p0606[0...n]
Motor overtemperature timer / Mot TempTimeStage
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.000 [s]
Description:
Sets the timer stage for the alarm threshold for the motor temperature monitoring function.
This timer stage is started when the temperature alarm threshold (p0604) is exceeded.
If the timer stage expires before the temperature in the meantime falls below the alarm threshold, the fault F07011
is output.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer stage has expired, then fault
F07011 is immediately output.
Dependency:
Refer to: p0604, p0605
Refer to: F07011, A07910
Note:
KTY sensor: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC sensor: The timer minimum value has no particular significance.
p0607[0...n]
Temperature sensor fault timer / Sensor fault time
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Motor
Min
0.000 [s]
Description:
Sets the timer stage between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer stage is started. If the sensor fault is still present after the timer stage has
expired, a corresponding fault message is output.
Note:
If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
p0610[0...n]
Response to motor overtemperature condition / Mot temp response
VECTOR
Can be changed: C2, T
Data type: Integer16
P-Group: Motor
Min
0
Description:
Sets the system response when the motor temperature reaches the alarm threshold.
Values:
0:
1:
2:
Dependency:
Refer to: p0601, p0604, p0605
Note:
the I_max reduction is not executed for PTC (p0601 = 1).
The I_max reduction results in a lower output frequency.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
No response, only alarm, no reduction of I_max
Alarm and reduction of I_max and fault (F07011)
Alarm and fault (F07011), no reduction of I_max
Data set: MDS
Units group: TIME
Max
600.000 [s]
Data set: MDS
Units group: TIME
Max
600.000 [s]
Data set: MDS
Units group: -
Max
2
Parameters
Parameter list
Access level: 2
Function diagram: 8016
Unit selection: -
Factory setting
240.000 [s]
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0.100 [s]
Access level: 2
Function diagram: 8016
Unit selection: -
Factory setting
2
1-101