Dependency:
The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power module, motor reactor) = filter inductance
p0230 = 3:
--> p0233 (power module, motor reactor) = filter inductance
--> p0234 (power module sinusoidal filter capacitance) = filter capacitance
--> p0290 (power module overload response) = inhibit pulse frequency reduction
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
--> p1802 (modulator modes) = space vector modulation without overcontrol
p0230 = 4:
--> p0290 (power module overload response) = inhibit pulse frequency reduction
--> p1802 (modulator modes) = space vector modulation without overcontrol
The user must set the following parameters according to the data sheet of the sinusoidal filter and also the user
must check whether they are permitted.
--> p0233 (power module, motor reactor) = filter inductance
--> p0234 (power module sinusoidal filter capacitance) = filter capacitance
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
Refer to: p0233, p0234, p0290, p1082, p1800, p1802
Note:
if a filter type cannot be selected, then this filter type is not permitted for the motor module.
p0230 = 2:
Chassis-type power modules with dv/dt filter may only be operated with a maximum pulse frequency of p1800 = 2.5
kHz. This means that the output frequency is restricted to 200 Hz.
p0230 = 3:
Sinusoidal filters with a rated pulse frequency of 1.25 or 2.5 kHz should only be operated with a current controller
sampling rate p0115[0] = 400 µs, sinusoidal filters with a rated pulses frequency of 2 or 4 kHz with p0115[0] = 250
µs.
The sinusoidal filter cannot be selected if the current controller sampling rate hasn't been appropriately set.
p0233
Power module motor reactor / PM mot reactor
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Drive converter
Min
0.000 [mH]
Description:
Enter the inductance of a filter connected at the power module output.
Dependency:
The parameter is automatically pre-assigned when selecting a filter via p0230.
Refer to: p0230
p0234
Power module sinusoidal filter capacitance / PM sine filter C
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Drive converter
Min
0.000 [µF]
Description:
Enters the capacitance of a sinusoidal filter connected at the power module output.
Dependency:
The parameter is automatically pre-assigned when selecting a filter via (p0230).
Refer to: p0230
Note:
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: INDUCTANCE_M3
Max
1000.000 [mH]
Data set: -
Units group: CAPACITY_M6
Max
1000.000 [µF]
Parameters
Parameter list
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0.000 [mH]
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0.000 [µF]
1-61