Siemens SINAMICS G List Manual page 562

Table of Contents

Advertisement

Faults and Alarms
List of faults and alarms
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
F07405 (N, A)
Drive: Kinetic buffering minimum speed not reached
Reaction:
OFF2 (DCBRAKE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
During kinetic buffering the speed fell below minimum speed (p1257) and the line supply did not return.
Remedy:
Check the speed threshold for the Vdc_min controller (kinetic buffering) (p1257).
See also: p1257
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F07406 (N, A)
Drive: Kinetic buffering maximum time exceeded
Reaction:
OFF3 (DCBRAKE, OFF1, OFF2, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The maximum buffer time (p1255) has been exceeded but the line supply has not returned.
Remedy:
Check the time threshold for Vdc-min controller (kinetic buffering) (p1255).
See also: p1255
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
A07409
Drive: V/f control, current limiting controller active
Reaction:
NONE
Acknowledge:
NONE
Cause:
The current limiting controller of the V/f control was activated because the current limit was exceeded.
Remedy:
The alarm is automatically withdrawn when increasing the current limit (p0640), reducing the load or using a slower
up ramp for the setpoint (reference) speed.
F07410
Drive: Current controller output limited
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
- motor not connected or motor contactor open.
- no DC link voltage present.
- motor module defective.
Remedy:
- connect the motor or check the motor contactor.
- check the DC link voltage (r0070).
- check the motor module.
F07411
Drive: Flux controller output limited
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
The specified flux setpoint cannot be reached although 90% of the maximum current has been specified.
- incorrect motor data.
- motor data and motor configuration (star/delta) do not match.
- the current limit has been set too low for the motor.
- the motor module is too small.
3-562
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004

Hide quick links: