Page 1
List Manual 12.2004 Edition sinamics SINAMICS G...
Page 3
Preface SINAMICS Parameters Function diagrams SINAMICS G List Manual Faults and Alarms List of Abbreviations Manual References Index Valid as from Drive Software version SINAMICS S Edition 12.2004...
Page 4
The designations in this documentation may be trademarks whose use by third-parties for their own purposes may infringe the rights of the owner. Copyright Siemens AG 2004 All Rights Reserved Exclusion of Liability The reproduction, transmission or use of this document or its contents We have conscientiously checked the contents of this manual to en- is not permitted without express written authority.
Page 5
• SINAMICS S List Manual • SINAMICS S150 Operating Manual This documentation is part of the technical customer documentation for SINAMICS. All documents can be obtained separately. Preface-5 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 6
The contents of this documentation are not part of an earlier or existing agree- ment, a promise, or a legal agreement, nor do they change this. All obligations entered into by Siemens result from the respective contract of sale that contains the complete and sole valid warranty arrangements. These contractual warranty provisions are neither extended nor curbed as a result of the statements made in this documentation.
Page 7
See feedback page at the end of this publication E-mail: motioncontrol.docu@erlf.siemens.de Internet Address Up-to-date information about our products can be found on the Internet at the fol- lowing address: http://www.siemens.com/motioncontrol Preface-7 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 8
Preface Preface-8 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Parameters Content Overview of parameters 1-12 Parameter list 1-23 Parameters for data sets 1-362 1-11 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 13
The following applies to visualization parameters: The fields "Min", "Max" and "Factory setting" are specified with a dash "-" and the relevant unit in square parenthesis. 1-13 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 14
Each parameter can belong to either one, several or all drive objects. The following information relating to "Drive object" and "Function module" can be displayed under the parameter number: 1-14 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 15
This can be one or more states. 1-15 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 16
The required access level can be set via p0003. The system uses the following access levels: 1. Standard 2. Extended 3. Expert 4. Service Note: Parameter p0003 is CU-specific (belongs to control unit). 1-16 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 17
The parameter is included in this function diagram. The structure of the parameter function and its interrelationship with other parameters is shown in the specified function diagram. Example: Function diagram: 3060.3 3060: Function diagram number Signal path (optional) 1-17 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 18
(e. g. depending on converter type, macro, power mod- ule). Description Explanation of the function of a parameter. Values Lists the possible values of a parameter. Recommendation Information about recommended settings. 1-18 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 19
Conditions which need to be fulfilled in connection with this parameter. Also includes special effects which can occur between this parameter and others. see also: List of other relevant parameters. 1-19 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 20
Corresponds to Caution Notice: Corresponds to Important Note: A description of individual safety notices can be found in the appendix to this man- ual (see Safety Information). 1-20 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
6500 6599 External reports 7000 7499 Parallel connection of power modules 7800 7899 EEPROM read/write parameters 8800 8899 Communication board 9400 9499 Parameter consistency and storage 1-21 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 22
Parameters Overview of parameters Table 1-2 Numerical Ranges of Parameters, continued Range Description From 9500 9899 Safety Integrated 9900 9949 Topology 9950 9999 Diagnostics (internal) 1-22 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Parameters Parameter list Parameter list Product: SINAMICS G, Version: V02.20.28.00, Label: ARM_M0475_11, Language: en r0002 Control module, operating display / CU op_display Can be changed: - Access level: 1 Data type: Integer16 Data set: - Function diagram: - P-Group: -...
Page 24
In access level 3 (experts), parameters are included that already require expert knowhow (e.g. knowhow about BICO parameterization). Parameters belonging to access level 4 (service) can only be modified after entering an appropriate code. 1-24 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 25
Sets the device and basic drive commissioning. By appropriately setting this parameter, those parameters are filtered that can be written into in the various commis- sioning steps. 1-25 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 26
For p3900 not equal to 0, at the end of the quick commissioning, this parameter is automatically reset to 0. Procedure for "parameter reset": Set p0010 = 30 and p0970 = 1. 1-26 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 27
The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc- tory intended on the CompactFlash Card. Refer to: p0015, p0700, p1000, p1500 1-27 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 28
Units group: SPEED_ROT Unit selection: - Factory setting - [1/min] - [1/min] - [1/min] Description: Displays the smooth actual value of the motor speed/velocity. Dependency: Refer to: r0063 1-28 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 29
The signal is not suitable as process quantity and may only be used as display quantity. The DC link voltage is available smoothed (r0026) and unsmoothed (r0070). 1-29 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 30
P-Group: Displays, signals Units group: CURRENT_AC_EFF Unit selection: - Factory setting - [Aeff] - [Aeff] - [Aeff] Description: Displays the smoothed torque-generating actual current. Dependency: Refer to: r0078 1-30 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 31
Displays the smoothed torque/force utilization as a percentage. The torque/force utilization is obtained from the required smoothed torque/force referred to the torque/force limit. Dependency: Refer to: r0081 1-31 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 32
Function diagram: 8014 P-Group: Displays, signals Units group: TEMPERATURE Unit selection: - Factory setting - [°C] - [°C] - [°C] Description: Displays the temperatures in the power module. 1-32 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 33
Enable run missing STOP2 enable missing STOP1 enable missing EP terminals enable missing Infeed enable missing Ramp-function generator enable missing Ramp-function generator start missing Setpoint enable missing 1-33 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 34
- the holding brake is closed or has still not been opened. Bit 31 = 1 (enable signal missing), if: - the speed setpoint is entered from jogging 1 or 2. 1-34 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 35
DDS eff., bit 0 DDS eff., bit 1 DDS eff., bit 2 DDS eff., bit 3 DDS eff., bit 4 Dependency: Refer to: p0820, p0821, p0822, p0823, p0824, r0837 1-35 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 36
P-Group: Displays, signals Units group: SPEED_ROT Unit selection: - Factory setting - [1/min] - [1/min] - [1/min] Description: Displays the speed/velocity sensed by the motor encoder (unsmoothed). 1-36 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 37
5300, 5730, 6310, 6730, 6731 P-Group: Displays, signals Units group: FREQUENCY Unit selection: - Factory setting - [Hz] - [Hz] - [Hz] Description: Displays the motor module output frequency. 1-37 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 38
In indices 3 ... 5, the offset currents of the 3 phases, which are added to correct the phase currents, are displayed. The sum of the 3 corrected phase currents is displayed in index 6. 1-38 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 39
P-Group: Modulation Units group: PERCENT Unit selection: - Factory setting - [%] - [%] - [%] Description: Displays the maximum modulation depth. Dependency: Refer to: p1803 1-39 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 40
Units group: CURRENT_AC_EFF Unit selection: - Factory setting - [Aeff] - [Aeff] - [Aeff] Description: Displays the torque/force generating current setpoint. Note: This value is irrelevant for the V/f control mode. 1-40 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 41
The torque/force utilization is obtained from the required smoothed torque/force referred to the torque/force limit. Dependency: Refer to: r0033 Note: The torque utilization is available smoothed (r0033) and unsmoothed (r0081). 1-41 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 42
Factory setting - [V] - [V] - [V] Description: Displays the actual phase voltage. Index: [0] = Phase U [1] = Phase V [2] = Phase W 1-42 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 43
For p0097 = 0, p0099 is automatically set to the factor setting. The setting p0097 = 1 is not possible for chassis-type power modules as well as for SINAMICS G or SINAMICS The setting p0097 = 12 is not possible for booksize power modules.
Page 44
If p0100 is changed, all of the rated motor parameters are reset. Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323, p0335, r0336, r0337, p1800 1-44 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 45
Data set: - Function diagram: - P-Group: Control Units group: - Unit selection: - Factory setting Description: Displays the application-specific view of the individual drive object. 1-45 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 46
TM31 (Terminal Module) 201: TM41 (Terminal Module) 202: TM17 High Feature (Terminal Module) 203: TM15 (Terminal Module) 254: CU-LINK Dependency: Refer to: r0103, p0103, p0107 Refer to: F01051 1-46 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 47
The values of the basic clock cycles are aligned to the number of drives. The factory settings should be kept. After parameters have been changed, they should be saved and a POWER ON carried-out. 1-47 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 48
= 4: 250 / 500 / 1000 / 500 µs p0112 = 5: 250 / 250 / 1000 / 250 µs Values: Expert xLow Standard High xHigh 1-48 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 49
3: Manual setting of the computation deadtime, late transfer 4-6: As for 0-2, however, no early transfers are set for vectors Dependency: Refer to: p0118 Refer to: A02100 1-49 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 50
Only component numbers can be entered into this parameter that correspond to a power module. Dependency: Refer to: r0107 Note: For parallel circuit configurations, the parameter index is assigned to a power module. 1-50 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 51
Unit selection: - Factory setting Description: Sets the number of motor data sets (MDS). Dependency: This parameter is only relevant for servo and vector drives (see p0107). 1-51 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 52
If the encoder evaluation and encoder are integrated (motor with DRIVE-CLiQ), then their component numbers are identical. For an SMC, different component numbers are assigned for the SMC (p0141) and the (actual) encoder (p0142). 1-52 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 53
Detects the terminal module assigned to this drive and data set. Note: While p0154 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate terminal mod- ule. 1-53 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 54
Description: Sets the number of drive data sets (DDS). Note: It is possible to toggle between open-loop and closed-loop control parameters using this data set changeover. 1-54 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 55
Using the parameter, each drive data set (= index) is assigned the associated encoder data (EDS) for encoder 3. The parameter value therefore corresponds to the number of the assigned encoder data set. 1-55 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 56
In the commissioning software, this name cannot be entered using the expert list, but is specified in the configura- tion assistant. The object name can be subsequently modified in the Project Navigator using standard Windows resources. 1-56 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 57
Data set: PDS Function diagram: - P-Group: Drive converter Units group: - Unit selection: - Factory setting Description: Displays the hardware properties of the power module. 1-57 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 58
[2] = Load duty cycle with slight overload condition [3] = S1 load duty cycle [4] = S6 load duty cycle Dependency: The value is displayed in [kW] or [hp]. Refer to: p0100, p0205 1-58 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 59
AC/AC drive units: The RMS value of the phase-to-phase line supply voltage should be entered. DC/AC drive units: The rated DC voltage of the supply busbars should be entered. 1-59 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 60
Factory setting Description: Sets the type of the filter at the motor side. Values: No filter Motor reactor dv/dt filter Sinusoidal filter, Siemens Sinusoidal filter, third-party 1-60 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 61
The parameter is automatically pre-assigned when selecting a filter via (p0230). Refer to: p0230 Note: The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground). 1-61 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 62
Units group: CURRENT_AC_EFF Unit selection: - Factory setting - [Aeff] - [Aeff] - [Aeff] Description: Displays the actual, maximum output current of the power module taking into account de-rating factors. 1-62 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 63
When the threshold value is exceeded, only an overload alarm is output. Dependency: Refer to: r0036, p0290 Refer to: A07805 Note: The I2t fault threshold is 100 %. If this value is exceeded, fault F30005 is output. 1-63 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 64
1FK7 synchronous motor 10000: Motor with DRIVE-CLiQ Dependency: When the motor type is changed, the code number in p0301 may be reset to 0 Refer to: p0301 1-64 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 65
(write protection). The write protection is canceled if the motor type p0300 is set to a non-Siemens motor that matches p0301 (e.g. p0300 = 2 for p0301 = 2xxxx). This also applies to the parameters of the integrated encoder sensing. In this case p0300 can only be set to p0300 = 10000 (read motor parameters) or to the corresponding non-Siemens motor (first digit of the motor code number) in order to be able to cancel the write protection.
Page 66
Refer to: p0100, p0309, r0332 Note: The parameter is not used for synchronous motors (p0300 = 2xx). The parameter is automatically preset for motors from the motor list (p0301). 1-66 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 67
The pole pair width is set in p0315. Refer to: p0310, r0313, p0314 Note: The parameter is automatically preset for motors from the motor list (p0301). 1-67 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 68
1000.00 [mm] 30.00 [mm] Description: Sets the pole pair width of the linear motor. Note: The parameter is automatically preset for motors from the motor list (p0301). 1-68 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 69
For synchronous motors, a value must always be entered for the maximum motor current. p0323 is a motor data. The user-selectable current limit is entered into p0640. 1-69 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 70
For p0309 > 0, this value is converted into the power factor and displayed. Dependency: If p0308 is not entered, the parameter is calculated from the rating plate parameters. 1-70 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 71
- [Hz] - [Hz] - [Hz] Description: Displays the rated frequency of the motor. For p0310 > 0, this value is displayed. Dependency: Refer to: p0311, p0314 1-71 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 72
No calculation Complete calculation Calculation of equivalent circuit diagram parameters Calculation of closed-loop control parameters Calculation of controller parameters Calculation of technological limits and threshold values 1-72 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 73
= 5: --> p1037, p1038, p1520, p1521, p1530, p1531, p1802, p1803, p2140, p2142, p2150, p2162, p2163, p2164, p2175, p2177, p2194 1-73 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 74
= 1 contains the calculations of p0340 = 2, 3, 4, 5 without overwriting the motor parameters from the Sie- mens motor lists (p0301 > 0). p0340 = 2 calculates the motor parameters (p0350 ... p0360), but only if it does involve a Siemens catalog motor (p0301 = 0).
