Remedy:
- carry-out a POWER ON.
See also: p9916
F33850
Encoder 3: Internal software error in the sensor module
Reaction:
NONE (DCBRAKE, ENCODER)
Acknowledge:
power on
Cause:
Internal software error in the sensor module of encoder 3.
Fault value (r0949, decimal):
1: Background time slice is blocked.
2: Checksum over the code memory is not OK.
10000: OEM memory of the EnDat encoder contains data that cannot be interpreted.
Remedy:
- replace the sensor module.
- if required, upgrade the firmware in the sensor module.
- contact the Hotline.
F33860
CU DRIVE-CLiQ: Telegram error
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communications error between the control unit and the encoder involved.
Fault value (r0949, hexadecimal):
11: CRC error and the receive telegram is too early.
01: CRC error.
12: The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too
early.
02: Telegram is shorter than specified in the length byte or in the receive list.
13: The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too
early.
03: Telegram is longer than specified in the length byte or in the receive list.
14: The length of the receive telegram does not match the receive list and the receive telegram is too early.
04: The length of the receive telegram does not match the receive list.
15: The type of the receive telegram does not match the receive list and the receive telegram is too early.
05: The type of the receive telegram does not match the receive list.
16: The address of the encoder in the telegram and in the receive list does not match and the receive telegram is too
early.
06: The address of the encoder in the telegram and in the receive list do not match.
19: The error bit in the receive telegram is set and the receive telegram is too early.
09: The error bit in the receive telegram is set.
10: The receive telegram is too early.
Remedy:
- carry-out a POWER ON.
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9915
F33885
CU DRIVE-CLiQ: Cyclic data transfer error
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communications error between the control unit and the encoder involved. The nodes do not send and
receive in synchronism.
Fault value (r0949, hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.
1A: Sign-of-life bit in the receive telegram not set and the receive telegram is too early.
21: The cyclic telegram has not been received.
22: Timeout in the telegram receive list.
40: Timeout in the telegram send list.
62: Error at the transition to cyclic operation.
Remedy:
- check the power supply voltage of the component involved.
- carry-out a POWER ON.
- replace the component involved.
See also: p9915