Parameters
Parameter list
p1806[0...n]
Filter time constant Vdc correction / T_filt Vdc_corr
VECTOR
Can be changed: U, T
Data type: Floating Point
P-Group: Control
Min
0.0 [ms]
Description:
Sets the filter time constant of the DC link voltage used to calculate the modulation depth.
r1807
Actual DC-link voltage to calculate the modulation depth / VdcActValMod_depth
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [V]
Description:
DC link voltage that is used to convert the setpoint voltage into an equivalent modulation depth.
Note:
P1737 can be used for filtering.
r1808
DC link voltage actual value for V_max calculation / Vdc act val U_max
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Displays, signals
Min
- [V]
Description:
DC link voltage used to determine the maximum possible output voltage.
r1809
Modulator mode actual / Modulator mode act
VECTOR
Can be changed: -
Data type: Integer16
P-Group: Modulation
Min
-
Description:
Displays the effective modulator mode.
Values:
1:
2:
3:
4:
5:
6:
7:
8:
p1817
Minimum ratio, pulse frequency to the output frequency / Min f_puls / f_max
VECTOR
Can be changed: C2
Data type: Floating Point
P-Group: Drive converter
Min
8.3
Description:
Sets the minimum ratio between the pulse frequency and the output frequency.
Notice:
If the ratio between the pulse frequency and the output frequency is reduced, then oscillations can occur in the out-
put current that can result in significant levels of current ripple with the appropriate negative effects.
1-218
Flat top modulation (FLB)
Space vector modulation (SVM)
Edge modulation from 28 Hz; 23:3
Edge modulation from 28 Hz; 19:1
Edge modulation from 60 Hz; 17:3
Edge modulation from 60 Hz; 17:1
Edge modulation from 100 Hz; 9:2
Edge modulation from 100 Hz; 9:1
Data set: DDS
Units group: TIME_M3
Max
10000.0 [ms]
Data set: -
Units group: VOLTAGE_DC
Max
- [V]
Data set: -
Units group: VOLTAGE_DC
Max
- [V]
Data set: -
Units group: -
Max
-
Data set: -
Units group: -
Max
15.0
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
0.0 [ms]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
- [V]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
- [V]
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
-
Access level: 4
Function diagram: -
Unit selection: -
Factory setting
12.5