p0316[0...n]
Motor torque constant / Mot kT
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.00 [Nm/A]
Description:
Sets the torque/force constant of the synchronous motor.
p0316 = 0: The torque/force constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque/force constant.
Dependency:
Refer to: r0334
Note:
The parameter is automatically preset for motors from the motor list (p0301).
This parameter is not used for induction motors (p0300 = 1xx).
p0320[0...n]
Motor rated magnetization current/short-circuit current / Mot I_mag_rated
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.000 [Aeff]
Description:
Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
p0322[0...n]
Maximum motor speed / Mot n_max
VECTOR
Can be changed: C2
Data type: Floating Point
P-Group: Motor
Min
0.0 [1/min]
Description:
Sets the maximum motor speed/velocity.
Dependency:
Refer to: p1082
Note:
The parameter is automatically preset for motors from the motor list (p0301).
p0323[0...n]
Maximum motor current / Mot I_max
VECTOR
Can be changed: C2
Data type: Floating Point
P-Group: Motor
Min
0.00 [Aeff]
Description:
Set the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Note:
The parameter is automatically preset for motors from the motor list (p0301).
For induction motors, the parameter has not effect if p0323 is set to 0.
For synchronous motors, a value must always be entered for the maximum motor current.
p0323 is a motor data. The user-selectable current limit is entered into p0640.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: MDS
Units group:
TORQUE_PER_CURR
Max
100.00 [Nm/A]
Data set: MDS
Units group: CURRENT_AC_EFF Unit selection: -
Max
5000.000 [Aeff]
Data set: MDS
Units group: SPEED_ROT
Max
210000.0 [1/min]
Data set: MDS
Units group: CURRENT_AC_EFF Unit selection: -
Max
20000.00 [Aeff]
Parameters
Parameter list
Access level: 1
Function diagram: -
Unit selection: -
Factory setting
0.00 [Nm/A]
Access level: 3
Function diagram: 5722
Factory setting
0.000 [Aeff]
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0.0 [1/min]
Access level: 2
Function diagram: 5722
Factory setting
0.00 [Aeff]
1-69