Siemens SINAMICS G List Manual page 595

Table of Contents

Advertisement

Remedy:
Re fault value = 130:
- carry-out safety commissioning routine.
Re fault value = 1000:
- again carry-out safety commissioning routine.
- replace the CompactFlash Card.
Re fault value = 2000:
- check the safety parameters in the motor module and adapt the reference checksum (p9899).
Re fault value = 2003:
- carry-out an acceptance test.
Re fault value = 9999:
- carry-out diagnostics for the other safety-related fault that is present.
Note:
MM: Motor module
SI: Safety Integrated
See also: p9899
F30651
SI MM: Not synchronized with the control unit
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
The Safety Integrated function is requesting synchronization of the safety time slices on the control unit and motor
module. This synchronization routine was not successful.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry-out a POWER ON (power off/on) for all components.
- upgrade the motor module software.
- upgrade the control unit software.
Note:
MM: Motor module
SI: Safety Integrated
F30652
SI MM: Monitoring clock cycle not permissible
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
The Safety Integrated monitoring clock cycle cannot be maintained due to the communication conditions requested
in the system.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, decimal):
Only for internal Siemens troubleshooting.
Remedy:
Upgrade the motor module software.
Note:
MM: Motor module
SI: Safety Integrated
F30655
SI MM: Align monitoring functions
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
An error has occurred when aligning the Safety Integrated monitoring functions on the control unit and motor module.
Control unit and motor module were not able to determine a common set of supported SI monitoring functions.
- there is either a DRIVE-CLIQ communications error or communications have failed.
- Safety Integrated software releases on the control unit and motor module are not compatible with one another.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, hexadecimal):
Only for internal Siemens troubleshooting.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms
3-595