Page 75
(only when the flying restart function is activated and the motor is rotating). After a normal stopping process, the delay time is not active - i.e. after OFF1, OFF3 or JOG 1-75 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 76
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica- tion routine (p1910). Note: The parameter is automatically preset for motors from the motor list (p0301). 1-76 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 77
The following applies for the flux values: p0362 < p0363 < p0364 < p0365 Refer to: p0366 Note: p0362 = 100 % corresponds to the rated motor flux. 1-77 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 78
The following applies for the flux values: p0362 < p0363 < p0364 < p0365 Refer to: p0369 Note: p0365 = 100 % corresponds to the rated motor flux. 1-78 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 79
Sets the third magnetizing current of the saturation characteristic as a [%] referred to the rated magnetizing current (p0331). Dependency: The following applies for the magnetizing currents: p0366 < p0367 < p0368 < p0369 Refer to: p0364 1-79 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 80
Displays the rated motor stator resistance at rated temperature (sum from p0625 and p0627). Dependency: Refer to: p0627 Note: The parameter is not used for synchronous motors (p0300 = 2xx). 1-80 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 81
- [mH] - [mH] - [mH] Description: Displays the magnetizing inductance of the motor. Note: The parameter is not used for synchronous motors (p0300 = 2xx). 1-81 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 82
Displays the actual rotor/secondary section resistance (phase value). The parameter is influenced by the temperature model. Note: This parameter is not used for synchronous motors (p0300 = 2xx). 1-82 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 83
Bit field: Signal name 0 signal 1 signal Linear encoder Absolute value encoder Multiturn encoder Track A/B square-wave Track A/B sinusoidal Track C/D Hall sensor EnDat encoder 1-83 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 84
Unit selection: - Factory setting 0 [nm] 250000000 [nm] 16000 [nm] Description: Sets the scale for a linear encoder. Note: The lowest permissible value is 250 nm. 1-84 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 85
Sets the fine resolution in bits of absolute position actual values for the PROFIBUS encoder interface. Note: This parameter applies to process data Gx_XIST2 when reading the absolute value. 1-85 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 86
Sets the distance in pulses between two zero marks for a rotary encoder. This information is used for zero mark monitoring. Note: For distance-coded zero marks, this means the basic distance. 1-86 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 87
Enters the denominator for the gearbox factor of the encoder evaluation. The gearbox factor specifies the speed ratio between the encoder shaft and motor shaft. Note: Negative gearbox factors should be implemented with p0410. 1-87 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 88
Units group: - Unit selection: - Factory setting 0000 hex FFFF FFFF hex 0000 hex Description: Serial number part 3 of the encoder for the commissioning. 1-88 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 89
In this case, the encoder must automatically support the function (e.g. encoder with EnDat interface). Index: [0] = Encoder 1 [1] = Encoder 2 [2] = Encoder 3 1-89 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 90
Voltage level 5 V Voltage level 24 V Remote sense (only SMC30) Resolver excit. Dependency: Refer to: p0404 Note: ZM: Zero mark This parameter is only used for diagnostics. 1-90 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 91
Displays the actual serial number part 2 of the appropriate encoder. Index: [0] = Encoder 1 [1] = Encoder 2 [2] = Encoder 3 Dependency: Refer to: p0441, p0442, p0443, p0444, p0445, r0460, r0462, r0463, r0464 1-91 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 92
DRIVE-CLiQ basic clock cycle and displayed with sign. Index: [0] = Encoder 1 [1] = Encoder 2 [2] = Encoder 3 1-92 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 93
Factory setting Description: Displays the encoder actual position value Gn_XIST1 according to PROFIdrive. Index: [0] = Encoder 1 [1] = Encoder 2 [2] = Encoder 3 1-93 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 94
Meas. on-the-fly Request absolute value cyclic Request parking encoder Request acknowledge encoder fault Note: The signal source for the encoder control word is set with p0480. 1-94 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 95
Sets the behavior for the ENCODER fault response (motor encoder). This means, for example, if an encoder fault occurs, sensorless operation can be automatically selected with a shutdown behavior that can be selected. 1-95 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 96
An input can only be assigned to one encoder as measuring probe 1, 2 or equivalent zero mark. Exception: The same encoder can be simultaneously used as measuring probe and equivalent zero mark as both functions cannot be simultaneously requested. 1-96 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 97
Trace signal for encoder diagnostics (double word representation). The output signal is selected in p0496. Index: [0] = Encoder 1 [1] = Encoder 2 [2] = Encoder 3 1-97 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 98
Factory setting Description: For controller gains, changes-over the units system between physical and referred (without dimensions) represen- tation types. Values: Physical representation No dimensions (referred) representation type 1-98 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 99
The temperature sensor for the temperature evaluation is set in p0600. For p0600 = 10 (temperature sensor via a BICO interconnection), the setting in p0601 has no significance. 1-99 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 100
200.0 [°C] 155.0 [°C] Description: Sets the fault threshold to monitor the motor temperature. Note: The parameter is automatically preset for motors from the motor list (p0301). 1-100 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 101
Refer to: p0601, p0604, p0605 Note: the I_max reduction is not executed for PTC (p0601 = 1). The I_max reduction results in a lower output frequency. 1-101 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 102
P-Group: Motor identification Units group: RESISTANCE Unit selection: - Factory setting - [Ohm] - [Ohm] - [Ohm] Description: Displays the identified stator resistance after the temperature identification run. 1-102 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 103
P-Group: Motor Units group: TEMPERATURE Unit selection: - Factory setting - [°C] - [°C] - [°C] Description: Displays the ambient temperature of the motor temperature model. 1-103 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 104
(p0323). Limiting to p0323 is only realized if p0323 > 0. The following applies for vector drives (refer to p0107): p0640 is limited to 4.0 * p0305. 1-104 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 105
The ACX file to be run must be created according to the definition for ACX macros and must be saved in the direc- tory intended on the CompactFlash Card. Refer to: p0015, p1000, p1500 Note: BI: Binector input 1-105 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 106
1 signal DI 0 (X122.1) High DI 1 (X122.2) High DI 2 (X122.3) High DI 3 (X122.4) High DI 4 (X132.1) High DI 5 (X132.2) High 1-106 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 107
Units group: - Unit selection: - Factory setting 0000 bin 1111 1111 1111 1111 bin 0000 bin Description: Sets the bidirectional digital inputs/outputs as an input or output. 1-107 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 108
Sets the signal source for terminal DI/DO 11 (X122.11). Note: DI/DO: Bidirectional digital input/output Prerequisite: The DI/DO must be set as an output (p0728.11 = 1). 1-108 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 109
Data set: - Function diagram: 2130, 2131, 2132, 2133 P-Group: Commands Units group: - Unit selection: - Factory setting Description: Displays the status of digital outputs. 1-109 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 110
- [%] - [%] - [%] Description: Displays the actual value of the signal to be output. Index: [0] = T0 [1] = T1 [2] = T2 1-110 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 111
The normalization characteristic for the test sockets is defined using two points. This parameter specifies the y coordinate (output voltage) of the first point on the characteristic. 1-111 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 112
Function diagram: 8134 P-Group: Terminals Units group: - Unit selection: - Factory setting Description: Sets the limit for a signal to be output via test sockets. 1-112 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 113
Sets the gain of a signal output of a physical address via test sockets. Index: [0] = T0 [1] = T1 [2] = T2 Dependency: Changes only become effective if p0776 does not equal 99. Refer to: p0788 1-113 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 114
Unit selection: - Factory setting 0000 bin 1111 1111 1111 1111 bin 0000 bin Description: Sets the setpoint for the input signals in the digital input simulation mode. 1-114 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 115
Dependency: Refer to: r0807 Note: The master control is used from the commissioning software (drive control panel) and from the advanced operator panel (AOP, local mode). 1-115 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 116
For a command data set, selected using the binector inputs, is displayed in r0836. The currently effective command data set is displayed in r0050. A command data set can be copied using p0809. 1-116 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 117
P-Group: Data sets Units group: - Unit selection: - Factory setting [0] 0 [1] 0 [2] 0 Description: Copies a drive data set (DDS) into another. 1-117 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 118
Unit selection: - Factory setting Description: Sets the signal source to select the drive data set, bit 3 (DDS, bit 3). Dependency: Refer to: r0051, r0837 1-118 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 119
Sets the signal source for control word 1 bit 0 (ON/OFF1). Recommenda- When the signal source is set, this does not trigger a response - but only a signal change of the source. tion: 1-119 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 120
Bit 1 = 0: OFF2 (immediate pulse cancellation for active infeed units, pre-charging contactor/line contactor open and power-on inhibit) Bit 1 = 1: No OFF2 (enable is possible) OC: Operating condition 1-120 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 121
Sets the signal source for control word 1 bit 10 (PLC control). Note: Bit 10 = 0: PLC has no master control Bit 10 = 1: Master ctrl by PLC 1-121 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 122
The line contactor monitoring is de-activated if the control signal of the particular drive object is set as the signal source for the feedback signal of the line contactor (BI: p0860 = r0863.1). 1-122 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 123
Drive 3: BI: p0864 with BO: Interconnect r0863.0 from drive 2, etc. The first drive only transfers the operating signal to the next drive after it has reached its ready condition. 1-123 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 124
Setpoint enable from the brake control Note: Bits 0, 1, 2, 4, 5, 6 and 9 are used for status word 1 of the PROFIdrive profile. 1-124 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 125
Unit selection: - Factory setting Description: Displays the operating mode. 1: Closed-loop speed controlled operation with ramp-function generator 3: Closed-loop speed controlled operation without ramp-function generator 1-125 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 126
Data type: Unsigned16 Data set: - Function diagram: 1750, 8060 P-Group: Messages Units group: - Unit selection: - Factory setting Description: This parameter is identical to r0945. 1-126 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 127
Number of fault situations that have occurred since the last reset. Dependency: The fault buffer is deleted (cleared) by setting p0952 to 0. Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136 1-127 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 128
= 42 --> SIEMENS r0964[1] = 5000 --> SINAMICS S CU320 r0964[1] = 5200 --> SINAMICS G CU320 r0964[2] = 102 --> first part of the firmware version V01.02 (second part, refer under index 6) r0964[3] = 2003 --> year 2003 r0964[4] = 1401 -->...
Page 129
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle. Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976). 1-129 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 130
= 9 --> PROFIdrive drive object sub-type class 1 r0975[7] = 0 (reserved) r0975[8] = 0 (reserved) r0975[9] = 0 (reserved) r0975[10] = 600 --> second part, firmware version (complete version: V01.02.06.00) 1-130 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 131
Starts to download parameters saved in a non-volatile fashion with p0977 = 11 Starts to download parameters saved in a non-volatile fashion with p0977 = 12 Starts to download Siemens internal setting 20 Starts to download Siemens internal setting 21...
Page 132
Data set: - Function diagram: 4704 P-Group: Encoder Units group: - Unit selection: - Factory setting Description: Displays the actual position encoder used according to PROFIdrive. 1-132 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 133
Function diagram: - P-Group: - Units group: - Unit selection: - Factory setting Description: Displays the parameters that exist for this drive. Dependency: Refer to: r0980, r0989 1-133 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 134
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be read from a higher-level control system (e.g. PROFIBUS master). 1-134 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 135
-210000.000 [1/min] 210000.000 [1/min] 0.000 [1/min] Description: Sets a value for the fixed speed / velocity setpoint 2. Dependency: Refer to: p1020, p1021, p1022, p1023, r1024, r1197 1-135 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 136
-210000.000 [1/min] 210000.000 [1/min] 0.000 [1/min] Description: Sets a value for the fixed speed / velocity setpoint 7. Dependency: Refer to: p1020, p1021, p1022, p1023, r1024, r1197 1-136 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 137
-210000.000 [1/min] 210000.000 [1/min] 0.000 [1/min] Description: Sets a value for the fixed speed / velocity setpoint 12. Dependency: Refer to: p1020, p1021, p1022, p1023, r1024, r1197 1-137 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 138
Data set: CDS Function diagram: 2505 P-Group: Setpoints Units group: - Unit selection: - Factory setting Description: Sets the signal source to select the speed/velocity fixed setpoint. 1-138 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 139
Refer to: p1070, r1197 Note: If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0). 1-139 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 140
Sets the maximum speed/velocity for the motorized potentiometer. Note: This parameter is automatically pre-assigned in the commissioning phase. The setpoint output from the motorized potentiometer is limited to this value. 1-140 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 141
Dependency: Refer to: p1030, p1035, p1036, p1042 Note: The effectiveness of the internal ramp-function generator can be set in automatic mode. 1-141 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 142
The setpoint is changed from the zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off has been activated). Dependency: Refer to: p1030, p1048, p1082 Note: When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended. 1-142 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 143
When the signal source is set, this does not trigger a response - but only a signal change of the source. tion: Dependency: Refer to: p1059 1-143 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 144
Unit selection: - Factory setting - [1/min] - [1/min] - [1/min] Description: Displays the effective main setpoint. The value shown is the main setpoint after scaling. 1-144 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 145
Sets the lowest possible speed/velocity. This value is not fallen below in operation. Note: The parameter value applies for both motor directions of rotation. In exception cases, the motor can operate below this value (e.g. when reversing). 1-145 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 146
P-Group: Setpoints Units group: SPEED_ROT Unit selection: - Factory setting -210000.000 [1/min] 0.000 [1/min] -210000.000 [1/min] Description: Sets the speed/velocity limit for the negative direction (of rotation). 1-146 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 147
Units group: SPEED_ROT Unit selection: - Factory setting 0.000 [1/min] 210000.000 [1/min] 0.000 [1/min] Description: Sets the skip speed/velocity 3. Dependency: Refer to: p1091, p1092, p1094, p1101 1-147 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 148
Factory setting - [1/min] - [1/min] - [1/min] Description: Displays the speed / velocity setpoint after the minimum limiting. Dependency: Refer to: p1091, p1092, p1093, p1094, p1101 1-148 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 149
999999.000 [s] 10.000 [s] Description: The drive is accelerated from standstill (setpoint = 0) up to the maximum speed/velocity (p1082) in this time. Dependency: Refer to: p1082 1-149 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 150
Cont. smoothing Discontininuous smoothing Dependency: No effect, up to initial rounding-off time p1130) > 0 s. Note: Rounding-off is always active for continuous smoothing. Overshoots may occur. 1-150 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 151
Refer to: p1140, p1142 Note: Bit 5 = 0: Stop the ramp-function generator (the ramp-function generator output is frozen) Bit 5 = 1: Enables the ramp-function generator 1-151 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 152
Sets the signal source for the ramp-function generator setting value. Dependency: The signal source for accepting the setting value is set using parameters. Refer to: p1143 1-152 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 153
Data set: - Function diagram: 2711 P-Group: Commands Units group: - Unit selection: - Factory setting 899.15 Description: Sets the signal source for "setpoint 2 enable". 1-153 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 154
Function diagram: 3080 P-Group: Control Units group: - Unit selection: - Factory setting 0000 bin 0011 bin 0011 bin Description: Sets the configuration for the speed/velocity setpoint. 1-154 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 155
Ramp-function generator held Ramp-function generator tracking active Maximum limit active Note: Re bit 02: The bit is an OR logic operation - bit 00 and bit 01. 1-155 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 156
Notice: For vector control, a value that is too low or too high can cause flying restart to become unstable. 1-156 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 157
Isd_set = 0 A Reserved Search in the positive direction Search Started Current impressed Search interrupted Deviation of the speed adaptation circuit = 0 No Speed control activated 1-157 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 158
This parameter setting is active for p1210 = 1, 4, 6. Refer to: p1210, r1214 Cautiont: A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1). 1-158 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 159
Motor holding brake always open Motor holding braking can be parameterized via BICO just like the sequential control, brake connection Dependency: Refer to: p1216, p1217, p1226, p1227 1-159 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 160
Sets the signal source for a conditional opening of the motor holding brake. Note: [0]: Signal, open brake, AND logic operation, input 1 [1]: Signal, open brake, AND logic operation, input 2 1-160 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 161
1 signal: Brake closed. When braking with 1 feedback signal, the inverted feedback signal is connected to the BICO input for the second feedback signal (p1223). 1-161 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 162
The pulses are then canceled. if the brake control is not activated, the following applies: When the threshold is fallen below, the pulses are cancelled and the drive coasts down. 1-162 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 163
For p1227 = 300.000 s, the following applies: The monitoring is deactivated. This is the pre-setting (default setting) for SINAMICS G. For p1227 = 0.000 s, the following applies: With OFF1 or OFF3 and a ramp-down time = 0, the pulses are immediately cancelled and the motor "coasts" down.
Page 164
If p1254 = 1 (automatic sensing of the switch-in level = on), then the following applies: r1242 = Vdc_max - 50.0 V (Vdc_max: overvoltage threshold of the power module) 1-164 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 165
If several modules are connected to the DC link, then the dynamic factor must be increased corresponding to the ratio of the additional capacitances to the capacitance of the module involved. 1-165 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 166
Units group: - Unit selection: - Factory setting Description: Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller. Values: Automatic detection disabled Automatic detection enabled 1-166 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 167
P-Group: Functions Units group: - Unit selection: - Factory setting 0000 bin 0010 1111 bin 0000 bin Description: Sets the control word for the motor holding brake. 1-167 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 168
Sets the configuration of the controller for the DC link voltage (Vdc controller) in the V/f operating mode. Values: Inhib Vdc ctrl Enables Vdc_max controller Enables Vdc_min controller (kinetic buffering) Enables Vdc_min controller and Vdc_max controller 1-168 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 169
P-Group: Functions Units group: VOLTAGE_DC Unit selection: - Factory setting - [V] - [V] - [V] Description: Displays the switch-in level for the Vdc_min controller (kinetic buffering) 1-169 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 170
Units group: TIME_M3 Unit selection: - Factory setting 0 [ms] 1000 [ms] 10 [ms] Description: Sets the derivative-action time constant for the Vdc controller (DC link voltage controller). 1-170 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 171
Sets the speed threshold for the Vdc-min controller (kinetic buffering). If this value is exceeded a fault is output; the required response can be parameterized . 1-171 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 172
A synchronous motor can only be operated in a V/f control mode (p1300 < 20). During operation (the pulses enabled) the open-loop/closed-loop control mode cannot be changed by changing- over drive data sets. 1-172 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 173
The voltage boost results in a higher motor temperature increase. Note: The voltage boost when accelerating can improve the response to small, positive setpoint changes. Prioritization of the voltage boosts: refer to p1310 1-173 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 174
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310. This parameter specifies the voltage of the second point along the characteristic. Dependency: Refer to: p1310, p1311, p1320, p1321, p1323, p1324, p1325, p1326, p1327 1-174 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 175
For closed-loop vector control, the following applies: Selects the freely programmable characteristic using p1300 = 3. Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1327 1-175 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 176
Prerequisite for a precise slip compensation for p1335 = 100 % are the precise motor parameters (p0350 ... p0360). If the parameters are not precisely known, a precise compensation can be achieved by varying p1335. 1-176 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 177
1.00 [ms] 1000.00 [ms] 20.00 [ms] Description: Sets the filter time constant of the controller for resonance damping with V/f control. Dependency: Refer to: p1300, p1338 1-177 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 178
Units group: VOLTAGE_AC_EFF Unit selection: - Factory setting - [Veff] - [Veff] - [Veff] Description: Displays the amount by which the converter output voltage is reduced. Dependency: Refer to: p1340 1-178 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 179
Unit selection: - Factory setting 0000 bin 1111 1111 1111 1111 bin 1000 0000 0010 0001 bin Description: Sets the configuration for the closed-loop speed control. 1-179 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 180
Data set: - Function diagram: 1530, 2522 P-Group: Control Units group: - Unit selection: - Factory setting Description: Displays the status word of the speed controller. 1-180 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 181
Sets the deadtime to balance the speed/velocity setpoint for active torque/force pre-control. The selected multiplier refers to the speed/velocity controller clock cycle (deadtime= p1428 * p0115[1]). 1-181 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 182
In conjunction with p1433 and p1435, the characteristics (in time) of the P-controlled speed control loop can be sim- ulated. For VECTOR (r0107) the following applies: The reference model is activated with p1400.3 = 1. Refer to: p1433, p1435 1-182 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 183
Displays the speed/velocity setpoint after setpoint limiting for the P component of the speed/velocity controller. For V/f operation, the value that is displayed is of no relevance. 1-183 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 184
- speed/velocity setpoint 2 (p1160). - speed/velocity setpoint for speed/velocity pre-control /(p1430). - setpoint from DSC (for DSC active). - setpoint via PC (for master control active, p3983). 1-184 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 185
Sets the lower starting point of the adaptation range for the additional adaptation of the P gain of the speed/velocity controller. The values are in % and refer to the set source of the adaptation signal. Dependency: Refer to: p1455, p1457, p1458, p1459 1-185 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 186
When automatically calculating the speed controller, only the motor moment of inertia is taken into account (p0341). For higher load moments of inertia (p0342 > 1 or p1498 > 0) we recommend that the speed controller gain is checked. 1-186 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 187
0.00 [1/min] Description: Sets the lower adaptation speed/velocity of the speed/velocity controller. No adaptation is effective below this speed/velocity. Dependency: Refer to: p1460, p1461, p1462, p1463, p1465 1-187 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 188
Sets the P gain for sensorless operation for the speed/velocity controller. Dependency: For VECTOR (r0107) the following applies: For p0528 = 1, the speed controller gain is represented without any dimensions. 1-188 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 189
For VECTOR (r0107) the following applies: The setting value of the speed controller integrator is weighted with the scaling factor of the signal source in p1479. 1-189 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 190
- [1/min] - [1/min] Description: Displays the output signal of the droop calculation. The droop feedback result is subtracted from the speed setpoint when activated (p1492). 1-190 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 191
0.0 [%] 400.0 [%] 100.0 [%] Description: Sets the scaling for the acceleration integrator at low speeds (only for sensorless torque control). Dependency: Refer to: p0341, p0342 1-191 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 192
A change is made to closed-loop torque control if, in p1300, closed-loop torque control was selected or if the selec- tion was made using the changeover source in p1501. it is also possible to change over in operation using p1501. 1-192 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 193
Function diagram: - P-Group: Control Units group: PERCENT Unit selection: - Factory setting -2000.0 [%] 2000.0 [%] 100.0 [%] Description: Sets the scaling for supplementary torque 2. 1-193 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 194
The factory setting depends on p0500. p0500 = 101 --> set to the maximum value Otherwise --> set to the rated value Refer to: p1520, p1522, p1523 1-194 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 195
Sets the scaling for the lower torque limit or the torque limit when regenerating. Dependency: p1400 bit 4 = 0: top / bottom p1400 bit 4 = 1: motoring / regenerating 1-195 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 196
Function diagram: 5640, 6640 P-Group: Control Units group: POWER_P3 Unit selection: - Factory setting 0.00 [kW] 10000.00 [kW] 0.00 [kW] Description: Sets the power limit when motoring. 1-196 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 197
P-Group: Control Units group: CURRENT_AC_EFF Unit selection: - Factory setting - [Aeff] - [Aeff] - [Aeff] Description: Displays the minimum limit for the torque-generating current component. 1-197 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 198
Units group: - Unit selection: - Factory setting Description: Sets the signal source for the scaling of the lower torque limiting to limit the speed controller output. 1-198 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 199
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux. 1-199 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 200
Function diagram: 6724 P-Group: Control Units group: CURRENT_AC_EFF Unit selection: - Factory setting - [Aeff] - [Aeff] - [Aeff] Description: Displays the output of the field weakening controller. 1-200 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 201
For p1610 = 0%, a current setpoint is calculated that corresponds to the no-load case (rated magnetizing current). For p1610 = 100 %, a current setpoint is calculated that corresponds to the rated motor torque. 1-201 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 202
Sets the smoothing time constant for the setpoint of the torque-generating current components. Note: The smoothing time does not become effective until the field-weakening range is reached. 1-202 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 203
1999.0 [Hz] Description: Sets the denominator natural frequency for current setpoint filter 1 (PT2, general filter). Dependency: The current setpoint filters are parameterized with p1656 to p1676. 1-203 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 204
The numerator damping can be determined from the equation for the 3 dB bandwidth: f_3dB bandwidth = 2 * D_numerator * f_bandstop frequency. 1-204 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 205
Factory setting 0.000 10.000 0.700 Description: Sets the numerator damping for current setpoint filter 2. Dependency: The current setpoint filters are parameterized with p1656 to p1676. 1-205 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 206
Units group: TIME_M3 Unit selection: - Factory setting 0.00 [ms] 1000.00 [ms] 2.00 [ms] Description: Sets the integral-action time of the current controller. Dependency: Refer to: p1715 1-206 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 207
Function diagram: - P-Group: Control Units group: PERCENT Unit selection: - Factory setting 0.0 [%] 200.0 [%] 75.0 [%] Description: Sets the scaling of the quadrature arm decoupling 1-207 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 208
5714, 5730, 6714, 6731 P-Group: Control Units group: VOLTAGE_AC_EFF Unit selection: - Factory setting - [Veff] - [Veff] - [Veff] Description: Displays the quadrature-axis component of voltage setpoint Uq. 1-208 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 209
- [%] Description: Signal to initiate stall detection Note: The signal is not calculated while magnetizing and only in the low speed range (below p1755 * p1756). 1-209 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 210
Sets the speed/velocity to change over the motor model to sensorless operation (without encoder). Dependency: Refer to: p1756 Note: The changeover speed applies for the changeover between open-loop and closed-loop control mode. 1-210 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 211
Units group: TIME_M3 Unit selection: - Factory setting 0 [ms] 1000 [ms] 4 [ms] Description: Sets the integral-action time of the controller for speed adaptation with encoder 1-211 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 212
Function diagram: - P-Group: Control Units group: - Unit selection: - Factory setting Description: Displays the effective gain of the integral component of the controller for speed adaptation. 1-212 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 213
Units group: ANGLE Unit selection: - Factory setting - [°] - [°] - [°] Description: Displays the difference between the motor model flux angle and the transformation angle. 1-213 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 214
Units group: - Unit selection: - Factory setting 0.000 1.000 0.100 Description: Sets the proportional gain for the Rs adaptation of the motor model of the induction motor. 1-214 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 215
Factory setting - [Hz] - [Hz] - [Hz] Description: Displays the power-on stator frequency / primary section frequency for the Lh adaptation of the induction motor. 1-215 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 216
Function diagram: - P-Group: Displays, signals Units group: FREQUENCY_P3 Unit selection: - Factory setting - [kHz] - [kHz] - [kHz] Description: Displays the actual converter switching frequency. 1-216 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 217
Unit selection: - Factory setting 0.0 [ms] 10000.0 [ms] 10.0 [ms] Description: Filter time constant for the smoothed modulation index to change over the modulator mode. 1-217 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 218
If the ratio between the pulse frequency and the output frequency is reduced, then oscillations can occur in the out- put current that can result in significant levels of current ripple with the appropriate negative effects. 1-218 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 219
The factor setting of p1832 is automatically set to 0.02 * rated drive converter current (r0207). If the actual operating frequency exceeds the value of p1831, then p1832 is not applied! 1-219 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 220
10.00 1.00 Description: Sets the damping factor for the actual value correction. The factor multiplies the T0/Tsig ratio in the feedback branch of the LR element 1-220 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 221
Refer to: A07980, A07981, A07982, A07983, A07984, A07985, F07986, A07987, A07988, F07990, A07991 Notice: In order to permanently accept the determined settings they must be saved in a non-volatile fashion (p0971, p0977). 1-221 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 222
Identification of static leakage inductance Lsig (r1914) without acceptance Voltage vector input Dependency: "Quick commissioning" must be carried-out (P10 = 1) before executing the motor data identification routine! Refer to: p1900 1-222 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 223
- [ms] - [ms] - [ms] Description: Displays the identified rotor time constant. Index: [0] = Phase U [1] = Phase V [2] = Phase W 1-223 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 224
Unit selection: - Factory setting - [mH] - [mH] - [mH] Description: Displays the nominal stator inductance identified for the 3rd point of the saturation characteristic. 1-224 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 225
Units group: INDUCTANCE_M3 Unit selection: - Factory setting - [mH] - [mH] - [mH] Index: [0] = Phase U [1] = Phase V [2] = Phase W 1-225 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 226
Units group: - Unit selection: - Factory setting 0000 bin 0001 1111 bin 0001 1111 bin Description: Sets the configuration of the automatic speed controller optimization 1-226 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 227
The percentage value is referred to p0310 (rated motor frequency). Dependency: Refer to: p0310, p1959 Refer to: A07983 Note: The saturation characteristics should be determined at an operating point with the lowest possible load. 1-227 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 228
After they have been determined, the values are transferred to p0362 ... p0365. Index: [0] = Value 1 [1] = Value 2 [2] = Value 3 [3] = Value 4 [4] = Value 5 1-228 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 229
Displays the identified moment of inertia of the drive. After it has been determined, the value is transferred to p0341, p0342. Dependency: Refer to: p0341, p0342, p1959 Refer to: A07984 1-229 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 230
Unit selection: - Factory setting Description: Displays the number of pulses determined during the vibration test. Note: A negative signal indicates an incorrect polarity of the encoder signal. 1-230 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 231
The adjustment value determined is saved in p0431. Values: Encoder adjustment de-activated Enc adjust. active Dependency: Refer to: p0431 Note: p1990 is automatically set to 0 after the encoder has been adjusted. 1-231 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 232
All currents specified as relative value are referred to this reference quantity. The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex. 1-232 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 233
P-Group: Displays, signals Units group: - Unit selection: - Factory setting Description: Displays the effective control word 1 (STW1) of the drive for the master control. 1-233 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 234
The serial interface for the debug monitor is COM1 (X140) or COM2 (internal). Value = 0: COM2 (internal) Value = 1: COM1 (X140), PPI is de-activated Note: A change only becomes effective after a POWER ON. 1-234 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 235
P-Group: Communication Units group: - Unit selection: - Factory setting Description: Selects the PZD (actual values) with word format to be sent to the PROFIBUS master. 1-235 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 236
[3] = PZD 4 [4] = PZD 5 Bit field: Signal name 0 signal 1 signal Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 1-236 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 237
Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p2051, p2061 1-237 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 238
Diagnostics display for the PROFIBUS interface. Index: [0] = Master bus address [1] = Master input total length bytes [2] = Master output total length bytes 1-238 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 239
[11] = PZD 12 + 13 [12] = PZD 13 + 14 [13] = PZD 14 + 15 [14] = PZD 15 + 16 Dependency: Refer to: p2051 1-239 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 240
Bit 19 Bit 20 Bit 21 Bit 22 Bit 23 Bit 24 Bit 25 Bit 26 Bit 27 Bit 28 Bit 29 Bit 30 Bit 31 1-240 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 241
Data set: - Function diagram: - P-Group: Communication Units group: - Unit selection: - Factory setting Description: PZD byte offset in the PROFIBUS receive telegram (master output). 1-241 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 242
Data set: - Function diagram: - P-Group: Communication Units group: - Unit selection: - Factory setting Description: PZD byte offset in the PROFIBUS send telegram (master input). 1-242 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 243
