Remedy:
- check the selected component number (p7828).
- check the DRIVE-CLiQ connection.
- save suitable firmware file for download in the directory /siemens/sinamics/code/sac/.
- after POWER ON has been carried-out again for the DRIVE-CLiQ component, download the firmware again.
A01006
Firmware update DRIVE-CLiQ component required
Reaction:
NONE
Acknowledge:
NONE
Cause:
The firmware of a DRIVE CLiQ component must be updated as there is no suitable firmware or firmware version in
the component for operation with the control unit.
Alarm value (r2124, decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Firmware update using the commissioning software:
The firmware version of all of the components on the "version overview" page can be read in the Project Navigator
under "Configuration" of the associated drive unit and an appropriate firmware update can be carried-out.
Firmware update via parameter:
- take the component number from the alarm value and enter into p7828.
- start the firmware download with p7829 = 1.
A01007
POWER ON DRIVE-CLiQ component required
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ component must be powered-up again (POWER ON) as, for example, the firmware was updated.
Alarm value (r2124, decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Switch-out the power supply of the specified DRIVE-CLiQ component and switch-in again.
F01010
Unknown drive type
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An unknown drive type was found.
Fault value (r0949, decimal):
Drive object number.
Remedy:
Check the EEPROM data of the drive objects.
F01015
Internal software error
Reaction:
OFF2
Acknowledge:
power on
Cause:
An internal software error has occurred.
Fault value (r0949, decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry-out a POWER ON (power off/on) for all components.
- upgrade the firmware release.
- contact the Hotline.
F01030
Monitoring master control: Sign-of-life failure PC
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
For active PC master control, no sign-of-life was received within the monitoring time.
The master control was returned to the active BICO interconnection.
Remedy:
Set the monitoring time higher at the PC/AOP or disable completely.
Notice:
The monitoring time should be set as short as possible. A long monitoring time means a late response when the
communications fail!
The monitoring time is set in milliseconds.
- in the AOP using the Main menu -> Settings -> Control settings -> Timeout monitoring
- In Starter using <Drive> -> Commissioning -> Control panel -> Button "Fetch master control" -> a window is dis-
played in which the monitoring time can be set.