Faults and Alarms
List of faults and alarms
F01505 (A)
BICO: Interconnection cannot be established
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A PROFIBUS telegram has been set (p0922).
An interconnection contained in the telegram, was not able to be established.
Fault value (r0949, decimal):
Parameter receiver that should be changed.
Remedy:
Establish another interconnection.
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F01506 (A)
BICO: No standard telegram
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The standard telegram in p0922 is not maintained and therefore p0922 is set to 999.
Fault value (r0949, decimal):
BICO parameter for which the write attempt was unsuccessful.
Remedy:
Again set the required standard telegram (p0922).
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F01510
BICO: Signal source is not float type
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The selected connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, decimal):
Parameter number to which an interconnection should be made (connector output).
Remedy:
Interconnect this connector input with a connector output having a float data type.
F01511 (A)
BICO: Interconnection between various normalizations
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested interconnection was set up. However, a conversion is made between the BICO output and BICO input
using the reference values.
- the BICO output has different normalized units than the BICO input.
- alarm only for interconnections within a drive object.
Alarm during commissioning and download inactive.
Example:
The BICO output has, as normalized unit, voltage and the BICO input has current.
This means that the factor p2002 (contains the reference value for current) / p2001 (contains the reference value for
voltage) is calculated between the BICO output and BICO input.
Fault value (r0949, decimal):
Parameter number of the BICO input (signal receiver).
Remedy:
No correction needed.
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F01512
BICO: No normalization available
Reaction:
OFF2
Acknowledge:
power on
Cause:
An attempt was made to determine a conversion factor for a normalization that does not exist.
Fault value (r0949, decimal):
Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor.
Remedy:
Apply normalization or check the transfer value.
3-536
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004