F07511
Drive: Enc. used multiple
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Each encoder may only be assigned to one drive and within a drive must - in each drive data set - either always be
encoder 1, always encoder 2 or always encoder 3. This unique assignment has been violated.
Fault value (r0949, decimal):
Codes the two parameters that refer to the same component number.
First parameter:
Index: First and second decimal position
Parameter number: Third decimal position (1 for p0187, 2 for p0188, 3 for p0189)
Drive number: Fourth and fifth decimal position
Second parameter:
Index: Sixth and seventh decimal position
Parameter number: Eighth decimal position (1 for p0187, 2 for p0188, 3 for p0189)
Drive number: Ninth and tenth decimal position
See also: p0141
Remedy:
Correct the double use of a component number using the two parameters coded in the fault value.
A07512
Drive: Encoder data set changeover not permissible
Reaction:
NONE
Acknowledge:
NONE
Cause:
A changeover of the encoder data set is prepared using p0187, p0188 or p0189. For this firmware release, an
encoder data set changeover is not supported. Commissioning can only be exited with the correct parameterization.
Alarm value (r2124, decimal):
Parameter number with incorrect indices (p0187, p0188 or p0189).
See also: p0187, p0188, p0189
Remedy:
The selectors to the encoder data sets (p0187, p0188, p0189) must, for all data sets, point to the same encoder data
set.
The following must apply:
p0187[0] = p0187[1] = ... = p0187[n]
p0188[0] = p0188[1] = ... = p0188[n]
p0189[0] = p0189[1] = ... = p0189[n]
A07530
Drive: Drive data set not available
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected drive data set is not available (p0837 > p0180). The drive data set was not changed-over.
See also: p0180, p0820, p0821, p0822, p0823, p0824, r0837
Remedy:
- select the existing drive data set.
- set-up additional drive data sets.
A07550 (F, N)
Drive: Not possible to reset encoder parameters
Reaction:
NONE
Acknowledge:
NONE
Cause:
When carrying-out a factory setting (e.g. using p0970 = 1), it was not possible to reset the encoder parameters. The
encoder parameters are directly read out of the encoder via DRIVE-CLiQ.
Alarm value (r2124, decimal):
Component number of the encoder involved.
Remedy:
- repeat the operation.
- check the DRIVE-CLiQ connection.
Reaction upon F:
NONE (DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowledge
IMMEDIATELY (power on)
upon F:
Reaction upon N:
NONE
Acknowledge
NONE
upon N:
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms
3-565