows:
- reduce the trace (record) time.
- increase the trace clock cycle.
- reduce the number of signals to be traced (recorded).
A02100
CU: Computation deadtime current controller too low
Reaction:
NONE
Acknowledge:
NONE
Cause:
The value in p0118 produces a dead time of one clock cycle because it lies before the setpoint becomes available.
A possible cause could be, for example, that the system characteristics no longer match those parameterized after
a component has been replaced.
Alarm value (r2124, floating point):
The minimum value for p0118 where a deadtime no longer occurs.
Remedy:
- set p0118 to a value greater than or equal to the alarm value.
- set p0117 to an automatic setting.
- check the firmware releases of the components involved.
See also: p0117, p0118
F03500 (A)
TM: Initialization
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (power on)
Cause:
When initializing the terminal modules, the terminals of the control unit or the terminal board 30, an internal software
error has occurred.
Fault value (r0949, decimal):
The thousands location = 1 ... 3:
The component number (p0151) of the module involved is specified at the ones, tens and hundreds position.
Remedy:
- power-down the power supply for the control unit and power-up again.
- check the DRIVE-CLiQ connection.
- if required, replace the terminal module.
The terminal module should be directly connected to a DRIVE-CLiQ socket of the control unit.
If the fault occurs again, replace the terminal module.
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F03505 (N, A)
TM: Analog input, wire breakage
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (power on)
Cause:
The input current of the TM analog input has exceeded the threshold value parameterized in p4061[x].
This fault can only occur, if p4056[x] = 3 (4 ... 20 mA with monitoring) is set.
Index x = 0: Analog input 0 (X522.1 to .3)
Index x = 1: Analog input 1 (X522.4 to .5)
Fault value (r0949, decimal):
The component number (p0151) of the module involved is specified at the ones, tens and hundreds position.
The thousands position specifies the analog input involved: 0: Analog input 0 (AI 0), 1: Analog input 1 (AI 1)
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms
3-553