p1042[0...n]
CI: Motorized potentiometer, automatic setpoint / Mop auto setpoint
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
p1043[0...n]
BI: Motorized potentiometer, accept setpoint / Mop accept set val
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for the setting command to accept the setting value for the motorized potentiometer.
Dependency:
Refer to: p1044
p1044[0...n]
CI: Motorized potentiometer, setting value / Mop setting value
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for the setting value for the motorized potentiometer.
Dependency:
Refer to: p1043
Note:
The value becomes effective for a 0/1 edge of the setting command.
r1045
CO: Motorized potentiometer, speed setpoint in front of the ramp-function generator
/ Mop n_set bef. RFG
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Setpoints
Min
- [1/min]
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator.
p1047[0...n]
Motorized potentiometer, ramp-up time / Mop ramp-up time
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [s]
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off
has been activated).
Dependency:
Refer to: p1030, p1048, p1082
Note:
When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
1-142
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Data set: -
Units group: SPEED_ROT
Max
- [1/min]
Data set: DDS
Units group: TIME
Max
1000.000 [s]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 3
Function diagram: 3020
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: 3020
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: 3020
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: 3020
Unit selection: -
Factory setting
- [1/min]
Access level: 2
Function diagram: 3020
Unit selection: -
Factory setting
10.000 [s]