p1135[0...n]
OFF3 ramp-down time / RFG OFF3 t_ramp-dn
VECTOR
Can be changed: C2, U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note:
This time can be exceeded if the DC-link voltage reaches its maximum value.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Setpoints
Min
0.000 [s]
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1140[0...n]
BI: Enables the ramp-function generator / Enable RFG
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for control word 1 bit 4 (operating condition/disable ramp-function generator).
Dependency:
Refer to: p1141, p1142
Note:
Bit 4 = 0: Inhibits the ramp-function generator (the ramp-function generator output is set to zero)
Bit 4 = 1: Operating condition (the ramp-function generator can be enabled)
p1141[0...n]
BI: Start ramp-function generator / Start RFG
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Setpoints
Min
-
Description:
Sets the signal source for control word 1 bit 5 (enables ramp-function generator/ stops ramp-function generator)
Dependency:
Refer to: p1140, p1142
Note:
Bit 5 = 0: Stop the ramp-function generator (the ramp-function generator output is frozen)
Bit 5 = 1: Enables the ramp-function generator
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: DDS
Units group: TIME
Max
600.000 [s]
Data set: DDS
Units group: TIME
Max
30.000 [s]
Data set: DDS
Units group: TIME
Max
30.000 [s]
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Parameters
Parameter list
Access level: 2
Function diagram: 3060,
3070
Unit selection: -
Factory setting
0.000 [s]
Access level: 2
Function diagram: 3070,
3080
Unit selection: -
Factory setting
0.000 [s]
Access level: 2
Function diagram: 3070
Unit selection: -
Factory setting
0.000 [s]
Access level: 3
Function diagram: 2442,
2443, 2501
Unit selection: -
Factory setting
1
Access level: 3
Function diagram: 2442,
2443, 2501
Unit selection: -
Factory setting
1
1-151