Faults and Alarms
List of faults and alarms
Cause:
An invalid data type was detected when evaluating the parameter files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxx-
yyy.ACX or CCxxxyyy.ACX saved on the CompactFlash Card.
Alarm value (r2124, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit. Operation without any restric-
tions is then possible.
After downloading the project, save the parameterization in STARTER using the function "Copy RAM to ROM" or
with p0977 = 1 so that the incorrect parameter files are overwritten on the CompactFlash Card.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowledge
IMMEDIATELY
upon F:
A01047 (F)
ACX: Parameter write error
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the parameters files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX or CCxxxyyy.ACX, saved on
the CompactFlash Card, a parameter value was not able to be transferred into the control unit memory.
Alarm value (r2124, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit. Operation without any restric-
tions is then possible.
After downloading the project, save the parameterization in STARTER using the function "Copy RAM to ROM" or
with p0977 = 1 so that the incorrect parameter files are overwritten on the CompactFlash Card.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowledge
IMMEDIATELY
upon F:
A01049
CU CompactFlash: It is not possible write into the file
Reaction:
NONE
Acknowledge:
NONE
Cause:
It is not possible to write into a write-protective file (PSxxxxxx.acx). The write task was interrupted.
Alarm value (r2124, decimal):
Drive object number.
Remedy:
Check whether the write-protected attribute has been set for the files on the CompactFlash Card under
.../USER/SINAMICS/DATA/... When required, remove write protection and save again (e.g. set p0971 to 1).
F01050
CompactFlash card and device not compatible
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The CompactFlash Card and the device type do not match (e.g. a CompactFlash Card for SINAMICS S is inserted
in SINAMICS G).
Remedy:
- insert the matching CompactFlash Card
- use the matching control unit or power module.
F01051
Drive object type is not available
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The drive object type in conjunction with the selected application-specific perspective is not available. The required
descriptive file (PDxxxyyy.ACX) does not exist on the CompactFlash Card.
Fault value (r0949, decimal):
Index of p0103 and p0107.
See also: p0103, p0107
Remedy:
- for this drive object type (p0107), select a valid application-specific perspective (p0103).
- save the required descriptive file (PDxxxyyy.ACX) on the CompactFlash Card.
See also: p0103, p0107
3-520
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004