Parameters
Parameter list
r0631[0...n]
Motor temperature model, stator core temperature / MotTMod T_iron
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Motor
Min
- [°C]
Description:
Displays the stator core temperature of the motor temperature model.
r0632[0...n]
Motor temperature model, stator winding temperature / MotTMod T_copper
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Motor
Min
- [°C]
Description:
Displays the stator winding temperature of the motor temperature model.
r0633[0...n]
Motor temperature model, rotor temperature / MotTMod T_rotor
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Motor
Min
- [°C]
Description:
Displays the rotor temperature of the motor temperature model.
p0640[0...n]
Current limit / Current limit
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.00 [Aeff]
Description:
Sets the current limit.
Dependency:
Refer to: r0209, p0323
Note:
p0640 is limited to r0209 and p0323. The limit to p0323 is not realized if a value of zero is entered there.
The resulting current limit is displayed in r0067. r0067 may be reduced by the thermal model of the motor module.
The torque and power limits (p1520, p1521, p1530, p1531) matching the current limit are automatically calculated
when exiting the quick commissioning using p3900 > 0 or using the automatic parameterization with p0340 = 3, 5.
p0640 is pre-assigned as follows using the automatic parameterization (p0340 = 1, p3900 > 0):
- for induction motors: p0640 = 1.5 * p0305
- for synchronous motors (only for servo drives, refer to p0107): p0640 = p0338
The parameter is therefore also limited to the maximum converter current (r0209) and the maximum motor current
(p0323). Limiting to p0323 is only realized if p0323 > 0.
The following applies for vector drives (refer to p0107): p0640 is limited to 4.0 * p0305.
1-104
Data set: MDS
Units group: TEMPERATURE
Max
- [°C]
Data set: MDS
Units group: TEMPERATURE
Max
- [°C]
Data set: MDS
Units group: TEMPERATURE
Max
- [°C]
Data set: DDS
Units group: CURRENT_AC_EFF Unit selection: -
Max
10000.00 [Aeff]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 4
Function diagram: 8016
Unit selection: -
Factory setting
- [°C]
Access level: 4
Function diagram: 8016
Unit selection: -
Factory setting
- [°C]
Access level: 4
Function diagram: 8016
Unit selection: -
Factory setting
- [°C]
Access level: 2
Function diagram: 5722,
6640
Factory setting
0.00 [Aeff]