p7043[0...n]
Parallel circuit configuration, valve lockout time correction, phase V negative / Comp
t_interl Vneg
VECTOR (Parallel)
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.00 [µs]
Description:
Using this correction time, the valve lockout time in phase V (p1829) is compensated for a negative phase current
for the particular motor module. This therefore takes into account a spread in the valve lockout times of motor mod-
ules in a parallel circuit configuration.
Dependency:
Refer to: p1829
p7044[0...n]
Parallel circuit configuration, valve lockout time correction, phase W positive / Comp
t_interl Wpos
VECTOR (Parallel)
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.00 [µs]
Description:
Using this correction time, the valve lockout time in phase W (p1830) is compensated for a positive phase current
for the particular motor module. This therefore takes into account a spread in the valve lockout times of motor mod-
ules in a parallel circuit configuration.
Dependency:
Refer to: p1830
p7045[0...n]
Parallel circuit configuration, valve lockout time correction, phase W negative /
Comp t_interl Wneg
VECTOR (Parallel)
Can be changed: U, T
Data type: Floating Point
P-Group: Modulation
Min
0.00 [µs]
Description:
Using this correction time, the valve lockout time in phase W (p1830) is compensated for a positive phase current
for the particular motor module. This therefore takes into account a spread in the valve lockout times of motor mod-
ules in a parallel circuit configuration.
Dependency:
Refer to: p1830
r7100[0...99]
Parallel circuit configuration, ring buffer fault/alarm code / Fault/alarm code
VECTOR (Parallel)
Can be changed: -
Data type: Unsigned32
P-Group: Displays, signals
Min
-
Description:
Ring buffer for faults and alarms that have occurred from power modules connected in parallel (motor module,
active line infeed, voltage sensing module).
Displays the fault/alarm code.
Dependency:
Refer to: r7101, r7102, r7103
Note:
The last fault case that occurred is documented in index 0.
The parameter is reset to 0 at POWER ON.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: PDS
Units group: TIME_M6
Max
1000000.00 [µs]
Data set: PDS
Units group: TIME_M6
Max
1000000.00 [µs]
Data set: PDS
Units group: TIME_M6
Max
1000000.00 [µs]
Data set: -
Units group: -
Max
-
Parameters
Parameter list
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0.00 [µs]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0.00 [µs]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0.00 [µs]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
-
1-319