Siemens SINAMICS G List Manual page 317

Table of Contents

Advertisement

r7025
Parallel circuit configuration, maximum deviation currents phase U / Phase U Max
i_dev
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [A]
Description:
Displays the maximum absolute deviation of the measured current actual values of phase U from the average value
as peak value.
The deviation of the individual currents from the average value is displayed in r7020.
Dependency:
Refer to: r7020, r7026, r7027
Refer to: A05052
r7026
Parallel circuit configuration, maximum deviation currents phase V / Phase V Max
i_dev
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [A]
Description:
Displays the maximum absolute deviation of the measured current actual values of phase V from the average value
as peak value.
The deviation of the individual currents from the average value is displayed in r7021.
Dependency:
Refer to: r7021, r7025, r7027
Refer to: A05052
r7027
Parallel circuit configuration, maximum deviation currents phase W / Phase W Max
i_dev
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [A]
Description:
Displays the maximum absolute deviation of the measured current actual values of phase W from the average
value as peak value.
The deviation of the individual currents from the average value is displayed in r7022.
Dependency:
Refer to: r7022, r7025, r7026
Refer to: A05052
r7030[0...n]
Parallel circuit configuration, deviation DC link voltage / Vdc deviation
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [V]
Description:
Displays the deviation of the measured DC link voltage from the average value.
The maximum deviation from the average value is displayed in r7031.
Dependency:
Refer to: r7031
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: CURRENT_AC_PP
Max
- [A]
Data set: -
Units group: CURRENT_AC_PP
Max
- [A]
Data set: -
Units group: CURRENT_AC_PP
Max
- [A]
Data set: PDS
Units group: VOLTAGE_DC
Max
- [V]
Parameters
Parameter list
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [A]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [A]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [A]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [V]
1-317

Hide quick links:

Advertisement

Table of Contents
loading