Parameters
Parameter list
r4052[0...1]
TM31 analog inputs, actual input voltage/current / TM31 AI input_U/I
TM31
Can be changed: -
Data type: Floating Point
P-Group: Terminals
Min
-
Description:
Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched-in.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The type of analog input AI x (voltage or current input) is set using p4056.
Refer to: p4056
Note:
AI: Analog input
p4053[0...1]
TB30 analog inputs, smoothing time constant / TB30 AI T_smooth
TB30
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
0.0 [ms]
Description:
Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of the terminal board 30
(TB30).
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
AI: Analog input
p4053[0...1]
TM31 analog inputs, smoothing time constant / TM31 AI T_smooth
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
0.0 [ms]
Description:
Sets the smoothing time constant of the 1st-order low pass filter for the analog inputs of terminal module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog input
r4055[0...1]
CO: TB30 analog inputs, actual value in percent / TB30 AI value in %
TB30
Can be changed: -
Data type: Floating Point
P-Group: Terminals
Min
- [%]
Description:
Displays the currently referred input value of the analog inputs of terminal board 30 (TB30).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
1-292
Data set: -
Units group: -
Max
-
Data set: -
Units group: TIME_M3
Max
1000.0 [ms]
Data set: -
Units group: TIME_M3
Max
1000.0 [ms]
Data set: -
Units group: PERCENT
Max
- [%]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 1
Function diagram: 9566,
9568
Unit selection: -
Factory setting
-
Access level: 1
Function diagram: 9104
Unit selection: -
Factory setting
0.0 [ms]
Access level: 1
Function diagram: 9566,
9568
Unit selection: -
Factory setting
0.0 [ms]
Access level: 1
Function diagram: 1790,
9104
Unit selection: -
Factory setting
- [%]

Hide quick links: