Siemens SINAMICS G List Manual page 116

Table of Contents

Advertisement

Parameters
Parameter list
r0807
BO: Master control active / PcCtrl active
VECTOR
Can be changed: -
Data type: Unsigned8
P-Group: Displays, signals
Min
-
Description:
Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Bit field:
Bit
Signal name
00
Master control active
Dependency:
Refer to: p0806
Note:
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The master control is used from the commissioning software (drive control panel) and from the advanced operator
panel (AOP, local mode).
p0809[0...2]
Copy command data set CDS / Copy CDS
VECTOR
Can be changed: T
Data type: Unsigned8
P-Group: Commands
Min
0
Description:
Copies one command data set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target command data set
[2] = Start copying
Note:
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In Index 1, enter the command data set that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Commands
Min
-
Description:
Sets the signal source to select the command data set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, p0811, p0812, p0813, r0836
Note:
Command data sets are selected using the binector inputs p0810, p0811, p0812 and p0813.
For a command data set, selected using the binector inputs, is displayed in r0836.
The currently effective command data set is displayed in r0050.
A command data set can be copied using p0809.
1-116
Data set: -
Units group: -
Max
-
0 signal
No
Data set: -
Units group: -
Max
15
Data set: -
Units group: -
Max
-
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
-
1 signal
FP
Yes
5030
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: 2578,
8920
Unit selection: -
Factory setting
0