Units group: - Unit selection: - Factory setting Description: Selects bits to be sent to the PROFIBUS master. The individual bits are combined to form status word 2. 1-243 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 244
Unit selection: - Factory setting Description: Selects bits to be sent to the PROFIBUS master. The individual bits are combined to form free status word 4. 1-244 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 245
Function diagram: 2472 P-Group: Communication Units group: - Unit selection: - Factory setting Description: Connector output to interconnect the status words to a PROFIBUS PZD send word. 1-245 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 246
Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 1-246 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 247
Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 1-247 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 248
Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p2099 1-248 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 249
Selects the faults for which the fault response should be changed Dependency: The fault is selected and the required response is set under the same index. Refer to: p2101 1-249 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 250
Units group: - Unit selection: - Factory setting Description: Sets the first signal source to acknowledge faults. Note: A fault acknowledgment is triggered with a 0/1 signal. 1-250 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 251
Units group: - Unit selection: - Factory setting Description: Sets the third signal source to acknowledge faults. Note: A fault acknowledgment is triggered with a 0/1 signal. 1-251 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 252
Sets the signal source for external fault 2. Dependency: External fault 2 --> F07861(A) Refer to: F07861 Note: An external fault is triggered with a 1/0 signal. 1-252 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 253
Function diagram: 1750, 8065 P-Group: Messages Units group: - Unit selection: - Factory setting 65535 Description: Number of alarms that have occurred after the last reset. 1-253 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 254
Sets the signal source for external alarm 2. Dependency: External alarm 2 --> A07851(F) Refer to: A07851 Note: An external alarm is triggered with a 1/0 signal. 1-254 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 255
It is not possible to re-parameterize the message type in the following cases: - if there is no existing message number. - if a message is present. 1-255 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 256
Refer to: r2110, r2123, r2124, r2125, r2134, r2145, r2146 Note: Alarm buffer structure (general principle): r2122[0], r2124[0], r2123[0], r2125[0] --> alarm 1 (the oldest) r2122[7], r2124[7], r2123[7], r2125[7] --> Alarm 8 (the latest) 1-256 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 257
It is not possible to re-parameterize the acknowledge mode of a fault in the following cases: - if there is no existing fault number. - the message type is not "fault" (F). - when a fault is present. 1-257 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 258
Bit field: Signal name 0 signal 1 signal Trigger signal p2128[0] Trigger signal p2128[1] Trigger signal p2128[2] Trigger signal p2128[3] Trigger signal p2128[4] Trigger signal p2128[5] 1-258 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 259
Displays additional information about the fault that occurred for float values. Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2136 Note: Displays additional information about the safety fault that has occurred (for float values) 1-259 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 260
Signal name 0 signal 1 signal Acknowledge fault External alarm 1 External alarm 2 External alarm 3 External fault 1 External fault 2 External fault 3 1-260 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 261
Description: Sets the hysteresis speed/velocity (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO: r2199.1). Dependency: Refer to: p2141, r2199 1-261 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 262
The binector input is automatically pre-assigned to r1199.2. The following applies for SERVO: The pre-assignment is only made when the function module "setpoint channel" is activated (r0108.8 = 1). 1-262 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 263
Sets the time constant of the PT1 element to smooth the speed / velocity actual value. The smoothed actual speed/velocity is compared with the threshold values and is only used for messages and signals. Dependency: Refer to: r2169 1-263 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 264
Units group: SPEED_ROT Unit selection: - Factory setting 0.00 [1/min] 60000.00 [1/min] 600.00 [1/min] Description: Sets the hysteresis speed/velocity (bandwidth) for the signal "n_act > n_max" (BO: r2197.6). 1-264 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 265
8010, 8012 P-Group: Messages Units group: SPEED_ROT Unit selection: - Factory setting - [1/min] - [1/min] - [1/min] Description: Displays the smoothed actual speed/velocity for messages/signals. 1-265 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 266
Data type: Integer16 Data set: DDS Function diagram: 8013 P-Group: Messages Units group: - Unit selection: - Factory setting Description: Sets the response when evaluating the load monitoring. 1-266 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 268
0.00 [Nm] Description: Sets the speed/torque envelop curve for the load monitoring. Dependency: The following applies: p2188 < p2187 Refer to: p2183, p2187 Refer to: A07926 1-268 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 269
Data set: - Function diagram: 1530, 2534 P-Group: Messages Units group: - Unit selection: - Factory setting Description: Displays the first status word for monitoring functions. 1-269 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 270
The speed threshold value 3 is set in p2161. Re bit 01: The comparison value is set in p2141. Re bit 11: The torque threshold value 2 is set in p2194. 1-270 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 271
-200.00 [%] 200.00 [%] 30.00 [%] Description: Sets the value for fixed value 4 of the technology controller. Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229 1-271 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 272
-200.00 [%] 200.00 [%] 80.00 [%] Description: Sets the value for fixed value 9 of the technology controller. Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229 1-272 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 273
-200.00 [%] 200.00 [%] 130.00 [%] Description: Sets the value for fixed value 14 of the technology controller. Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229 1-273 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 274
Units group: - Unit selection: - Factory setting Description: Sets the signal source to select the fixed value of the technology controller. Dependency: Refer to: p2220, p2221, p2222 1-274 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 275
Displays the setpoint memory for the motorized potentiometer of the technology controller. For p2230.0 = 1, the last setpoint that was saved is entered after ON. Dependency: Refer to: p2230 1-275 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 276
Sets the starting value for the motorized potentiometer of the technology controller. For p2230.0 = 0, this setpoint is entered after ON. Dependency: Refer to: p2230 1-276 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 277
- [%] - [%] Description: Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the technology controller. Dependency: Refer to: r2245 1-277 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 278
650.00 [s] 1.00 [s] Description: Sets the ramp-up time of the technology controller. Dependency: Refer to: p2258 Note: The ramp-up time is referred to 100 %. 1-278 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 279
Units group: - Unit selection: - Factory setting Description: Sets the technology controller type. Values: D component in the actual value signal D component in the fault signal 1-279 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 280
Function diagram: 7958 P-Group: Technology Units group: - Unit selection: - Factory setting 0.000 1000.000 1.000 Description: Sets the proportional gain (P component) of the technology controller. 1-280 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 281
Sets the ramp-up and ramp-down time for the maximum and minimum limiting (p2291 and p2292) of the technology controller. Dependency: Refer to: p2291, p2292 Note: The ramp-up/ramp-down times are referred to 100 %. 1-281 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 282
Sets a fixed percentage. Dependency: Refer to: p2900, p2930 Note: The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint) 1-282 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 283
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of 0. When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associ- ated with a selected Siemens list motor are not overwritten. p3902[0...n]...
Page 284
Access level: 4 Data type: Integer16 Data set: - Function diagram: - P-Group: - Units group: - Unit selection: - Factory setting Description: Displays the ramp-up state. 1-284 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 285
(p4095.x = 1) to terminal mode (p4095.x = 0). The input signal at terminal DI x or DI/DO x is displayed in bit x of r4021. 1-285 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 286
DI 7 (X530.4) High DI/DO 8 (X541.2) High DI/DO 9 (X541.3) High DI/DO 10 (X541.4) High DI/DO 11 (X541.5) High Note: DI: Digital input DI/DO: Bidirectional digital input/output 1-286 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 287
Signal name 0 signal 1 signal DI/DO 8 (X541.2) Input Output DI/DO 9 (X541.3) Input Output DI/DO 10 (X541.4) Input Output DI/DO 11 (X541.5) Input Output 1-287 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 288
If the signal at the binector input p4031 is high, then terminal COM 1 (X542.5) is connected to NO 1 (X542.6). Note: DO: Digital output NC: Normally closed contact NO: Normally open contact 1-288 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 289
Sets the signal source for terminal DI/DO 10 (X541.4) of terminal module 31 (TM31). Note: DI/DO: Bidirectional digital input/output Prerequisite: The DI/DO must be set as an output (p4028.10 = 1). 1-289 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 290
Function diagram: 9556, 9560, 9562 P-Group: Commands Units group: - Unit selection: - Factory setting Description: Displays the status of the digital outputs of terminal module 31 (TM31). 1-290 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 291
Displays the actual input voltage at the analog inputs of the terminal board 30 (TB30). Index: [0] = AI 0 (X482.1/X482.2) [1] = AI 1 (X482.3/X482.4) Note: AI: Analog input 1-291 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 292
Displays the currently referred input value of the analog inputs of terminal board 30 (TB30). When interconnected, the signals are referred to the reference quantities p200x and p205x. 1-292 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 293
For operation with the load resistor switched-in, the voltage between the differential inputs AI+ and AI- may not exceed 15 V or the impressed current of 60 mA; if this is not carefully observed, the input will be damaged. 1-293 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 294
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic. Index: [0] = AI 0 (X482.1/X482.2) [1] = AI 1 (X482.3/X482.4) Note: The parameters for the characteristic do not limit. 1-294 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 295
Refer to: p4056 Notice: This parameter is automatically overwritten when the analog input type (p4056) is modified. Note: The parameters for the characteristic do not limit. 1-295 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 296
Unit selection: - Factory setting 0 [ms] 1000 [ms] 100 [ms] Description: Sets the delay time for wire-breakage monitoring of the analog inputs on terminal module 31 (TM31). 1-296 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 297
Activates the absolute value generation for the analog input signals of terminal module 31 (TM31). Values: No absolute value generation Absolute value generation switched-in Index: [0] = AI 0 (X521.1/X521.2, S5.0) [1] = AI 1 (X521.3/X521.4, S5.1) 1-297 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 298
P-Group: Terminals Units group: - Unit selection: - Factory setting Description: Sets the signal source for enabling the analog inputs of the terminal board 30 (TB30). 1-298 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 299
Displays the actual referred output value of the analog outputs of the terminal board 30 (TB30). Index: [0] = AO 0 (X482.5/X482.6) [1] = AO 1 (X482.7/X482.8) 1-299 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 300
Factory setting Description: Displays the actual output voltage in V when set as voltage output. Displays the actual output voltage in mA when set as current output. 1-300 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 301
= 1, 4 correspond to a voltage output (p4074, p4078, p4080, p4083 are displayed in V). p4076[x] = 0, 2, 3correspond to a current output (p4074, p4078, p4080, p4083 are displayed in mA). 1-301 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 302
The normalization characteristic for the analog outputs is defined using 2 points. This parameter specifies the y coordinate (output voltage in V) of the 1st value pair of the characteristic. 1-302 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 303
This parameter is automatically overwritten when the analog output type is changed (p4076). Note: This parameter is overwritten if p4076 (type of analog output) is changed. The parameters for the characteristic do not limit. 1-303 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 304
Sets the signal source to invert the analog output signals of terminal module 31 (TM31). Index: [0] = AO 0 (X522.1, X522.2, X522.3) [1] = AO 1 (X522.4, X522.5, X522.6) 1-304 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 305
Unit selection: - Factory setting 0000 bin 0000 1111 1111 1111 bin 0000 bin Description: Sets the simulation mode for the digital inputs of terminal module 31 (TM31). 1-305 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 306
Sets the setpoint for the input signals in the simulation mode of the digital inputs of terminal module 31 (TM31). Bit field: Signal name 0 signal 1 signal DI 0 (X520.1) High DI 1 (X520.2) High 1-306 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 307
The setpoint for the input voltage is specified via p4098. Refer to: p4098 Note: AI: Analog input This parameter is not saved when data is backed-up (p0971, p0977). 1-307 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 308
The sampling times can only be set as an integer multiple of the basic sampling time (p0110, p0111). Refer to: p0009, p0110, p0111 Note: The modified sampling time is not effective until the drive unit is powered-up again. 1-308 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 309
Displays the actual resistance value of the temperature sensor connected at terminal module 31 (TM31). Note: The temperature sensor is connected at terminals X522.7(+) and X522.8(-). The maximum measurable resistance value is approx. 1700 Ohm. 1-309 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 310
The temperature sensor is connected at terminals X522.7(+) and X522.8(-). For an invalid temperature actual value, (e.g. a short-circuit at the sensor input), r4105 = -300 °C is displayed. 1-310 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 311
Connection at speed setpoint after filter and r4818 Connection at current setpoint before filter and r4818 Connection at speed setpoint before filter and r4818 Connection at physical address and r4818 1-311 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 312
Function diagram: - P-Group: Trace and function generator Units group: - Unit selection: - Factory setting Description: Sets the signal to be generated for the function generator. 1-312 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 313
If p4810 = 1, 2, 4: the amplitude is referred to p2002 (rated motor current). If p4810 = 3, 5: the amplitude is referred to p2000 (rated motor speed). 1-313 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 314
P-Group: Trace and function generator Units group: PERCENT Unit selection: - Factory setting 0.00 [%] 10000.00 [%] 100.00 [%] Description: Sets the upper limit for the function generator. 1-314 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 315
Sets the alarm threshold to detect current dissymmetry in the parallel circuit configuration. The deviation between the measured values and average value is evaluated. The specified value is referred to the rated power module current (p7251[0]). 1-315 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 316
Displays the deviation between the measured current actual value of phase W and the average value as peak value. The maximum deviation from the average value is displayed in r7027. Dependency: Refer to: r7020, r7021, r7027 1-316 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 317
Displays the deviation of the measured DC link voltage from the average value. The maximum deviation from the average value is displayed in r7031. Dependency: Refer to: r7031 1-317 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 318
This therefore takes into account a spread in the valve lockout times of motor modules in a parallel circuit configuration. Dependency: Refer to: p1829 1-318 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 319
Refer to: r7101, r7102, r7103 Note: The last fault case that occurred is documented in index 0. The parameter is reset to 0 at POWER ON. 1-319 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 320
Refer to: r7100, r7101, r7102 Note: The last fault case that occurred is documented in index 0. The parameter is reset to 0 at POWER ON. 1-320 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 321
Description: Displays the air intake temperature in the power module for a parallel circuit configuration. The maximum value of all power modules is displayed in r0037[3]. 1-321 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 322
Description: Displays the inverter temperature 4 in the power module for a parallel circuit configuration. The maximum value of all power modules is displayed in r0037[8]. 1-322 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 323
Description: Displays barrier junction temperature 1 in the power module for a parallel circuit configuration. The maximum value of all power modules is displayed in r0037[13]. 1-323 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 324
Description: Displays barrier junction temperature 6 in the power module for a parallel circuit configuration. The maximum value of all power modules is displayed in r0037[18]. 1-324 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 325
- [A] - [A] Description: Displays the measured actual value of phase W as peak value. The summed value of all power modules is displayed in r0069[2]. 1-325 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 326
- [V] - [V] Description: Displays the measured actual value of the DC link voltage. The average value of all power modules is displayed in r0070. 1-326 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 327
[2] = Load duty cycle with slight overload condition [3] = S1 load duty cycle [4] = S6 load duty cycle Dependency: The value is displayed in [kW] or [hp]. Refer to: p0100, p0205 1-327 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 328
Component number of the DRIVE-CLiQ component for which a firmware download is to be made. Dependency: Refer to: p0121, p0141, p0151, p7829 Note: The downloaded is started by setting p7829 to "1" . 1-328 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 329
[3] = [4] = [5] = [6] = [7] = [8] = [9] = [10] = [11] = [12] = [13] = [14] = [15] = 1-329 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 330
Data set: - Function diagram: - P-Group: - Units group: - Unit selection: - Factory setting Description: Indicates the signals contained in the selected telegram (P7830). 1-330 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 331
10660: ENC_ID_SENSOR_STATE 10661: ENC_ID_BASIC_SYSTEM 10662: ENC_ID_REFMARK_STATUS 10663: ENC_ID_DSA_STATUS1_SENSOR 10664: ENC_ID_DSA_RMSTAT_HANDSHAKE 10665: ENC_ID_DSA_CONTROL1_SENSOR 10676: ENC_ID_COUNTCORR_SAW_VALUE 10677: ENC_ID_COUNTCORR_ABS_VALUE 10678: ENC_ID_SAWTOOTH_CORR 10692: ENC_ID_RESISTANCE_CALIB_INSTANT 10693: ENC_ID_SERPROT_POS 10724: ENC_ID_ACT_FUNMAN_FUNCTION 10725: ENC_ID_SAFETY_COUNTER_CRC 1-331 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 332
4 byte unsigned 8 byte float 4 byte double 8 byte mm dd yy HH MM SS MS DOW ASCII string SIMUMERIK frame type SIMUMERIK axis type 1-332 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 333
Unit selection: - Factory setting Description: Parameter to display a DSA signal in the signed-integer format. The associated signal number is represented at the appropriate index in r7831. 1-333 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 334
Unit selection: - Factory setting Description: Parameter to display the units of a DSA signal. The associated signal number is represented at the appropriate index in r7831. 1-334 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 335
Volt seconds / meter Newton seconds / meter Micronewton Liters / minute Cubic centimeter Millimeters / Volt minute Newton/Volt Millivolt peak-to-peak Volt rms Millivolt rms Amps rms 1-335 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 336
Percent 137: Amp / Volt 138: Volt 139: Millivolt 140: Microvolt 141: Amps 142: Milliamps 143: Microamps 144: Milliamps rms 145: Millimeter 146: Nanometer 147: Joules 1-336 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 337
Unit selection: - Factory setting Description: Contains the macros that are available on this drive object for the macro trigger parameter p0015. Dependency: Refer to: p0015 1-337 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 338
Unit selection: - Factory setting Description: Contains the macros that are available on this drive object for the macro trigger parameter p1500. Dependency: Refer to: p1500 1-338 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 339
P-Group: Communication Units group: - Unit selection: - Factory setting Description: Connector output for interconnecting the PZD (setpoints) received from the COMM BOARD in the word format. 1-339 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 340
Data set: - Function diagram: 9208, 9210 P-Group: Communication Units group: - Unit selection: - Factory setting Description: Displays PZD (actual values) sent to COMM BOARD. 1-340 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 341
Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Dependency: Refer to: p8851, p8861 1-341 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 342
P-Group: Communication Units group: - Unit selection: - Factory setting Description: Selects PZD (actual values) to be sent to COMM BOARD in the double word format. 1-342 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 343
Data set: - Function diagram: - P-Group: Communication Units group: - Unit selection: - Factory setting Description: Byte offset of the PZD in the COMM BOARD receive telegram. 1-343 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 344
Units group: - Unit selection: - Factory setting Description: Binector output for bit-serial interconnection of a PZD1 (normally control word 1) word received from the COMM BOARD. 1-344 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 345
9206 P-Group: Communication Units group: - Unit selection: - Factory setting Description: Binector output for bit-serial interconnection of a PZD3 word received from the COMM BOARD.. 1-345 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 346
Displays the number of modified parameters and those that have still not be saved for this drive object. Dependency: Refer to: p0971, p0977 Note: The modified parameters that still need to be saved are internally listed in r9410 ... r9419. 1-346 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 347
Resets the BICO interconnections to other drives to 0, 1 or to the factory setting. Each interconnection can be indi- vidually reset. Values: Set connection to 0 Set connection to 1 (100 %) Set connection to factory setting Finished Dependency: Refer to: r9490, r9491, r9492 1-347 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 348
Refer to: p9601 Note: The following signal sources are permitted: - fixed zero (standard setting) - digital inputs (DI 0 to DI 7 on the control unit 1-348 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 349
Enters the Safety Integrated password. Dependency: Refer to: F01659 Note: It is not permissible to change Safety Integrated parameter settings until the Safety Integrated password has been entered. 1-349 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 350
Displays the safety integrated monitoring functions supported on the control unit and motor module. The control unit determines this display. Bit field: Signal name 0 signal 1 signal SH supported via terminal SBC supported Dependency: Refer to: r9871 1-350 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 351
The status of a group of n drives is, for drives 1 to n - 1 displayed with a delay of one monitoring clock cycle; this is a system-related effect. 1-351 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 352
Unit selection: - Factory setting Description: Displays the checksum over the checked Safety Integrated parameters on the control unit (actual checksum). Dependency: Refer to: p9799, r9898 1-352 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 353
A SGE changeover is not simultaneously effective due to the different runtimes in the two monitoring channels. After an SGE switchover, dynamic data is not subject to a crosswise data comparison during this tolerance time. Dependency: Refer to: p9650 1-353 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 354
1 signal SH supported via terminal SBC supported Dependency: Refer to: r9771 Note: MM: Motor module SBC: Safe brake control SH: Safe standstill SI: Safety Integrated 1-354 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 355
P-Group: Safety Integrated Units group: - Unit selection: - Factory setting Description: Displays the number of the cross-checked data which has caused STOP F on the motor module. 1-355 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 356
The appropriate action should be selected corresponding to the message that is displayed/output. Note: In order to permanently accept the acknowledgement of the fault that can be resolved, then it must be saved in a non-volatile fashion (p0977). 1-356 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 357
Enters the number of the component where the setting of how the actual topology should be compared to the target topology should be changed. Dependency: Refer to: p9908 1-357 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 358
Function diagram: - P-Group: Topology Units group: - Unit selection: - Factory setting 0000 hex 0007 07FF hex 0007 02FF hex Description: Only for internal Siemens service. 1-358 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 359
Activate start license key Dependency: Refer to: p9920 Refer to: A13000, A13001 Note: When the license key has been activated, p9921 is automatically reset to 0. 1-359 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 360
Controls the runtime measurements. Values: Stop runtime measurement Start runtime meas (internal) Clear trace buffer (internal) Activate calculation of remaining computing time Dependency: Refer to: r9976 1-360 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 361
If the system configuration is changed, the measurement must be stopped and re-activated. Index: [0] = Remaining computation time (min) [1] = Remaining computation time (averaged) [2] = Remaining computation time (max) Dependency: Refer to: p9950 1-361 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
References: /IH1/ SINAMICS S120 Commissioning Manual in section "Data Sets" The following list contains those parameters which are dependent on Command Data Sets. Product: SINAMICS G, Version: V02.20.28.00, Label: ARM_M0475_11, Language: en p0700[0...n] Macro binector input (BI) / Macro BI p0820[0...n] BI: Drive data set selection DDS bit 0 / DDS select., bit 0...
Page 363
CI: Technology controller setpoint 2 / Tec_ctr setpoint 2 p2264[0...n] CI: Technology controller actual value / Tec_ctr act val p2289[0...n] CI: Technology controller pre-control signal / Tec_ctr prectrl 1-363 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
SINAMICS S120 Commissioning Manual in section "Data Sets" The following list contains those parameters which are dependent on Drive Data Sets. Product: SINAMICS G, Version: V02.20.28.00, Label: ARM_M0475_11, Language: en p0186[0...n] Motor data sets (MDS) number / MDS number p0187[0...n] Encoder 1 encoder data set number / Enc 1 EDS number p0188[0...n]...
Page 365
I_max voltage controller integral action time / I_max_U_ctrl Tn p1350[0...n] Soft starting / Soft starting p1400[0...n] Speed control configuration / n_ctrl config p1401[0...n] Flux control configuration / F_ctrl config 1-365 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 366
Current setpoint filter 2 denominator natural frequency / I_set_filt 2 fn_n p1664[0...n] Current setpoint filter 2 denominator damping / I_set_filt 2 D_n p1665[0...n] Current setpoint filter 2 numerator natural frequency / I_set_filt 2 fn_z 1-366 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 367
Motor locked delay time / Mot lock t_del p2178[0...n] Motor stalled delay time / Mot stall t_del p2181[0...n] Load monitoring, response / Load monit. resp. 1-367 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 368
CO: Fixed value 1 [%] / Fixed value 1 [%] p2901[0...n] CO: Fixed value 2 [%] / Fixed value 2 [%] p2930[0...n] CO: Fixed value M [Nm] / Fixed value M [Nm] 1-368 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
2-472 2.14 Faults and alarms 2-478 2.15 Test sockets 2-483 2.16 Data sets 2-485 2.17 Terminal Board 30 (TB30) 2-488 2.18 Terminal Module 31 (TM31) 2-493 2-369 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
2470 – Send telegram free interconnection via BICO (p0922 = 999) ....2-406 2-370 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 371
3040 – Direction of rotation limitating and direction of rotation reversal ....2-439 2-371 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 372
8010 – Speed messages ........... 2-473 2-372 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 373
9577 – Sensor monitoring KTY/PTC ......... . 2-503 2-373 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
1020 – Explanation of the symbols (Part 1) 2-375 1021 – Explanation of the symbols (Part 2) 2-376 1024 – Explanation of the symbols (Part 3) 2-377 1025 – Handling BICO-Technology 2-378 2-374 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 375
Function diagrams Explanations of the function diagrams Picture 2-1 1020 – Explanation of the symbols (Part 1) 2-375 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 376
Function diagrams Explanations of the function diagrams Picture 2-2 1021 – Explanation of the symbols (Part 2) 2-376 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 377
Function diagrams Explanations of the function diagrams Picture 2-3 1024 – Explanation of the symbols (Part 3) 2-377 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 378
Function diagrams Explanations of the function diagrams Picture 2-4 1025 – Handling BICO-Technology 2-378 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
1710 – Vector Closed loop current control 2-387 1750 – Monitoring functions, faults, alarms 2-388 1790 – Terminal Board 30 (TB30) 2-389 1840 – Terminal Module 31 (TM31) 2-390 2-379 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 380
Function diagrams Overviews Picture 2-5 1510 – CU320 Input-/Output terminals 2-380 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 381
Function diagrams Overviews Picture 2-6 1520 – PROFIBUS 2-381 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 382
Function diagrams Overviews Picture 2-7 1530 – Internal control/status words 2-382 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 383
Function diagrams Overviews Picture 2-8 1550 – Setpoint channel 2-383 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 384
Function diagrams Overviews Picture 2-9 1680 – Vector Encoder evaluation functions (position, speed, temperature) 2-384 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 385
Function diagrams Overviews Picture 2-10 1690 – Vector V/f-control 2-385 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 386
Function diagrams Overviews Picture 2-11 1700 – Vector Closed-loop speed control and formation of the torque limits 2-386 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 387
Function diagrams Overviews Picture 2-12 1710 – Vector Closed loop current control 2-387 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 388
Function diagrams Overviews Picture 2-13 1750 – Monitoring functions, faults, alarms 2-388 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 389
Function diagrams Overviews Picture 2-14 1790 – Terminal Board 30 (TB30) 2-389 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 390
Function diagrams Overviews Picture 2-15 1840 – Terminal Module 31 (TM31) 2-390 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
2131 – Digital inputs/outputs bidirectional (DI/DO 10 ... DI/DO 11) 2-395 2132 – Digital inputs/outputs bidirectional (DI/DO 12 ... DI/DO 13) 2-396 2133 – Digital inputs/outputs bidirectional (DI/DO 14 ... DI/DO 15) 2-397 2-391 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 392
Function diagrams CU320 input/output terminals Picture 2-16 2100 – Input/output terminals - digital inputs electrically isolated (DI 0 ... DI 3) 2-392 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 393
Function diagrams CU320 input/output terminals Picture 2-17 2120 – Digital inputs electrically isolated (DI 4 ... DI 7) 2-393 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 394
Function diagrams CU320 input/output terminals Picture 2-18 2130 – Digital inputs/outputs bidirectional (DI/DO 8 ... DI/DO 9) 2-394 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 395
Function diagrams CU320 input/output terminals Picture 2-19 2131 – Digital inputs/outputs bidirectional (DI/DO 10 ... DI/DO 11) 2-395 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 396
Function diagrams CU320 input/output terminals Picture 2-20 2132 – Digital inputs/outputs bidirectional (DI/DO 12 ... DI/DO 13) 2-396 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 397
Function diagrams CU320 input/output terminals Picture 2-21 2133 – Digital inputs/outputs bidirectional (DI/DO 14 ... DI/DO 15) 2-397 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
2472 – Status words free interconnection 2-407 2481 – Receive telegram free interconnection via BICO (p0922 = 999) 2-408 2483 – Send telegram free interconnection via BICO (p0922 = 999) 2-409 2-398 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 399
Function diagrams PROFIBUS Picture 2-22 2410 – PROFIBUS address, diagnostics 2-399 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 400
Function diagrams PROFIBUS Picture 2-23 2420 – Telegrams and Process data 2-400 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 401
Function diagrams PROFIBUS Picture 2-24 2440 – Standard/manufacturer-specific receive telegram interconnection 2-401 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 402
Function diagrams PROFIBUS Picture 2-25 2442 – STW1 control word interconnection (p2038 = 0) 2-402 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 403
Function diagrams PROFIBUS Picture 2-26 2450 – Standard/manufacturer-specific send telegram interconnection 2-403 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 404
Function diagrams PROFIBUS Picture 2-27 2452 – ZSW1 Status word interconnection (p2038 = 0) 2-404 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 405
Function diagrams PROFIBUS Picture 2-28 2460 – Receive telegram, free interconnection via BICO (p0922 = 999) 2-405 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 406
Function diagrams PROFIBUS Picture 2-29 2470 – Send telegram free interconnection via BICO (p0922 = 999) 2-406 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 407
Function diagrams PROFIBUS Picture 2-30 2472 – Status words free interconnection 2-407 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 408
Function diagrams PROFIBUS Picture 2-31 2481 – Receive telegram free interconnection via BICO (p0922 = 999) 2-408 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 409
Function diagrams PROFIBUS Picture 2-32 2483 – Send telegram free interconnection via BICO (p0922 = 999) 2-409 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
2-418 2546 – Control word, faults/alarms 2-419 2548 – Status word, faults/alarms 1 and 2 2-420 2578 – Control word command data set selection (CDS) 2-421 2-410 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 411
Function diagrams Internal control/status words Picture 2-33 2501 – Control word sequence control 2-411 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 412
Function diagrams Internal control/status words Picture 2-34 2503 – Status word sequence control 2-412 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 413
Function diagrams Internal control/status words Picture 2-35 2505 – Control word setpoint channel 2-413 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 414
Function diagrams Internal control/status words Picture 2-36 2520 – Control word speed controller 2-414 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 415
