Parameters
Parameter list
Dependency:
Refer to: p2153
p2174[0...n]
Torque threshold value 1 / M_thresh val 1
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Messages
Min
0.00 [Nm]
Description:
Sets the torque/force threshold value for the signal "Torque setpoint < torque threshold value 1" (BO: r2198.10).
Dependency:
Refer to: r2198
p2175[0...n]
Motor locked speed threshold / Mot lock n_thresh
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Messages
Min
0.00 [1/min]
Description:
Sets the speed / velocity threshold for the signal "Motor locked" (BO: r2198.6).
Dependency:
Refer to: p2177, r2198
p2177[0...n]
Motor locked delay time / Mot lock t_del
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Messages
Min
0.000 [s]
Description:
Sets the delay time for the message "Motor locked" (BO: r2198.6).
If "Motor locked" is identified within this time, then ZSW2.6 is set and an appropriate fault is output.
Dependency:
Refer to: p2175, r2198
p2178[0...n]
Motor stalled delay time / Mot stall t_del
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Messages
Min
0.000 [s]
Description:
Sets the delay time for the message "Motor stalled" (BO: r2198.7).
If "Motor stalled" is identified within this time, then ZSW2.7 is set and an appropriate fault is output.
Dependency:
Refer to: r2198
p2181[0...n]
Load monitoring, response / Load monit. resp.
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Integer16
P-Group: Messages
Min
0
Description:
Sets the response when evaluating the load monitoring.
1-266
Data set: DDS
Units group: TORQUE
Max
99999.00 [Nm]
Data set: DDS
Units group: SPEED_ROT
Max
210000.00 [1/min]
Data set: DDS
Units group: TIME
Max
65.000 [s]
Data set: DDS
Units group: TIME
Max
1.000 [s]
Data set: DDS
Units group: -
Max
6
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 2
Function diagram: 8012
Unit selection: -
Factory setting
5.13 [Nm]
Access level: 3
Function diagram: 8012
Unit selection: -
Factory setting
120.00 [1/min]
Access level: 2
Function diagram: 8012
Unit selection: -
Factory setting
1.000 [s]
Access level: 3
Function diagram: 8012
Unit selection: -
Factory setting
0.010 [s]
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
0