Siemens SINAMICS G List Manual page 328

Table of Contents

Advertisement

Parameters
Parameter list
r7251[0...4]
Parallel circuit configuration, rated power module current / PM I_rated
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Drive converter
Min
- [Aeff]
Description:
Displays the rated current of the individual power modules connected in parallel for various load duty cycles.
The sum of the rated currents of all power modules connected in parallel is displayed in r0207.
Index:
[0] = Rating plate
[1] = Load duty cycle with high overload condition
[2] = Load duty cycle with slight overload condition
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
r7252[0...4]
Parallel circuit configuration, maximum power module current / PM I_max
VECTOR (Parallel)
Can be changed: -
Data type: Floating Point
P-Group: Drive converter
Min
- [Aeff]
Description:
Displays the maximum output current of the individual power modules connected in parallel.
The sum of the maximum currents of all power modules connected in parallel is displayed in r0209.
Index:
[0] = Rating plate
[1] = Load duty cycle with high overload condition
[2] = Load duty cycle with slight overload condition
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
p7828
Firmware download component number / FW_download number
CU
Can be changed: U, T
Data type: Unsigned16
P-Group: -
Min
0
Description:
Component number of the DRIVE-CLiQ component for which a firmware download is to be made.
Dependency:
Refer to: p0121, p0141, p0151, p7829
Note:
The downloaded is started by setting p7829 to "1" .
1-328
Data set: -
Units group: CURRENT_AC_EFF Unit selection: -
Max
- [Aeff]
Data set: -
Units group: CURRENT_AC_EFF Unit selection: -
Max
- [Aeff]
Data set: -
Units group: -
Max
399
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 2
Function diagram: -
Factory setting
- [Aeff]
Access level: 2
Function diagram: -
Factory setting
- [Aeff]
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
0