Function diagrams Internal control/status words Picture 2-37 2522 – Status word speed controller 2-415 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 416
Function diagrams Internal control/status words Picture 2-38 2534 – Status word monitoring functions 1 2-416 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 417
Function diagrams Internal control/status words Picture 2-39 2536 – Status word monitoring functions 2 2-417 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 418
Function diagrams Internal control/status words Picture 2-40 2537 – Status word monitoring functions 3 2-418 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 419
Function diagrams Internal control/status words Picture 2-41 2546 – Control word, faults/alarms 2-419 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 420
Function diagrams Internal control/status words Picture 2-42 2548 – Status word, faults/alarms 1 and 2 2-420 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 421
Function diagrams Internal control/status words Picture 2-43 2578 – Control word command data set selection (CDS) 2-421 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Function diagrams Sequence control Sequence control Function diagrams 2610 – Control unit 2-423 2614 – Missing enable signals 2-424 2-422 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 423
Function diagrams Sequence control Picture 2-44 2610 – Control unit 2-423 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 424
Function diagrams Sequence control Picture 2-45 2614 – Missing enable signals 2-424 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
2704 – Expanded brake control/standstill detection (r0108.14 = 1) 2-427 2707 – Expanded brake control/opening and closing a brake (r0108.14 = 1) 2-428 2711 – Expanded brake control/signal outputs (r0108.14 = 1) 2-429 2-425 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 426
Function diagrams Motor holding brake Picture 2-46 2701 – Basic brake control (r0108.14 = 0) 2-426 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 427
Function diagrams Motor holding brake Picture 2-47 2704 – Expanded brake control/standstill detection (r0108.14 = 1) 2-427 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 428
Function diagrams Motor holding brake Picture 2-48 2707 – Expanded brake control/opening and closing a brake (r0108.14 = 1) 2-428 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 429
Function diagrams Motor holding brake Picture 2-49 2711 – Expanded brake control/signal outputs (r0108.14 = 1) 2-429 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Safety Integrated Function diagrams 2800 – Parameter manager 2-431 2802 – Monitoring functions and faults/alarms 2-432 2804 – Status words 2-433 2810 – Safe standstill (SH) 2-434 2-430 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 431
Function diagrams Safety Integrated Picture 2-50 2800 – Parameter manager 2-431 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 432
Function diagrams Safety Integrated Picture 2-51 2802 – Monitoring functions and faults/alarms 2-432 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 433
Function diagrams Safety Integrated Picture 2-52 2804 – Status words 2-433 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 434
Function diagrams Safety Integrated Picture 2-53 2810 – Safe standstill (SH) 2-434 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
3050 – Suppression bandwidth and speed limiting 2-440 3060 – Basic ramp-function generator 2-441 3070 – Expanded ramp-function generator 2-442 3080 – Ramp-function generator selection, status word, tracking 2-443 2-435 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 436
Function diagrams Setpoint channel Picture 2-54 3010 – Fixed speed setpoints 2-436 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 437
Function diagrams Setpoint channel Picture 2-55 3020 – Motorized potentiometer 2-437 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 438
Function diagrams Setpoint channel Picture 2-56 3030 – Main/supplementary setpoint, setpoint scaling, jogging 2-438 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 439
Function diagrams Setpoint channel Picture 2-57 3040 – Direction of rotation limitating and direction of rotation reversal 2-439 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 440
Function diagrams Setpoint channel Picture 2-58 3050 – Suppression bandwidth and speed limiting 2-440 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 441
Function diagrams Setpoint channel Picture 2-59 3060 – Basic ramp-function generator 2-441 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 442
Function diagrams Setpoint channel Picture 2-60 3070 – Expanded ramp-function generator 2-442 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 443
Function diagrams Setpoint channel Picture 2-61 3080 – Ramp-function generator selection, status word, tracking 2-443 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
6723 – Field weakening controller, flux controller for induction motors (p0300 = 1) 2-466 6730 – Interface to the motor module for induction motors (p0300 = 1) 2-467 2-444 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 445
Function diagrams Vector control Picture 2-62 6004 – Raw signal and temperature sensing 2-445 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 446
Function diagrams Vector control Picture 2-63 6010 – Speed actual value and rotor position sensing, motor encoder (encoder 1) 2-446 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 447
Function diagrams Vector control Picture 2-64 6030 – Speed setpoint, droop 2-447 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 448
Function diagrams Vector control Picture 2-65 6031 – Pre-control balancing Reference/acceleration modell 2-448 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 449
Function diagrams Vector control Picture 2-66 6040 – Speed control with/without encoder 2-449 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 450
Function diagrams Vector control Picture 2-67 6050 – Kp_n-/Tn_n adaption 2-450 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 451
Function diagrams Vector control Picture 2-68 6060 – Torque setpoint 2-451 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 452
Function diagrams Vector control Picture 2-69 6220 – Vdc_max controller and Vdc_min controller 2-452 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 453
Function diagrams Vector control Picture 2-70 6300 – V/f characteristic and voltage boost 2-453 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 454
Function diagrams Vector control Picture 2-71 6310 – Resonance damping and slip compensation 2-454 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 455
Function diagrams Vector control Picture 2-72 6320 – Vdc_max controller and Vdc_min controller 2-455 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 456
Function diagrams Vector control Picture 2-73 6489 – V/f control status word 1 2-456 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 457
Function diagrams Vector control Picture 2-74 6490 – Speed control configuration 2-457 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 458
Function diagrams Vector control Picture 2-75 6491 – Flux control configuration 2-458 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 459
Function diagrams Vector control Picture 2-76 6492 – Control status word 1 2-459 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 460
Function diagrams Vector control Picture 2-77 6493 – Control status word 3 2-460 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 461
Function diagrams Vector control Picture 2-78 6630 – Upper/lower torque limit 2-461 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 462
Function diagrams Vector control Picture 2-79 6640 – Current/power/torque limits 2-462 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 463
Function diagrams Vector control Picture 2-80 6710 – Current setpoint filter 2-463 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 464
Function diagrams Vector control Picture 2-81 6714 – Iq and Id controllers 2-464 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 465
Function diagrams Vector control Picture 2-82 6722 – Field weakening characteristic, Id setpoint 2-465 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 466
Function diagrams Vector control Picture 2-83 6723 – Field weakening controller, flux controller for induction motors (p0300 = 1) 2-466 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 467
Function diagrams Vector control Picture 2-84 6730 – Interface to the motor module for induction motors (p0300 = 1) 2-467 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Technology controller Function diagrams 7950 – Fixed values (r0108.16 = 1) 2-469 7954 – Motorized potentiometer (r0108.16 = 1) 2-470 7958 – Control (r0108.16 = 1) 2-471 2-468 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 469
Function diagrams Technology controller Picture 2-85 7950 – Fixed values (r0108.16 = 1) 2-469 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 470
Function diagrams Technology controller Picture 2-86 7954 – Motorized potentiometer (r0108.16 = 1) 2-470 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 471
Function diagrams Technology controller Picture 2-87 7958 – Control (r0108.16 = 1) 2-471 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
8012 – Torque messages/signals, motor locked/stalled 2-474 8013 – Load monitoring (r0108.17 = 1) 2-475 8014 – Thermal monitoring, power modulel 2-476 8016 – Thermal motor monitoring 2-477 2-472 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 473
Function diagrams Signals and monitoring functions Picture 2-88 8010 – Speed messages 2-473 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 474
Function diagrams Signals and monitoring functions Picture 2-89 8012 – Torque messages/signals, motor locked/stalled 2-474 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 475
Function diagrams Signals and monitoring functions Picture 2-90 8013 – Load monitoring (r0108.17 = 1) 2-475 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 476
Function diagrams Signals and monitoring functions Picture 2-91 8014 – Thermal monitoring, power modulel 2-476 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 477
Function diagrams Signals and monitoring functions Picture 2-92 8016 – Thermal motor monitoring 2-477 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Faults and alarms Function diagrams 8060 – Fault buffer 2-479 8065 – Alarm buffer 2-480 8070 – Fault/alarm trigger word (r2129) 2-481 8075 – Fault/alarm configuration 2-482 2-478 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 479
Function diagrams Faults and alarms Picture 2-93 8060 – Fault buffer 2-479 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 480
Function diagrams Faults and alarms Picture 2-94 8065 – Alarm buffer 2-480 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 481
Function diagrams Faults and alarms Picture 2-95 8070 – Fault/alarm trigger word (r2129) 2-481 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 482
Function diagrams Faults and alarms Picture 2-96 8075 – Fault/alarm configuration 2-482 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Function diagrams Test sockets 2.15 Test sockets Function diagrams 8134 – Test sockets 2-484 2-483 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 484
Function diagrams Test sockets Picture 2-97 8134 – Test sockets 2-484 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Function diagrams Data sets 2.16 Data sets Function diagrams 8565 – Drive Data Set, DDS 2-486 8570 – Encoder Data Set, EDS 2-487 2-485 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 486
Function diagrams Data sets Picture 2-98 8565 – Drive Data Set, DDS 2-486 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 487
Function diagrams Data sets Picture 2-99 8570 – Encoder Data Set, EDS 2-487 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
9102 – Electrically isolated digital outputs (DO 0 ... DO 3) 2-490 9104 – Analog inputs (AI 0 ... AI 1) 2-491 9106 – Analog outputs (AO 0 ... AO 1) 2-492 2-488 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 489
Function diagrams Terminal Board 30 (TB30) Picture 2-100 9100 – Electrically isolated digital inputs (DI 0 ... DI 3) 2-489 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 490
Function diagrams Terminal Board 30 (TB30) Picture 2-101 9102 – Electrically isolated digital outputs (DO 0 ... DO 3) 2-490 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 491
Function diagrams Terminal Board 30 (TB30) Picture 2-102 9104 – Analog inputs (AI 0 ... AI 1) 2-491 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 492
Function diagrams Terminal Board 30 (TB30) Picture 2-103 9106 – Analog outputs (AO 0 ... AO 1) 2-492 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
9568 – Analog input 1 (AI 1) 2-500 9572 – Analog outputs (AO 0 ... AO 1) 2-501 9576 – Temperature evaluation KTY/PTC 2-502 9577 – Sensor monitoring KTY/PTC 2-503 2-493 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 494
Function diagrams Terminal Module 31 (TM31) Picture 2-104 9550 – Electrically isolated digital inputs (DI 0 ... DI 3) 2-494 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 495
Function diagrams Terminal Module 31 (TM31) Picture 2-105 9552 – Electrically isolated digital inputs (DI 4 ... DI 7) 2-495 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 496
Function diagrams Terminal Module 31 (TM31) Picture 2-106 9556 – Electrically isolated digital relay outputs (DO 0 ... DO 1) 2-496 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 497
Function diagrams Terminal Module 31 (TM31) Picture 2-107 9560 – Bidirectional digital inputs/outputs (DI/DO 8 ... DI/DO 9) 2-497 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 498
Function diagrams Terminal Module 31 (TM31) Picture 2-108 9562 – Bidirectional digital inputs/outputs (DI/DO 10 ... DI/DO 11) 2-498 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 499
Function diagrams Terminal Module 31 (TM31) Picture 2-109 9566 – Analog input 0 (AI 0) 2-499 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 500
Function diagrams Terminal Module 31 (TM31) Picture 2-110 9568 – Analog input 1 (AI 1) 2-500 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 501
Function diagrams Terminal Module 31 (TM31) Picture 2-111 9572 – Analog outputs (AO 0 ... AO 1) 2-501 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 502
Function diagrams Terminal Module 31 (TM31) Picture 2-112 9576 – Temperature evaluation KTY/PTC 2-502 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 503
Function diagrams Terminal Module 31 (TM31) Picture 2-113 9577 – Sensor monitoring KTY/PTC 2-503 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 504
Function diagrams Terminal Module 31 (TM31) 2-504 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 505
Faults and Alarms Content Overview of Faults and Alarms 3-506 List of faults and alarms 3-514 3-505 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
• The alarm is entered in the alarm buffer. How are alarms eliminated? • Alarms are "self acknowledging", that is, they are reset automati- cally when the cause of the alarm has been eliminated. 3-506 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 507
• Power-on disable is activated. Closed-loop torque control (p1300 = 23) • Switchover to speed-controlled operation and other reactions as described for speed-controlled operation. 3-507 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 508
The "Safe Stop" (SH) function must be deselected before these faults are acknowl- edged. READY The fault can be acknowledged only in the READY state. In this state, the DC link is charged and the pulses disabled. 3-508 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 509
• Download with modified structure (e. g. number of drive objects changed). • Power-up after other parameter values have been loaded (e. g. p0976 = 10). • Firmware release upgrade. 3-509 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Information about reaction and acknowledgement are specified independently for a report with adjustable report type (e.g. reaction to F, acknowledgement for F). 3-510 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 511
The alarm value specifies additional, precise information about an alarm. The alarm value is entered in the alarm buffer in r2124[0...7] and specifies addi- tional, precise information about an alarm. 3-511 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 512
Description of the potential methods for eliminating the cause of the active fault or alarm. Warning In individual cases, the servicing and maintenance personnel are responsible for choosing a suitable method for eliminating the cause of faults. 3-512 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Faults and Alarms List of faults and alarms List of faults and alarms Product: SINAMICS G, Version: V02.20.28.00, Label: ARM_M0475_11, Language: en F01000 Internal software error Reaction: OFF2 Acknowledge: power on Cause: An internal software error has occurred. Fault value (r0949, hexadecimal): Only for internal Siemens troubleshooting.
Page 515
- check the selected component number (p7828). - check the DRIVE-CLiQ connection. - save suitable firmware file for download in the directory /siemens/sinamics/code/sac/. - after POWER ON has been carried-out again for the DRIVE-CLiQ component, download the firmware again. A01006...
Page 516
The value for xxx depends on p0977 with which the save operation was started: p0977 = 1, 10, 11, 12 --> xxx = 0, 10, 11, 12 The two most significant bytes are used for internal Siemens troubleshooting. Remedy: Check whether one of the files to be overwritten has the attribute "read only" and change this file attribute into "writ- able".
Page 517
The value for xxx depends on p0977 with which the save operation was started: p0977 = 1, 10, 11, 12 --> xxx = 0, 10, 11, 12 The two most significant bytes are used for internal Siemens troubleshooting. Remedy: Check whether one of the files to be overwritten (PSxxxyyy.*, CAxxxyyy.*, CCxxxyyy.*) has the attribute "read only"...
Page 518
204: Write access not permitted. Remedy: - enter the correct value into the specified parameter. - identify the parameter that narrows (restricts) the limits of the specified parameter. 3-518 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 519
= 1 so that the incorrect parameter files are overwritten on the CompactFlash Card. A01046 (F) CU CompactFlash: Configuration data invalid Reaction: NONE Acknowledge: NONE 3-519 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 520
- for this drive object type (p0107), select a valid application-specific perspective (p0103). - save the required descriptive file (PDxxxyyy.ACX) on the CompactFlash Card. See also: p0103, p0107 3-520 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 521
NONE Acknowledge: IMMEDIATELY Cause: More than one SINAMICS G power module type is being operated from the control unit. Fault value (r0949, decimal): Number of the second drive with a SINAMICS G power module type. Remedy: Only one SINAMICS G drive type is permitted.
