p0976
Reset and load all parameters / Reset load all par
CU
Can be changed: C1
Data type: Unsigned16
P-Group: Factory settings
Min
0
Description:
Resets or downloads all parameters of the drive system.
Values:
0:
1:
2:
3:
10:
11:
12:
20:
21:
22:
23:
24:
25:
26:
100:
Note:
After all of the parameters have been reset to their factory setting, the system must commissioned for the first time
again.
Resetting or loading is realized in the non-volatile memory.
Procedure:
1. Set p0009 = 30 (parameter reset).
2. Set p0976 to "required value". A new system run-up is started.
p0009 is automatically set to 0 after this has been carried-out.
p0977
Save all parameters / Save all par
CU
Can be changed: U, T
Data type: Unsigned16
P-Group: Displays, signals
Min
0
Description:
Saves all parameters of the drive system to the non-volatile memory (CompactFlash Card).
Values:
0:
1:
10:
11:
12:
20:
21:
22:
23:
24:
25:
26:
Dependency:
Refer to: p0976
Cautiont:
The control unit power supply may only be powered-down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Note:
Parameters saved with p0977 = 10, 11 or 12 can be downloaded again with p0976 = 10, 11 or 12.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
not active
Starts to reset all parameters to factory setting
Starts to download parameters saved in a non-volatile fashion with p0977 = 1
Start to download the volatile parameters from RAM
Starts to download parameters saved in a non-volatile fashion with p0977 = 10
Starts to download parameters saved in a non-volatile fashion with p0977 = 11
Starts to download parameters saved in a non-volatile fashion with p0977 = 12
Starts to download Siemens internal setting 20
Starts to download Siemens internal setting 21
Starts to download Siemens internal setting 22
Starts to download Siemens internal setting 23
Starts to download Siemens internal setting 24
Starts to download Siemens internal setting 25
Starts to download Siemens internal setting 26
Starts to reset all BICO interconnections
not active
Saves all parameters loaded at POWER ON in a non-volatile fashion
Saves all parameters in a non-volatile fashion, downloaded with p0976 = 10 as option
Saves all parameters in a non-volatile fashion, downloaded with p0976 = 11 as option
Saves all parameters in a non-volatile fashion, downloaded with p0976 = 12 as option
Saves all parameters as setting 20 in a non-volatile fashion (reserved)
Saves all parameters as setting 21 in a non-volatile fashion (reserved)
Saves all parameters as setting 22 in a non-volatile fashion (reserved)
Saves all parameters as setting 23 in a non-volatile fashion (reserved)
Saves all parameters as setting 24 in a non-volatile fashion (reserved)
Saves all parameters as setting 25 in a non-volatile fashion (reserved)
Saves all parameters as setting 26 in a non-volatile fashion (reserved)
Data set: -
Units group: -
Max
100
Data set: -
Units group: -
Max
26
Parameters
Parameter list
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 1
Function diagram: -
Unit selection: -
Factory setting
0
1-131

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents