Siemens SINAMICS G List Manual page 263

Table of Contents

Advertisement

p2149[0...n]
Monitoring, configuration / Monit config
VECTOR
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Min
0000 bin
Description:
Configuration word for messages and monitoring functions.
Bit field:
Bit
Signal name
00
Enable alarm A07903
Dependency:
Refer to: r2197
Refer to: A07903
Note:
Re bit 00:
Alarm A07903 is output when the bit is set with p2197.7 = 0 (n_set <> n_act).
p2150[0...n]
Hysteresis speed 3 / n_hysteresis 3
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Messages
Min
0.00 [1/min]
Description:
Sets the hysteresis speed/velocity (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
Refer to: p2161, r2197, r2199
p2151[0...n]
CI: Speed setpoint for messages/signals / n_set for msg
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Messages
Min
-
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
Ramp-up/ramp-down completed (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
Refer to: r2197, r2198, r2199
p2153[0...n]
Speed actual value filter time constant / n_act_filt T
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Messages
Min
0 [ms]
Description:
Sets the time constant of the PT1 element to smooth the speed / velocity actual value. The smoothed actual
speed/velocity is compared with the threshold values and is only used for messages and signals.
Dependency:
Refer to: r2169
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: DDS
Units group: -
Max
0001 bin
0 signal
No
Data set: DDS
Units group: SPEED_ROT
Max
300.00 [1/min]
Data set: CDS
Units group: -
Max
-
Data set: DDS
Units group: TIME_M3
Max
1000000 [ms]
Parameters
Parameter list
Access level: 3
Function diagram: 8010
Unit selection: -
Factory setting
0000 bin
1 signal
FP
Yes
8010
Access level: 3
Function diagram: 8010
Unit selection: -
Factory setting
2.00 [1/min]
Access level: 3
Function diagram: 8010
Unit selection: -
Factory setting
1170[0]
Access level: 3
Function diagram: 8010
Unit selection: -
Factory setting
0 [ms]
1-263