Parameters
Parameter list
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2183, p2189, p2190
Refer to: A07926
p2185[0...n]
Load monitoring torque threshold 1, upper / M_thresh 1 upper
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Floating Point
P-Group: Messages
Min
0.00 [Nm]
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2185 > p2186
Refer to: p2182, p2186
Refer to: A07926
p2186[0...n]
Load monitoring torque threshold 1, lower / M_thresh 1 lower
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Floating Point
P-Group: Messages
Min
0.00 [Nm]
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
p2187[0...n]
Load monitoring torque threshold 2, upper / M_thresh 2 upper
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Floating Point
P-Group: Messages
Min
0.00 [Nm]
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
p2188[0...n]
Load monitoring torque threshold 2, lower / M_thresh 2 lower
VECTOR (Extended
Can be changed: U, T
msg)
Data type: Floating Point
P-Group: Messages
Min
0.00 [Nm]
Description:
Sets the speed/torque envelop curve for the load monitoring.
Dependency:
The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
1-268
Data set: DDS
Units group: TORQUE
Max
99999.00 [Nm]
Data set: DDS
Units group: TORQUE
Max
99999.00 [Nm]
Data set: DDS
Units group: TORQUE
Max
99999.00 [Nm]
Data set: DDS
Units group: TORQUE
Max
99999.00 [Nm]
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
99999.00 [Nm]
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
0.00 [Nm]
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
99999.00 [Nm]
Access level: 3
Function diagram: 8013
Unit selection: -
Factory setting
0.00 [Nm]