Cause:
The connection to one of the heatsink temperature sensors in the power module is interrupted.
Fault value (r0949, hexadecimal):
Bit 0: Module slot (electronics slot)
Bit 1: Air intake
Bit 2: Inverter 1
Bit 3: Inverter 2
Bit 4: Inverter 3
Bit 5: Inverter 4
Bit 6: Inverter 5
Bit 7: Inverter 6
Bit 8: Rectifier 1
Bit 9: Rectifier 2
See also: r0949
Remedy:
Contact the manufacturer.
F30013
Power module: Temperature sensor heatsink short-circuit
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
The heatsink temperature sensor in the motor module is short-circuited.
Fault value (r0949, hexadecimal):
Bit 0: Module slot (electronics slot)
Bit 1: Air intake
Bit 2: Inverter 1
Bit 3: Inverter 2
Bit 4: Inverter 3
Bit 5: Inverter 4
Bit 6: Inverter 5
Bit 7: Inverter 6
Bit 8: Rectifier 1
Bit 9: Rectifier 2
Remedy:
Contact the manufacturer.
F30017
Power module: Hardware current limit has responded too often
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The hardware current limitation in the relevant phase (see A30031, A30032, A30033) has responded too often. The
number of times the limit has been exceeded depends on the design and type of power module.
For infeed units, the following applies:
- closed-loop control is incorrectly parameterized.
- load on the infeed is too high.
- voltage sensing module incorrectly connected.
- commutating reactor missing or the incorrect type.
- power module defective.
The following applies to motor modules:
- closed-loop control is incorrectly parameterized.
- fault in the motor or in the power cables.
- the power cables exceed the maximum permissible length.
- motor load too high
- power module defective.
Fault value (r0949, binary):
Bit 0: Phase U
Bit 1: Phase V
Bit 2: Phase W
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Faults and Alarms
List of faults and alarms
3-587