Faults and Alarms
Overview of Faults and Alarms
Table 3-2
Fault reactions, continued
List
PROFId-
rive
STOP1
-
STOP2
-
DCBRAKE
-
ENCODER
-
Acknowledgement of faults
The list of faults and alarms specifies how to acknowledge each fault after the
cause has been remedied.
Table 3-3
Acknowledgement of faults
List
POWER ON
The fault is acknowledged by a POWER ON process (switch drive unit off and on again).
Note:
If this action has not eliminated the fault cause, the fault is displayed again immediately
after power up.
IMMEDIATELY
Starting from a drive object, the fault can be acknowledged by the following methods:
1 Acknowledge by setting parameter:
p3981 = 0 --> 1
2 Acknowledge via binector inputs:
p2103
p2104
p2105
3 Acknowledge using PROFIBUS control signal:
STW1.7 = 0 --> 1 (edge)
Note:
• These faults can also be acknowledged by a POWER ON operation.
• If this action has not eliminated the fault cause, the fault is displayed again immedi-
ately after power up.
• Safety Integrated faults
The "Safe Stop" (SH) function must be deselected before these faults are acknowl-
edged.
READY
The fault can be acknowledged only in the READY state.
In this state, the DC link is charged and the pulses disabled.
3-508
Reaction
-
Available soon
• n_set = 0 is input immediately to brake the drive along
n_set = 0
the OFF3 deceleration ramp (p1135).
• The drive remains in closed-loop speed control mode.
-
Available soon
Internal/external
The fault reaction ENCODER is applied as a function of
pulse disable
the setting in p0491.
(p0491)
Factory setting:
p0491 = 0 --> Encoder fault causes OFF2
BI: 1. Acknowledge faults
BI: 2. Acknowledge faults
BI: 3. Acknowledge faults
Description
Description
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004