Faults and Alarms
List of faults and alarms
Cause:
The topology comparison has detected a power module in the target topology that is not used in the actual topology.
Alarm value (r2124, decimal):
Component number of the additional target components.
Note:
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
- delete the drive belonging to the power module in the commissioning software project and download the new con-
figuration into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
A01482
Topology: Comparison shows sensor module not present in the actual topology
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a sensor module in the target topology that is not used in the actual topology.
Alarm value (r2124, decimal):
Component number of the additional target components.
Note:
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
- re-configure the drive belonging to the sensor module in the commissioning software project (encoder configura-
tion) and download the new configuration into the drive unit.
- delete the drive belonging to the sensor module in the commissioning software project and download the new con-
figuration into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
A01483
Topology: Comparison shows terminal module not present in the actual topology
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a terminal module in the target topology that is not used in the actual topol-
ogy.
Alarm value (r2124, decimal):
Component number of the additional target components.
Note:
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
- delete the terminal module in the commissioning software project and download the new configuration into the drive
unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
A01485
Topology: Comparison CX32 in actual topology missing
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a controller extension 32 (CX32) in the target topology that is not used in the
actual topology.
Alarm value (r2124, decimal):
Component number of the additional target components.
Note:
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
- delete the CX32 in the commissioning software project and download the new configuration into the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
A01486
Topology: Comparison shows DRIVE-CLiQ not present in the actual topology
Reaction:
NONE
Acknowledge:
NONE
3-534