Page 522
Only for internal Siemens troubleshooting. Remedy: Increase the basic clock cycle of DRIVE-CLiQ communications. See also: p0112 F01250 CU: CU-EEPROM incorrect read-only data Reaction: NONE (OFF2) Acknowledge: power on 3-522 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 523
Cause: A drive object number is missing in p0978 Alarm value (r2124, decimal): Index of p0101 under which the missing drive object number can be determined. 3-523 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 524
- by entering a 0, the drive objects with PZD are separated from those without PZD. A01330 Topology: Quick commissioning not possible Reaction: NONE Acknowledge: NONE 3-524 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 525
Byte 1 = 5: The component is not permissible for SERVO. - byte 2 = 1: SINAMICS G available. - byte 2 = 2: Chassis available. - high word = preliminary component number of the 1st component found that resulted in the fault.
Page 526
The fault only occurs if the topology was commissioned using the automatic internal device mechanism and not using the commissioning software. Fault value (r0949, decimal): Only for internal Siemens troubleshooting. See also: r0098, p0099 3-526 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 527
Change the configuration. Connect less than 199 components to the control unit. Re fault value = 2: Remove the component with unknown component type. F01375 Topology: Actual topology duplicate connection between two components Reaction: NONE Acknowledge: IMMEDIATELY 3-527 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 528
- commissioning software: Go online, upload the drive unit, adapt the topology offline and download the modified project. - automatically remove the topology error (p9904). A01382 Topology: Comparison shows sensor module shifted Reaction: NONE Acknowledge: NONE 3-528 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 529
- commissioning software: Go online, upload the drive unit, adapt the topology offline and download the modified project. - automatically remove the topology error (p9904). A01386 Topology: Comparison shows DRIVE-CLiQ component shifted Reaction: NONE Acknowledge: NONE 3-529 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 530
- commissioning software: Go online, upload the drive unit, adapt the topology offline and download the modified project. - automatically remove the topology error (p9904). A01389 Topology: Comparison shows motor with DRIVE-CLiQ shifted Reaction: NONE Acknowledge: NONE 3-530 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 531
- parameterize the topology comparison of all components (p9906). - parameterize the topology comparison of one components (p9907, p9908). A01421 Topology: Comparison, different components Reaction: NONE Acknowledge: NONE 3-531 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 532
- download the target topology that matches the actual topology (commissioning software). - automatically remove the topology error (p9904). See also: p9904 A01429 Topology: Comparison shows connection is different for more than component Reaction: NONE Acknowledge: NONE 3-532 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 533
Then, download the target topology again using the commissioning software. A01481 Topology: Comparison shows power module not present in the actual topology Reaction: NONE Acknowledge: NONE 3-533 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 534
- check that the actual topology matches the target topology and if required, change over. - check DRIVE-CLiQ cables for interruption and contact problems. A01486 Topology: Comparison shows DRIVE-CLiQ not present in the actual topology Reaction: NONE Acknowledge: NONE 3-534 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 535
- check that the actual topology matches the target topology and if required, change over. - check DRIVE-CLiQ cables for interruption and contact problems. 3-535 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 536
Fault value (r0949, decimal): Unit (e.g. corresponding to SPEED) for which an attempt was made to determine a factor. Remedy: Apply normalization or check the transfer value. 3-536 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 537
1010: Pulses enabled although SH is selected or an internal STOP A is present. 1015: Feedback of the safe pulse cancellation for motor modules connected in parallel are different. 9999: Subsequent response to fault F01611. 3-537 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 538
- check the wiring of the safety-relevant input signals (contact problems). - replace the motor module involved. Note: CU: Control unit SI: Safety Integrated N01620 (F, A) SI CU: Safe standstill active Reaction: NONE Acknowledge: NONE 3-538 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 539
- check the electrical cabinet design and cable routing for EMC compliance - replace the motor module involved. Note: CU: Control unit SI: Safety Integrated 3-539 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 540
Re fault value = 9999: - carry-out diagnostics for the other safety-related fault that is present. Note: CU: Control unit SI: Safety Integrated See also: p9799, p9899 3-540 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 541
- check the electrical cabinet design and cable routing for EMC compliance Note: CU: Control unit SI: Safety Integrated F01656 SI CU: Incorrect motor module parameter Reaction: OFF2 Acknowledge: IMMEDIATELY (power on) 3-541 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 542
The motor module does not support the safety-related functions (e.g. the motor module version is not the correct one). Safety Integrated cannot be commissioned. Note: This fault results in a STOP A that cannot be acknowledged. 3-542 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 543
A connection was detected but the node ID exchange mechanism does not function. The reason is probably that the component is defective. This fault can only be acknowledged in cyclic communication. 3-543 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 544
PZD replacement. Reaction upon F: NONE (OFF1) Acknowledge IMMEDIATELY upon F: A01901 (F) PROFIBUS: Parameterizing telegram error Reaction: NONE Acknowledge: NONE 3-544 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 545
11: CU link fault. 12: CX32 not in cyclic operation. Remedy: Check the receive configuration data. Reaction upon F: NONE (OFF1, OFF2, OFF3) Acknowledge IMMEDIATELY upon F: 3-545 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 546
Fault value (r0949, decimal): 0: The transfer of the send-configuration data has been exceeded (time). 1: The transfer of the receive-configuration data has been exceeded (time). 3-546 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 547
Number of the drive object with the different speed controller clock cycle. Remedy: - set the speed controller clock cycles the same (p0115[1]). See also: p0115 A01940 PROFIBUS: Clock synchronism still not reached Reaction: NONE Acknowledge: NONE 3-547 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 548
NONE upon N: Reaction upon A: NONE Acknowledge NONE upon A: F01951 CU DRIVE-CLiQ: Synchronization, application clock cycle missing Reaction: OFF2 (NONE) Acknowledge: IMMEDIATELY (power on) 3-548 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 549
See also: p4800 A02005 Function generator: Drive does not exist Reaction: NONE Acknowledge: NONE Cause: The drive object specified for connection does not exist. See also: p4815 3-549 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 550
- stop before parameterizing the function generator (p4800 = 0). - if required, start the function generator (p4800 = 1). See also: p4800 A02025 Function generator: Period too short Reaction: NONE Acknowledge: NONE 3-550 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 551
Input an existing time slice cycle. The existing time slices can be read out via p7901. A02050 Trace: Start not possible Reaction: NONE Acknowledge: NONE Cause: The trace has already been started. 3-551 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 552
Use a valid data type. A02070 Trace: Parameter cannot be changed Reaction: NONE Acknowledge: NONE Cause: The trace parameter settings cannot be changed when the trace is active. 3-552 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 553
The component number (p0151) of the module involved is specified at the ones, tens and hundreds position. The thousands position specifies the analog input involved: 0: Analog input 0 (AI 0), 1: Analog input 1 (AI 1) 3-553 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 554
Alarm threshold for overtemperature of the power semiconductor in the AC converter has been reached. The response is set using p0290. If the chip temperature increases by an additional 15 K, then fault F30025 is initiated. 3-554 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 555
A power module signals that the pulses are enabled although the pulses are inhibited. Fault value (r0949, decimal): Number of the power module involved. Remedy: The power module is defective and must be replaced. 3-555 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 556
For parallel circuit configurations, only power modules with identical EEPROM versions may be used. F05057 Parallel circuit configuration: Power module versions differ Reaction: NONE Acknowledge: IMMEDIATELY 3-556 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 557
- check the parameterization (p0600, p0601). See also: p0600, p0601, p0607 F07016 Drive: Motor temperature sensor fault, fault Reaction: OFF1 (NONE, OFF2, OFF3, STOP1, STOP2) Acknowledge: IMMEDIATELY 3-557 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 558
The ACX file (PM file) to be executed was not able to be found in the appropriate directory. Fault value (r0949, decimal): Parameter number with which the execution was started. See also: p0015 3-558 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 559
- the higher-level control has withdrawn the "control by PLC" signal in operation. - data transfer via the fieldbus (master - drive) was interrupted in operation. 3-559 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 560
IMMEDIATELY Cause: During a flying restart, it was identified that the search current reached is too low. It is possible that the motor is not connected. 3-560 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 561
The kinetic energy of the motor is used in order to buffer the DC link. This brakes the drive. See also: p1240 Remedy: The alarm disappears when power supply returns. 3-561 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 562
- motor data and motor configuration (star/delta) do not match. - the current limit has been set too low for the motor. - the motor module is too small. 3-562 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 563
This fault causes the pulses to be cancelled - this is necessary to transfer the angular commutation offset to p0431. See also: p1990 Remedy: The fault can be acknowledged without any additional measures. 3-563 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 564
Drive data set + 100*first identical encoder + 1000*second identical encoder. See also: p0141, p0187, p0188, p0189 Remedy: Different encoders are always assigned to one drive data set. See also: p0141, p0187, p0188, p0189 3-564 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 565
- check the DRIVE-CLiQ connection. Reaction upon F: NONE (DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2) Acknowledge IMMEDIATELY (power on) upon F: Reaction upon N: NONE Acknowledge NONE upon N: 3-565 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 566
Fault value (r0949, decimal): The fault value includes the encoder data set number involved. Remedy: Check parameterization (p0421, p0404 Bit 0 and Bit 1). Upgrade the sensor module firmware. 3-566 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 567
See also: p0141, p0187, p0188, p0189, p0400 Remedy: Select the speed encoder in p0400. See also: p0400 F07575 Drive: Motor encoder not ready Reaction: OFF2 (NONE) Acknowledge: IMMEDIATELY 3-567 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 568
- ensure that there is a DC link voltage. Check the DC-link busbar. Enable the infeed. - replace the associated infeed or drive of the signaling component. - check the line supply voltage setting (p0210). See also: p0857 3-568 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 569
Acknowledge: IMMEDIATELY Cause: No rated data are stored in the power module EEPROM. See also: p0205, r0206, r0207, r0208, r0209 Remedy: Replace the power module or inform Siemens Customer Service. F07815 Drive: Power module has been changed Reaction: NONE Acknowledge:...
Page 570
IMMEDIATELY (power on) Cause: BICO signal "external alarm" triggered. See also: p2106 Remedy: Eliminate the causes of this fault. Reaction upon A: NONE Acknowledge NONE upon A: 3-570 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 571
- check r1087 and if required, correct p1082, CI: p1088 and p2162. F07902 (N, A) Drive: Motor stalled Reaction: OFF2 (NONE, OFF1, OFF3, STOP1, STOP2) Acknowledge: IMMEDIATELY 3-571 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 572
1: No output current reduction. 2: Output current reduction active. See also: p0604, p0610 Remedy: - check the motor load. - check the motor ambient temperature. 3-572 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 573
> p2190 Alarm value (r2124, decimal): Number of the parameter with the invalid value. Remedy: Set the parameters for the load monitoring according to the applicable rules. 3-573 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 574
See also: p0300, p0301, p0304, p0305, p0307, p0310, p0311, p0314, p0316, p0320, p0322, p0323 Reaction upon A: NONE Acknowledge NONE upon A: F07955 Drive: motor was changed Reaction: NONE Acknowledge: IMMEDIATELY 3-574 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 575
Drive: Automatic encoder adjustment activated Reaction: NONE Acknowledge: NONE Cause: The automatic encoder adjustment is activated. The automatic encoder adjustment is carried-out with the next power-on command. See also: p1990 3-575 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 576
Check the encoder connection and encoder cable. It is possible that there is a problem associated with the ground connection. Note: The encoder test can be switched-out (disabled) using p1959.0. See also: p1959 3-576 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 577
9: Too few data to be able to reliably identify the moment of inertia. 10: After the setpoint step, the speed either changed too little or in the incorrect direction. 11: The identified moment of inertia is not plausible. 3-577 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 578
No encoder available. The automatic speed controller optimization routine is carried-out without encoder (sensor- less). Alarm value (r2124, decimal): 1: An encoder is not connected. 2: It involves a SINAMICS G drive unit that only supports sensorless closed-loop control. 3-578 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 579
The alarm automatically disappears after the motor data identification routine has been successfully completed or for the setting p1900 = 0. Reaction upon N: NONE Acknowledge NONE upon N: 3-579 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 580
- check the set monitoring time if the error persists. See also: p2040 Reaction upon A: NONE Acknowledge NONE upon A: F08502 (A) COMM BOARD: Monitoring time, sign-of-life expired Reaction: OFF1 (OFF2, OFF3) Acknowledge: IMMEDIATELY 3-580 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 581
Remedy: Check communication line. Reaction upon F: NONE (OFF1, OFF2, OFF3) Acknowledge IMMEDIATELY upon F: A08530 (F) COMM BOARD: Message channel error Reaction: NONE Acknowledge: NONE 3-581 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 582
1: Non-cyclic send buffer (SDO response buffer) has overflowed. 2: Non-cyclic receive buffer (SDO receive buffer) has overflowed. 3: Cyclic send buffer (SDO response buffer) has overflowed. 3-582 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 583
Increase the number of channels in p8740 and confirm the selection using p8741. Reduce the number of PDOs by setting the COB-ID to invalid. See also: p8740, p8741 3-583 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 584
- power cables exceed the maximum permissible length. - power module defective. Fault value (r0949): Bit 0: Phase U. Bit 1: Phase V. Bit 2: Phase W. 3-584 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 585
- reduce the pulse frequency if this is higher than the rated pulse frequency. Notice: This fault can only be acknowledged after this alarm threshold for alarm A05000 has been fallen below. See also: p1800 3-585 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 586
- the DC link voltage ripple has exceeded the permissible limit value. Remedy: Check the fuses in the main circuit. F30012 Power module: Temperature sensor heatsink wire breakage Reaction: OFF1 (OFF2) Acknowledge: IMMEDIATELY 3-586 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 587
- the power cables exceed the maximum permissible length. - motor load too high - power module defective. Fault value (r0949, binary): Bit 0: Phase U Bit 1: Phase V Bit 2: Phase W 3-587 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 588
- overload - ambient temperature too high. - pulse frequency too high. Fault value (r0949): Temperature difference between the heatsink and chip [1 Bit = 0.01 °C]. 3-588 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 589
- check the line supply voltage - check the line supply. See also: p0210 A30031 Power module: Hardware current limiting, phase U Reaction: NONE Acknowledge: NONE 3-589 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 590
- check whether the ambient temperature is in the permissible range. Notice: This fault can only be acknowledged after this alarm threshold for alarm A05002 has been fallen below. 3-590 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 591
Reaction upon F: NONE (OFF1, OFF2, OFF3) Acknowledge IMMEDIATELY (power on) upon F: A30042 Power module: Fan operating time reached or exceeded Reaction: NONE Acknowledge: NONE 3-591 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 592
2000: Status of the SH terminals on the control unit and motor module are different. 2001: Feedback signal for safe pulse cancellation on the control unit and motor module are different. 3-592 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 593
- check the electrical cabinet design and cable routing for EMC compliance Note: MM: Motor module SI: Safety Integrated F30630 SI MM: Brake control defective Reaction: OFF2 Acknowledge: IMMEDIATELY (power on) 3-593 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 594
2003: Acceptance test is required as a safety parameter has been changed. 9999: Subsequent response of another safety-related fault that occurred at run-up that requires an acceptance test. 3-594 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 595
