Parameters
Parameter list
p0111
DRIVE-CLiQ basis sampling time selection / DLQ bas clock eval
TM31, VECTOR
Can be changed: C1
Data type: Integer16
P-Group: Control
Min
0
Description:
Selects the basis clock cycle for this drive.
Values:
0:
1:
2:
Dependency:
Refer to: p0110
Note:
All of the drives communicating via the same DRIVE-CLiQ socket of the control unit must have the same basic
clock cycle.
After parameters have been changed, they should be saved and a POWER ON carried-out.
p0112
Sampling times pre-setting p0115 / t_sample for p0115
VECTOR
Can be changed: C1
Data type: Integer16
P-Group: Control
Min
0
Description:
Pre-assignment of the sampling times in p0115.
The clock cycles for the current controller/speed controller/flux controller/setpoint channel are pre-assigned as fol-
lows:
SINAMICS S, servo drive:
p0112 = 2: 125 / 250 / 250 / 4000 µs
p0112 = 3: 125 / 125 / 125 / 4000 µs
p0112 = 4: 62.5 / 62.5 / 62.5 / 1000 µs
SINAMICS S, active infeed:
p0112 = 1: 400 / - / - / 1600 µs
p0112 = 2: 250 / - / - / 2000 µs
p0112 = 3: 125 / - / - / 2000 µs
p0112 = 4: 125 / - / - / 1000 µs
p0112 = 5: 125 / - / - / 500 µs
SINAMICS S, basic infeed:
p0112 = 1: 2000 / - / - / 2000 µs
p0112 = 2: 2000 / - / - / 2000 µs
p0112 = 3: 2000 / - / - / 2000 µs
p0112 = 4: 1000 / - / - / 1000 µs
p0112 = 5: 500 / - / - / 500 µs
SINAMICS S/G, vector drive:
p0112 = 1: 400 / 1600 / 1600 / 1600 µs (for a rated pulse frequency of 1.25 kHz)
p0112 = 2: 250 / 1000 / 2000 / 1000 µs
p0112 = 3: 250 / 1000 / 1000 / 1000 µs (for a rated pulse frequency of 2 kHz)
p0112 = 4: 250 / 500 / 1000 / 500 µs
p0112 = 5: 250 / 250 / 1000 / 250 µs
Values:
0:
1:
2:
3:
4:
5:
1-48
Bas. clock cycle 0
Bas. clock cycle 1
Bas. clock cycle 2
Expert
xLow
Low
Standard
High
xHigh
Data set: -
Units group: -
Max
2
Data set: -
Units group: -
Max
5
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
3