Faults and Alarms
List of faults and alarms
Cause:
An error was detected when downloading a project using the commissioning (start-up) software (e.g. incorrect
parameter value).
For the specified parameter, it was detected that dynamic limits were exceeded that could possibly depend on other
parameters.
Fault value (r0949, decimal):
Low word: Parameter number (16 bits without sign)
Byte 3: Parameter index
Byte 4: Fault detection
0: Parameter number illegal.
1: Parameter value cannot be changed.
2: Lower or upper value limit exceeded.
3: Sub-index incorrect.
4: No array, no sub-index.
5: Data type incorrect.
6: Setting not permitted (only resetting).
7: Descriptive element cannot be changed.
9: Descriptive data not available.
11: No master control.
15: No text array present.
17: Task cannot be executed due to operating status.
20: Illegal value.
21: Response too long.
22: Parameter address illegal.
23: Format illegal.
24: Number of values not consistent.
25: Drive object does not exist.
101: Presently de-activated.
104: Illegal value.
107: Write access not permitted when controller enabled.
108: Units unknown.
109: Write access only in the commissioning state, encoder (p0010 = 4).
110: Write access only in the commissioning state, motor (p0010 = 3).
111: Write access only in the commissioning state, power module (p0010 = 2).
112: Write access only in the quick commissioning mode (p0010 = 1).
113: Write access only in the ready mode (p0010 = 0).
114: Write access only in the commissioning state, parameter reset (p0010 = 30).
115: Write access only in the Safety Integrated commissioning state (p0010 = 95).
116: Write access only in the commissioning state, technological application/units (p0010 = 5).
117: Write access only in the commissioning state (p0010 not equal to 0).
118: Write access only in the commissioning state, download (p0010 = 29).
119: Parameter may not be written into in download.
120: Write access only in the startup state, drive basis configuration (device: p0009 = 3).
121: Write access only in commissioning state Define drive type" (device: p0009 = 2).
122: Write access only in commissioning state Data set basic configuration" (device: p0009 = 4).
123: Write access only in commissioning state "Device Configuration" (device: p0009 = 1).
124: Write access only in commissioning state Device download" (device: p0009 = 29).
125: Write access only in commissioning state Device parameter reset" (device: p0009 = 30).
126: Write access only in commissioning state Device ready" (device: p0009 = 0).
127: Write access only in commissioning state Device" (device: p0009 not equal to 0).
129: Parameter may not be written into in download.
130: Transfer of the master control is inhibited via BI: p0806.
131: Required BICO interconnection not possible, because BICO output does not supply floating value
132: Free BICO interconnection inhibited via p0922.
133: Access method not defined.
200: Below the valid values.
201: Above the valid values.
202: Not accessible from BOP.
203: Cannot be read from BOP.
204: Write access not permitted.
Remedy:
- enter the correct value into the specified parameter.
- identify the parameter that narrows (restricts) the limits of the specified parameter.