r1547[0...1]
Torque limit for speed controller output / M_max outp n_ctrl
VECTOR (n/M)
Can be changed: -
Data type: Floating Point
P-Group: Control
Min
- [Nm]
Description:
Displays the torque limit to limit the speed controller output.
Index:
[0] = Upper limit
[1] = Lower limit
r1548[0...1]
Stall current limit, torque-generating, maximum / Isq_max stall
VECTOR (n/M)
Can be changed: -
Data type: Floating Point
P-Group: Control
Min
- [Aeff]
Description:
Displays the limit for the torque-generating current component using the stall calculation, the current limit of the
motor module as well as the parameterization in p0640.
Index:
[0] = Upper limit
[1] = Lower limit
p1570[0...n]
CO: Flux setpoint / Flux setpoint
VECTOR (n/M)
Can be changed: U, T
Data type: Floating Point
P-Group: Control
Min
50.0 [%]
Description:
Sets the flux setpoint referred to rated motor flux.
Note:
For p1570 > 100 %, the flux setpoint increases as a function of the load from 100 % (no-load operation) to the set-
ting in p1570 (above rated motor torque).
p1574[0...n]
Voltage reserve dynamic / U_reserve dyn
VECTOR (n/M)
Can be changed: U, T
Data type: Floating Point
P-Group: Control
Min
0 [Veff]
Description:
Sets a dynamic voltage reserve.
Note:
Increasing the reserve reduces the steady-state maximum output voltage (r0071).
p1580[0...n]
Efficiency optimization / Efficiency opt.
VECTOR (n/M)
Can be changed: U, T
Data type: Floating Point
P-Group: Control
Min
0 [%]
Description:
Sets the efficiency optimization. When optimizing the efficiency, the flux setpoint of the closed-loop control is
adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: -
Units group: TORQUE
Max
- [Nm]
Data set: -
Units group: CURRENT_AC_EFF Unit selection: -
Max
- [Aeff]
Data set: DDS
Units group: FLUX_RELATIVE
Max
200.0 [%]
Data set: DDS
Units group: VOLTAGE_AC_EFF Unit selection: -
Max
150 [Veff]
Data set: DDS
Units group: PERCENT
Max
100 [%]
Parameters
Parameter list
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
- [Nm]
Access level: 4
Function diagram: -
Factory setting
- [Aeff]
Access level: 2
Function diagram: 6722
Unit selection: -
Factory setting
100.0 [%]
Access level: 3
Function diagram: 6723,
6724
Factory setting
10 [Veff]
Access level: 2
Function diagram: 6722
Unit selection: -
Factory setting
0 [%]
1-199