Parameters
Parameter list
p1142[0...n]
BI: Enable speed setpoint / Enable n_set
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for control word 1 bit 6 (enables setpoint/disable setpoint).
Dependency:
Refer to: p1140, p1141
Note:
Bit 6 = 0: Inhibits the setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enables the setpoint
p1143[0...n]
BI: Ramp-function generator, accept setting value / Accept RFG set val
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency:
The signal source for the ramp-function generator setting value is set using parameters.
Refer to: p1144
Note:
0/1 signal:
The ramp-function generator output is immediately (without delay) set to the setting value of the ramp-function gen-
erator.
1 signal:
The setting value of the ramp-function generator is effective.
1/0 signal:
The input value of the ramp-function generator is effective. The ramp-function generator output is adapted to the
input value using the ramp-up time or the ramp-down time.
0 signal:
The input value of the ramp-function generator is effective.
p1144[0...n]
CI: Ramp-function generator setting value / RFG setting value
VECTOR
Can be changed: U, T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for the ramp-function generator setting value.
Dependency:
The signal source for accepting the setting value is set using parameters.
Refer to: p1143
1-152
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 3
Function diagram: 2442,
2443, 2501
Unit selection: -
Factory setting
1
Access level: 3
Function diagram: 3070
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: 3070
Unit selection: -
Factory setting
0