Siemens SINAMICS G List Manual page 16

Table of Contents

Advertisement

Parameters
Overview of parameters
The following states may be specified:
• C1
• C2
• U
• T
Note:
Parameter p0009 is CU-specific (belongs to control unit).
Parameter p0010 is drive-specific (belongs to each drive object).
The operating status of individual drive objects is displayed in r0002.
Access level (refers only to access via Basic Operator Panel)
Specifies the access level required to be able to display and change the relevant
parameter. The required access level can be set via p0003.
The system uses the following access levels:
1. Standard
2. Extended
3. Expert
4. Service
Note:
Parameter p0003 is CU-specific (belongs to control unit).
1-16
Converter commissioning
Converter commissioning is in progress (p0009 > 0).
Pulses cannot be enabled.
A modified parameter value does not take effect until converter com-
missioning mode is exited with p0009 = 0.
Drive object commissioning
Drive commissioning is in progress (p0009 = 0 and p0010 > 0).
Pulses cannot be enabled.
A modified parameter value does not take effect until drive commis-
sioning mode is exited with p0010 = 0.
Operation
Pulses are enabled.
Ready
Pulses are not enabled and status "C1" or "C2" is not active.
C1: Commissioning 1
C2: Commissioning 2
U: Run
T: Ready to run
 Siemens AG 2004 All Rights Reserved