p1048[0...n]
Motorized potentiometer, ramp-down time / Mop ramp-down time
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [s]
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1047, p1082
Note:
The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
r1050
CO: Motorized potentiometer, setpoint after the ramp-function generator / Mop setp
after RFG
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Setpoints
Min
- [1/min]
Description:
Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Recommenda-
Interconnect the signal with main setpoint (p1070).
tion:
Dependency:
Refer to: p1070
p1055[0...n]
BI: Jog bit 0 / Jog bit 0
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for jog 1.
Recommenda-
When the signal source is set, this does not trigger a response - but only a signal change of the source.
tion:
Dependency:
Refer to: p1058
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for jog 2.
Recommenda-
When the signal source is set, this does not trigger a response - but only a signal change of the source.
tion:
Dependency:
Refer to: p1059
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: DDS
Units group: TIME
Max
1000.000 [s]
Data set: -
Units group: SPEED_ROT
Max
- [1/min]
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Parameters
Parameter list
Access level: 2
Function diagram: 3020
Unit selection: -
Factory setting
10.000 [s]
Access level: 3
Function diagram: 1550,
3020
Unit selection: -
Factory setting
- [1/min]
Access level: 3
Function diagram: 2501,
3030
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: 2501,
3030
Unit selection: -
Factory setting
0
1-143