Faults and Alarms
List of faults and alarms
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (refer to p0101).
- it is not permissible that a drive object number is repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
A01321
Topology: Drive object number does not exist in configuration
Reaction:
NONE
Acknowledge:
NONE
Cause:
p0978 contains a drive object number that does not exist.
Alarm value (r2124, decimal):
Index of p0978 under which the drive object number can be determined.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (refer to p0101).
- it is not permissible that a drive object number is repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
A01322
Topology: Drive object number present twice in configuration
Reaction:
NONE
Acknowledge:
NONE
Cause:
a drive object number is present more than once in p0978.
Alarm value (r2124, decimal):
Index of p0978 under which the involved drive object number is located.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (refer to p0101).
- it is not permissible that a drive object number is repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
A01330
Topology: Quick commissioning not possible
Reaction:
NONE
Acknowledge:
NONE
3-524
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004