p4058[0...1]
TM31 analog inputs, characteristic value y1 / TM31 AI char y1
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-1000.00 [%]
Description:
Sets the normalization characteristic for the analog inputs of terminal module 31 (TM31).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not limit.
p4059[0...1]
TB30 analog inputs, characteristic value x2 / TB30 AI char x2
TB30
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-11.000 [V]
Description:
Sets the normalization characteristic for the analog inputs of terminal board 30 (TB30).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the x coordinate (input voltage in V) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not limit.
p4059[0...1]
TM31 analog inputs, characteristic value x2 / TM31 AI char x2
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-20.000
Description:
Sets the normalization characteristic for the analog inputs of terminal module 31 (TM31).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The units of this parameter (V or mA) depend on the analog input type.
Refer to: p4056
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not limit.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: PERCENT
Max
1000.00 [%]
Data set: -
Units group: VOLTAGE_AC_PP
Max
11.000 [V]
Data set: -
Units group: -
Max
20.000
Parameters
Parameter list
Access level: 2
Function diagram: 9566,
9568
Unit selection: -
Factory setting
0.00 [%]
Access level: 2
Function diagram: 9104
Unit selection: -
Factory setting
10.000 [V]
Access level: 2
Function diagram: 9566,
9568
Unit selection: -
Factory setting
10.000
1-295