Faults and Alarms
List of faults and alarms
Remedy:
- carry-out a POWER ON (power off/on) for all components.
- upgrade the motor module software.
- upgrade the control unit software.
- check the electrical cabinet design and cable routing for EMC compliance
Note:
MM: Motor module
SI: Safety Integrated
F30656
SI MM: Incorrect motor module parameter
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
When accessing the Safety Integrated parameters for the motor module on the CompactFlash Card, an error has
occurred.
Note:
This fault results in a STOP A.
Fault value (r0949, decimal):
129: Safety parameters for the motor module corrupted.
131: Internal software error on the control unit.
255: Internal motor module software error.
Remedy:
- re-commission the safety functions.
- upgrade the control unit software.
- upgrade the motor module software.
- replace the CompactFlash Card.
Note:
MM: Motor module
SI: Safety Integrated
F30659
SI MM: Write task for parameter rejected
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (power on)
Cause:
The write task for one or several Safety Integrated parameters on the control unit was rejected.
Note:
This fault does not result in a safety stop response.
Fault value (r0949, decimal):
10: An attempt was made to enable the SH function although this cannot be supported.
11: An attempt was made to enable the SBC function although this cannot be supported.
See also: r9771, r9871
Remedy:
Re fault value = 10, 11:
- check whether there are faults in the safety function alignment between the control unit and the motor module
involved (F01655, F30655) and if required, carry-out diagnostics for the faults involved.
- use a motor module that supports the function safe standstill or safe brake control.
- upgrade the motor module software.
- upgrade the control unit software.
Note:
MM: Motor module
SI: Safety Integrated
F30801
Power module DRIVE-CLiQ: Sign-of-life missing
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the control unit and the power module involved.
Fault value (r0949, hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- replace the component involved.
See also: p9916
F30802
Power module: Time slice overflow
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
3-596
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004