Faults and Alarms
List of faults and alarms
Cause:
The maximum operating time of the fan in the power module is set in p0252.
This message indicates the following:
Fault value (r0949, decimal):
0: The maximum fan operating time is 500 hours.
1: The maximum fan operating time has been exceeded.
Remedy:
Replace the fan in the power module and reset the operating hours counter to 0 (p0251 = 0).
See also: p0251, p0252
F30600
SI MM: STOP A initiated
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
The Safety Integrated function on the motor module has detected a fault and initiated STOP A (pulse cancellation
via the safety shutdown path of the motor module).
- forced checking procedure of the safety shutdown path of the motor module unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, decimal):
0: Stop request from the control unit.
1005: Pulses cancelled although SH not selected and there is not internal STOP A present.
1010: Pulses enabled although SH is selected or an internal STOP A is present.
9999: Subsequent response to fault F30611.
Remedy:
- select safe standstill and then de-select again.
- check whether the safe standstill function on the control unit is enabled (p9601).
If required, select the safety commissioning mode (p0010), enable the safe standstill function on the control unit and
motor module (p9601, p9801), exist the safety commissioning mode (p0010) and carry-out a POWER ON for all com-
ponents (power-down/power-up).
- replace the motor module involved.
Re fault value = 9999:
- carry-out diagnostics for fault F30611.
Note:
MM: Motor module
SI: Safety Integrated
F30611
SI MM: Defect in a monitoring channel
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (power on)
Cause:
The Safety Integrated function on the motor module has detected a fault in the crosswise data comparison and ini-
tiated a STOP F.
As a result of this fault, after the parameterized transition has expired (p9858), fault F30600 (power module Safety
Integrated: STOP A initiated) is output.
Fault value (r0949, decimal):
0: Stop request from the control unit.
1 to 999:
Number of the crosswise compared data that resulted in this fault.
1: Safety Integrated monitoring clock cycle (r9780, r9880).
2: Safety Integrated enable safety functions (p9601, p9801).
3: Safety Integrated tolerance time SGE changeover (p9650, p9850).
4: Safety Integrated transition period STOP F to STOP A (p9658, p9858).
5: Safety Integrated enable safe brake control (p9602, p9802).
This number is also displayed in r9895.
1000:
Watchdog timer has expired. Within the time of approx. 5 * p9850 too many switching operations have occurred at
the safety-related input signals of the control unit.
1001, 1002: Initialization error, change timer / check timer.
2000: Status of the SH terminals on the control unit and motor module are different.
2001: Feedback signal for safe pulse cancellation on the control unit and motor module are different.
3-592
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004