p2189[0...n]
Load monitoring torque threshold 3, upper / M_thresh 3 upper
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Floating Point
P-Group: Messages
Min
0.00 [Nm]
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2189 > p2190
Refer to: p2184, p2190
Refer to: A07926
p2190[0...n]
Load monitoring torque threshold 3, lower / M_thresh 3 lower
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Floating Point
P-Group: Messages
Min
0.00 [Nm]
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
p2192[0...n]
Load monitoring, delay time / Load monit t_del
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Floating Point
P-Group: Messages
Min
0.00 [s]
Description:
Sets the delay time to evaluate the load monitoring.
p2194[0...n]
Torque threshold value 2 / M_thresh val 2
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Messages
Min
0.00 [%]
Description:
Sets the torque/force threshold value for the signal "Torque utilization < torque threshold value 2" (BO: r2199.11).
Dependency:
Refer to: r0033, r2199
r2197
CO/BO: Status word monitoring 1 / ZSW monitor 1
VECTOR
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Min
-
Description:
Displays the first status word for monitoring functions.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: DDS
Units group: TORQUE
Max
99999.00 [Nm]
Data set: DDS
Units group: TORQUE
Max
99999.00 [Nm]
Data set: DDS
Units group: TIME
Max
65.00 [s]
Data set: DDS
Units group: PERCENT
Max
100.00 [%]
Data set: -
Units group: -
Max
-
Parameters
Parameter list
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
99999.00 [Nm]
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
0.00 [Nm]
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
10.00 [s]
Access level: 2
Function diagram: 8012
Unit selection: -
Factory setting
90.00 [%]
Access level: 2
Function diagram: 1530,
2534
Unit selection: -
Factory setting
-
1-269