Dependency:
For p4810 = 2 the limit only applies to the current setpoint, but not the speed setpoint (offset).
p4830
Function generator time slice cycle / FG time slice
CU
Can be changed: U, T
Data type: Floating Point
P-Group: Trace and function generator
Min
0.03125 [ms]
Description:
Sets the time slice cycle in which the function generator is called.
r7000
Parallel circuit configuration, number of active power modules / No. active PM
VECTOR (Parallel)
Can be changed: -
Data type: Unsigned16
P-Group: Modulation
Min
-
Description:
Displays the active power modules for a parallel circuit configuration.
Dependency:
Refer to: p7001
p7001[0...n]
Parallel circuit configuration, enable power modules / Enable PM
VECTOR (Parallel)
Can be changed: T
Data type: Integer16
P-Group: Modulation
Min
0
Description:
Enables the power modules in the parallel circuit configuration.
Values:
0:
1:
Dependency:
Refer to: r7000
r7002[0...n]
Parallel circuit configuration, status power modules / Status PM
VECTOR (Parallel)
Can be changed: -
Data type: Integer16
P-Group: Modulation
Min
-
Description:
Displays the status of the power modules in the parallel circuit configuration.
Values:
0:
1:
Dependency:
Refer to: r7000, p7001
p7010
Parallel circuit configuration, current dissymmetry alarm threshold / i_dissym A
thresh
VECTOR (Parallel)
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
2 [%]
Description:
Sets the alarm threshold to detect current dissymmetry in the parallel circuit configuration.
The deviation between the measured values and average value is evaluated. The specified value is referred to the
rated power module current (p7251[0]).
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Deactivated
Activated
Pulses inhibited
Pulses enabled
Data set: -
Units group: TIME_M3
Max
2.00000 [ms]
Data set: -
Units group: -
Max
-
Data set: PDS
Units group: -
Max
1
Data set: PDS
Units group: -
Max
-
Data set: -
Units group: PERCENT
Max
100 [%]
Parameters
Parameter list
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0.12500 [ms]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
-
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
1
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
-
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
20 [%]
1-315