Note:
p2280 = 0: The proportional gain is disabled.
p2285
Technology controller integral action time / Tec_ctr Tn
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
0.000 [s]
Description:
Sets the integral actual time (I component, integrating time constant) of the technology controller.
Note:
p2285 = 0: The integral action time is disabled.
p2289[0...n]
CI: Technology controller pre-control signal / Tec_ctr prectrl
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Unsigned32
P-Group: Technology
Min
-
Description:
Sets the signal source for the pre-control signal of the technology controller.
p2291
Technology controller maximum limiting / Tec_ctr max_limit
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
-200.00 [%]
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution!
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2292
Technology controller minimum limiting / Tec_ctr min_lim
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
-200.00 [%]
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
Caution!
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2293
Technology controller ramp-up/ramp-down time / Tec_ctr ramp up/dn
VECTOR (Tech ctrl) Can be changed: U, T
Data type: Floating Point
P-Group: Technology
Min
0.00 [s]
Description:
Sets the ramp-up and ramp-down time for the maximum and minimum limiting (p2291 and p2292) of the technology
controller.
Dependency:
Refer to: p2291, p2292
Note:
The ramp-up/ramp-down times are referred to 100 %.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: TIME
Max
60.000 [s]
Data set: CDS
Units group: -
Max
-
Data set: -
Units group: PERCENT
Max
200.00 [%]
Data set: -
Units group: PERCENT
Max
200.00 [%]
Data set: -
Units group: TIME
Max
100.00 [s]
Parameters
Parameter list
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
0.000 [s]
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
0
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
100.00 [%]
Access level: 2
Function diagram: 7958
Unit selection: -
Factory setting
0.00 [%]
Access level: 3
Function diagram: 7958
Unit selection: -
Factory setting
1.00 [s]
1-281