Faults and Alarms
List of faults and alarms
Cause:
The topology comparison has detected a DRIVE-CLiQ component in the actual topology that has been shifted with
respect to the target topology.
Alarm value (r2124, hexadecimal):
Byte 1: Component number of the component shifted in the target topology
The connection in the actual topology where the shifted component was detected, is described in bytes 2, 3 and 4.
Byte 2: Component class
Byte 3: component number
Byte 4: Connection number
Note:
Component class and connection number are described in F01375.
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting the topologies:
- undo the change to the actual topology by changing-over the DRIVE-CLiQ cables.
- commissioning software: Go online, upload the drive unit, adapt the topology offline and download the modified
project.
- automatically remove the topology error (p9904).
A01387
Topology: Comparison shows option slot component shifted
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a option slot component in the actual topology that has been shifted with
respect to the target topology.
Alarm value (r2124, hexadecimal):
Byte 1: Component number of the component shifted in the target topology
The connection in the actual topology where the shifted component was detected, is described in bytes 2, 3 and 4.
Byte 2: Component class
Byte 3: component number
Byte 4: Connection number
Note:
Component class and connection number are described in F01375.
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting the topologies:
- undo the change to the actual topology by changing-over the DRIVE-CLiQ cables.
- commissioning software: Go online, upload the drive unit, adapt the topology offline and download the modified
project.
- automatically remove the topology error (p9904).
A01388
Topology: Comparison shows EnDat encoder shifted
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected an EnDat encoder in the actual topology that has been shifted with respect
to the target topology.
Alarm value (r2124, hexadecimal):
Byte 1: Component number of the component shifted in the target topology
The connection in the actual topology where the shifted component was detected, is described in bytes 2, 3 and 4.
Byte 2: Component class
Byte 3: component number
Byte 4: Connection number
Note:
Component class and connection number are described in F01375.
The drive system run-up is stopped. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting the topologies:
- undo the change to the actual topology by changing-over the DRIVE-CLiQ cables.
- commissioning software: Go online, upload the drive unit, adapt the topology offline and download the modified
project.
- automatically remove the topology error (p9904).
A01389
Topology: Comparison shows motor with DRIVE-CLiQ shifted
Reaction:
NONE
Acknowledge:
NONE
3-530
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004