Remedy:
Re fault value = 1 to 999:
- check the crosswise compared data that resulted in a STOP F.
- carry-out a POWER ON (power off/on) for all components.
- upgrade the motor module software.
- upgrade the control unit software.
Re fault value = 1000:
- check the wiring of the safety-relevant input signals on the control unit (contact problems).
Re fault value = 1001, 1002:
- carry-out a POWER ON (power off/on) for all components.
- upgrade the motor module software.
- upgrade the control unit software.
Re fault value = 2000, 2001:
- check the tolerance time SGE changeover and if required, increase the value (p9650, p9850).
- check the wiring of the safety-relevant input signals (contact problems).
- replace the motor module involved.
Note:
MM: Motor module
SI: Safety Integrated
N30620 (F, A)
SI MM: Safe standstill active
Reaction:
NONE
Acknowledge:
NONE
Cause:
The safe standstill function was selected on the motor module and is active.
Note:
This fault does not result in a safety stop response.
Remedy:
None necessary.
Note:
MM: Motor module
SI: Safety Integrated
Reaction upon F:
OFF2
Acknowledge
IMMEDIATELY (power on)
upon F:
Reaction upon A:
NONE
Acknowledge
NONE
upon A:
F30625
SI MM: Sign-of-life error in safety data
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
The Safety Integrated function on the motor module has detected an error in the sign-of-life of the safety data and
initiated a STOP A.
- there is either a DRIVE-CLIQ communications error or communications have failed.
- a time slice overflow of the safety software has occurred.
Fault value (r0949, decimal):
Only for internal Siemens troubleshooting.
Remedy:
- select safe standstill and then de-select again.
- carry-out a POWER ON (power off/on) for all components.
- check whether there is a DRIVE-CLiQ communications error between the control unit and the motor module
involved and if required, carry-out a diagnostics routine for the faults identified.
- de-select all drive functions that are not absolutely necessary.
- reduce the number of drives.
- check the electrical cabinet design and cable routing for EMC compliance
Note:
MM: Motor module
SI: Safety Integrated
F30630
SI MM: Brake control defective
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms