r1087
Speed limit negative effective / n_limit neg eff
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Setpoints
Min
- [1/min]
Description:
Displays the effective negative speed/velocity limit.
p1088[0...n]
CI: Speed limit negative direction of rotation / n_limit neg
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for the speed/velocity limit of the negative direction.
p1091[0...n]
Skip speed 1 / Skip speed 1
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [1/min]
Description:
Sets the skip speed/velocity 1.
Dependency:
Refer to: p1092, p1093, p1094, p1101
Note:
The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
p1092[0...n]
Skip speed 2 / Skip speed 2
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [1/min]
Description:
Sets the skip speed/velocity 2.
Dependency:
Refer to: p1091, p1093, p1094, p1101
p1093[0...n]
Skip speed 3 / Skip speed 3
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [1/min]
Description:
Sets the skip speed/velocity 3.
Dependency:
Refer to: p1091, p1092, p1094, p1101
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: SPEED_ROT
Max
- [1/min]
Data set: CDS
Units group: -
Max
-
Data set: DDS
Units group: SPEED_ROT
Max
210000.000 [1/min]
Data set: DDS
Units group: SPEED_ROT
Max
210000.000 [1/min]
Data set: DDS
Units group: SPEED_ROT
Max
210000.000 [1/min]
Parameters
Parameter list
Access level: 3
Function diagram: 3050,
5030, 5210, 6640, 8010
Unit selection: -
Factory setting
- [1/min]
Access level: 3
Function diagram: 3050
Unit selection: -
Factory setting
1086[0]
Access level: 3
Function diagram: 3050
Unit selection: -
Factory setting
0.000 [1/min]
Access level: 3
Function diagram: 3050
Unit selection: -
Factory setting
0.000 [1/min]
Access level: 3
Function diagram: 3050
Unit selection: -
Factory setting
0.000 [1/min]