Parameters
Parameter list
p4060[0...1]
TB30 analog inputs, characteristic value y2 / TB30 AI char y2
TB30
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-1000.00 [%]
Description:
Sets the normalization characteristic for the analog inputs of terminal board 30 (TB30).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not limit.
p4060[0...1]
TM31 analog inputs, characteristic value y2 / TM31 AI char y2
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
-1000.00 [%]
Description:
Sets the normalization characteristic for the analog inputs of terminal module 31 (TM31).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not limit.
p4061[0...1]
TM31 analog inputs, wire breakage monitoring response threshold / TM31 WireBrk-
Thresh
TM31
Can be changed: U, T
Data type: Floating Point
P-Group: Terminals
Min
0.00 [mA]
Description:
Sets the response threshold for wire-breakage monitoring of the analog inputs of terminal module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
Wire-breakage monitoring is active for the following type of analog input: p4056[x] = 3 (unipolar current input moni-
tors 4 mA ... 20 mA).
Refer to: p4056
p4062[0...1]
TM31 analog inputs, wire breakage monitoring, delay time / TM31 wirebrk t_del
TM31
Can be changed: U, T
Data type: Unsigned16
P-Group: Terminals
Min
0 [ms]
Description:
Sets the delay time for wire-breakage monitoring of the analog inputs on terminal module 31 (TM31).
1-296
Data set: -
Units group: PERCENT
Max
1000.00 [%]
Data set: -
Units group: PERCENT
Max
1000.00 [%]
Data set: -
Units group: CURRENT_DC_M3
Max
20.00 [mA]
Data set: -
Units group: TIME_M3
Max
1000 [ms]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 2
Function diagram: 9104
Unit selection: -
Factory setting
100.00 [%]
Access level: 2
Function diagram: 9566,
9568
Unit selection: -
Factory setting
100.00 [%]
Access level: 2
Function diagram: 9566,
9568
Unit selection: -
Factory setting
2.00 [mA]
Access level: 2
Function diagram: 9566,
9568
Unit selection: -
Factory setting
100 [ms]