- Safety Integrated software releases on the control unit and motor module are not compatible with one another. Note: This fault results in a STOP A that cannot be acknowledged. Fault value (r0949, hexadecimal): Only for internal Siemens troubleshooting. 3-595 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 596
- check the electrical cabinet design and cable routing for EMC compliance - replace the component involved. See also: p9916 F30802 Power module: Time slice overflow Reaction: OFF2 Acknowledge: IMMEDIATELY 3-596 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 597
A DRIVE-CLiQ communications error has occurred between the control unit and the power module involved. Data were not able to be sent. Fault value (r0949, hexadecimal): 41: Telegram type does not match send list. 3-597 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 598
19: The error bit in the receive telegram is set and the receive telegram is too early. 09: The error bit in the receive telegram is set. 10: The receive telegram is too early. 3-598 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 599
- carry-out a POWER ON. See also: p9915 F30897 DRIVE-CLiQ: No communications to the components Reaction: OFF2 (DCBRAKE, ENCODER, NONE, OFF1, OFF3, STOP1, STOP2) Acknowledge: power on (IMMEDIATELY) 3-599 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 600
- replace the firmware on the power module by an older firmware version (r0128). - upgrade the firmware on the control unit (r0018). Reaction upon F: NONE (DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2) Acknowledge IMMEDIATELY (power on) upon F: 3-600 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 601
Bit 5 = 1: EMC / connect the cable shield, replace the encoder or encoder cable, replace the sensor module. Bit 6 = 1: The sensor module does not support this encoder. Acknowledgment: This fault can only be acknowledged by canceling the pulses. 3-601 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 602
A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec. SMC10: A signal level of 2900 mV peak value corresponds to the numerical value 6666 hex = 26214 dec. 3-602 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 603
Fault value (r0949, binary): Bit 0: Undervoltage condition on the sense line (threshold 4.75 V). Bit 1: Encoder power supply voltage overcurrent condition (threshold 450 mA). 3-603 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 604
The fault value is a bit field. Every set bit indicates functionality that is faulted. The bit assignment corresponds to that of p0404 (e.g. bit 5 set: Error C/D track). See also: p0404 3-604 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 605
Bit 3: Battery discharged. Bit 4: Reference point passed. Remedy: Replace encoder. Reaction upon F: NONE (DCBRAKE, ENCODER, OFF1, OFF2, OFF3, STOP1, STOP2) Acknowledge IMMEDIATELY upon F: 3-605 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 606
- aged lighting system. Reaction upon F: NONE (DCBRAKE, ENCODER, OFF1, OFF2, OFF3, STOP1, STOP2) Acknowledge IMMEDIATELY upon F: Reaction upon A: NONE Acknowledge NONE upon A: 3-606 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 607
- correct the sense of rotation of a Hall sensor that may be connected as equivalent C/D track. - check that the encoder cables are routed in compliance with EMC. - check the adjustment of the Hall sensor. 3-607 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 608
Remedy: Hardware defect: Replace the sensor module. Firmware error: If required, upgrade the firmware. F31805 Encoder 1: Incorrect EPROM checksum Reaction: ENCODER (DCBRAKE, NONE) Acknowledge: IMMEDIATELY 3-608 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 609
Fault value (r0949, hexadecimal): 21: The cyclic telegram has not been received. 22: Timeout in the telegram receive list. 40: Timeout in the telegram send list. 3-609 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 610
- replace the sensor module. - if required, upgrade the firmware in the sensor module. - contact the Hotline. F31860 CU DRIVE-CLiQ: Telegram error Reaction: ENCODER (DCBRAKE, NONE) Acknowledge: IMMEDIATELY 3-610 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 611
- check whether the firmware version of the encoder (r0148) matches the firmware version of control unit (r0018). F31887 CU DRIVE-CLiQ: Component faulted Reaction: ENCODER (DCBRAKE, NONE) Acknowledge: IMMEDIATELY 3-611 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 612
N: Reaction upon A: NONE Acknowledge NONE upon A: F31905 Encoder 1: Parameteriz. error Reaction: ENCODER (DCBRAKE, NONE, OFF1, OFF2, OFF3, STOP1, STOP2) Acknowledge: IMMEDIATELY 3-612 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 613
- adapt the parameter for the clearance between zero marks (p0425). - replace the encoder or encoder cable. F32101 Encoder 2: Zero mark failed Reaction: NONE (DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2) Acknowledge: IMMEDIATELY 3-613 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 614
Bit 3: Encoder power supply overvoltage condition. Bit 4: Encoder power supply undervoltage condition. Bit 5: Encoder power supply overcurrent condition. Bit 6: The battery must be changed. 3-614 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 615
- check that the encoder cables are routed in compliance with EMC. - check the plug connections. - replace the encoder or encoder cable. - check the encoder module (e.g. contacts). 3-615 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 616
- if the Hall sensor is used as equivalent C/D track, check the connection. - check the C or D track connection. - replace the encoder or encoder cable. 3-616 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 617
Bit 6: Position value longer than 40 bits. Remedy: - check that the encoder cables are routed in compliance with EMC. - check the plug connections. - replace the encoder. 3-617 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 618
Reaction upon N: NONE Acknowledge NONE upon N: N32415 (F, A) Encoder 2: Amplitude alarm, track A or B (A^2 + B^2) Reaction: NONE Acknowledge: NONE 3-618 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 619
F: Reaction upon N: NONE Acknowledge NONE upon N: A32419 (F, N) Encoder 2: Track A or B outside the tolerance range Reaction: NONE Acknowledge: NONE 3-619 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 620
- check that the encoder cables are routed in compliance with EMC. - check the plug connections. - replace the encoder or encoder cable. - coding disk dirty or strong magnetic fields. 3-620 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 621
Fault value (r0949, hexadecimal): 1, 2, 3: Encode initialization with the motor rotating. Remedy: Acknowledge the fault. F32820 Encoder 2 DRIVE-CLiQ: Telegram error Reaction: NONE (OFF1, OFF2) Acknowledge: IMMEDIATELY 3-621 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 622
Acknowledge: IMMEDIATELY Cause: DRIVE-CLiQ communications error between the control unit and the encoder involved. Fault value (r0949, hexadecimal): 0B: Synchronization error during alternating cyclic data transfer. 3-622 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 623
62: Error at the transition to cyclic operation. Remedy: - check the power supply voltage of the component involved. - carry-out a POWER ON. - replace the component involved. See also: p9915 3-623 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 624
- replace the firmware on the sensor module by an older firmware version (r0148). - upgrade the firmware on the control unit (r0018). Reaction upon N: NONE Acknowledge NONE upon N: 3-624 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 625
The measured zero mark clearance does not correspond to the parameterized zero mark clearance (p0425 for rotat- ing encoders). Fault value (r0949, decimal): Last measured zero mark clearance in increments (4 increments = 1 encoder pulse). 3-625 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 626
Bit 3: Encoder power supply overvoltage condition. Bit 4: Encoder power supply undervoltage condition. Bit 5: Encoder power supply overcurrent condition. Bit 6: The battery must be changed. 3-626 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 627
- check that the encoder cables are routed in compliance with EMC. - check the plug connections. - replace the encoder or encoder cable. - check the encoder module (e.g. contacts). 3-627 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 628
- if the Hall sensor is used as equivalent C/D track, check the connection. - check the C or D track connection. - replace the encoder or encoder cable. 3-628 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 629
Bit 6: Position value longer than 40 bits. Remedy: - check that the encoder cables are routed in compliance with EMC. - check the plug connections. - replace the encoder. 3-629 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 630
Reaction upon N: NONE Acknowledge NONE upon N: N33415 (F, A) Encoder 3: Amplitude alarm, track A or B (A^2 + B^2) Reaction: NONE Acknowledge: NONE 3-630 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 631
F: Reaction upon N: NONE Acknowledge NONE upon N: A33419 (F, N) Encoder 3: Track A or B outside the tolerance range Reaction: NONE Acknowledge: NONE 3-631 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 632
- check that the encoder cables are routed in compliance with EMC. - check the plug connections. - replace the encoder or encoder cable. - coding disk dirty or strong magnetic fields. 3-632 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 633
Fault value (r0949, hexadecimal): 1, 2, 3: Encode initialization with the motor rotating. Remedy: Acknowledge the fault. F33820 Encoder 3 DRIVE-CLiQ: Telegram error Reaction: NONE (OFF1, OFF2) Acknowledge: IMMEDIATELY 3-633 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 634
Acknowledge: IMMEDIATELY Cause: DRIVE-CLiQ communications error between the control unit and the encoder involved. Fault value (r0949, hexadecimal): 0B: Synchronization error during alternating cyclic data transfer. 3-634 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 635
62: Error at the transition to cyclic operation. Remedy: - check the power supply voltage of the component involved. - carry-out a POWER ON. - replace the component involved. See also: p9915 3-635 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 636
- replace the firmware on the sensor module by an older firmware version (r0148). - upgrade the firmware on the control unit (r0018). Reaction upon N: NONE Acknowledge NONE upon N: 3-636 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 637
IMMEDIATELY (power on) upon F: Reaction upon N: NONE Acknowledge NONE upon N: F34207 (N, A) VSM: Temperature fault threshold exceeded Reaction: NONE Acknowledge: IMMEDIATELY (power on) 3-637 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 638
An error has occurred during the RAM test on the voltage sensing module. Remedy: - check whether the permissible ambient temperature for the voltage sensing module is being maintained. - replace the voltage sensing module. 3-638 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 639
- carry-out a POWER ON. - check the electrical cabinet design and cable routing for EMC compliance - check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...). See also: p9916 3-639 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 640
- if required, upgrade the firmware in the voltage sensing module. - contact the Hotline. F34860 CU DRIVE-CLiQ: Telegram error Reaction: NONE (OFF1, OFF2) Acknowledge: IMMEDIATELY 3-640 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 641
Fault value (r0949, hexadecimal): 41: Telegram type does not match send list. Remedy: - carry-out a POWER ON. F34887 CU DRIVE-CLiQ: Component faulted Reaction: NONE (OFF1, OFF2) Acknowledge: IMMEDIATELY 3-641 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 642
An error has occurred in while accessing via the internal TM I2C bus. Remedy: Replace the terminal module. Reaction upon F: NONE Acknowledge IMMEDIATELY (power on) upon F: 3-642 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 643
Alarm value (r2124, decimal): Alarm number. If required, the significance of this new alarm can be referred to in a more recent description of the control unit. 3-643 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 644
Reaction upon N: NONE Acknowledge NONE upon N: Reaction upon A: NONE Acknowledge NONE upon A: A35211 (F, N) TM: Temperature threshold value exceeded Reaction: NONE Acknowledge: NONE 3-644 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 645
Enter the encoder pulse number in the permissible range (p0408). Reaction upon F: OFF1 (NONE, OFF2, OFF3) Acknowledge IMMEDIATELY (power on) upon F: Reaction upon N: NONE Acknowledge NONE upon N: 3-645 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 646
- check whether the permissible ambient temperature for the terminal module is being maintained. - replace the terminal module. Reaction upon F: NONE Acknowledge IMMEDIATELY (power on) upon F: Reaction upon N: NONE Acknowledge NONE upon N: 3-646 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 647
Reaction upon F: NONE Acknowledge IMMEDIATELY (power on) upon F: Reaction upon N: NONE Acknowledge NONE upon N: F35820 TM DRIVE-CLiQ: Telegram error Reaction: OFF1 (OFF2) Acknowledge: IMMEDIATELY 3-647 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 648
A DRIVE-CLiQ communications error has occurred between the control unit and the terminal module involved. Fault value (r0949, hexadecimal): 0B: Synchronization error during alternating cyclic data transfer. 3-648 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 649
62: Error at the transition to cyclic operation. Remedy: - check the power supply voltage of the component involved. - carry-out a POWER ON. - replace the component involved. See also: p9915 3-649 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 650
- replace the firmware on the terminal module by an older firmware version (r0158). - upgrade the firmware on the control unit (r0018). Reaction upon N: NONE Acknowledge NONE upon N: 3-650 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 651
10: TM15 24 V power supply for DI/DO 16 ... 23 (X522) missing. 20: TM41 24 V power supply for DI/DO 0 ... 3 missing. Remedy: Check the terminals for the power supply voltage (L1+, L2+, L3+, M). 3-651 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 652
NONE Acknowledge IMMEDIATELY (power on) upon F: Reaction upon N: NONE Acknowledge NONE upon N: A35920 (F, N) TM: Temperature sensor fault Reaction: NONE Acknowledge: NONE 3-652 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 653
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40004 Fault on drive object with object number 4 Reaction: NONE Acknowledge: IMMEDIATELY 3-653 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 654
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40011 Fault on drive object with object number 11 Reaction: NONE Acknowledge: IMMEDIATELY 3-654 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 655
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40018 Fault on drive object with object number 18 Reaction: NONE Acknowledge: IMMEDIATELY 3-655 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 656
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40025 Fault on drive object with object number 25 Reaction: NONE Acknowledge: IMMEDIATELY 3-656 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 657
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40032 Fault on drive object with object number 32 Reaction: NONE Acknowledge: IMMEDIATELY 3-657 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 658
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40039 Fault on drive object with object number 39 Reaction: NONE Acknowledge: IMMEDIATELY 3-658 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 659
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40046 Fault on drive object with object number 46 Reaction: NONE Acknowledge: IMMEDIATELY 3-659 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 660
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40053 Fault on drive object with object number 53 Reaction: NONE Acknowledge: IMMEDIATELY 3-660 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 661
First fault that has occurred for this drive object. Remedy: Evaluate the fault buffer of the specified object. F40060 Fault on drive object with object number 60 Reaction: NONE Acknowledge: IMMEDIATELY 3-661 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 662
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40105 Alarm on drive object with object number 5 Reaction: NONE Acknowledge: NONE 3-662 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 663
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40112 Alarm on drive object with object number 12 Reaction: NONE Acknowledge: NONE 3-663 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 664
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40119 Alarm on drive object with object number 19 Reaction: NONE Acknowledge: NONE 3-664 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 665
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40126 Alarm on drive object with object number 26 Reaction: NONE Acknowledge: NONE 3-665 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 666
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40133 Alarm on drive object with object number 33 Reaction: NONE Acknowledge: NONE 3-666 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 667
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40140 Alarm on drive object with object number 40 Reaction: NONE Acknowledge: NONE 3-667 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 668
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40147 Alarm on drive object with object number 47 Reaction: NONE Acknowledge: NONE 3-668 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 669
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40154 Alarm on drive object with object number 54 Reaction: NONE Acknowledge: NONE 3-669 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 670
First alarm that has occurred for this drive object. Remedy: Evaluate the alarm buffer of the specified object. A40161 Alarm on drive object with object number 61 Reaction: NONE Acknowledge: NONE 3-670 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 671
22: Timeout in the telegram receive list. 40: Timeout in the telegram send list. Remedy: - carry-out a POWER ON. - replace the component involved. See also: p9916 3-671 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 672
19: The error bit in the receive telegram is set and the receive telegram is too early. 09: The error bit in the receive telegram is set. 10: The receive telegram is too early. 3-672 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 673
A DRIVE-CLiQ communications error has occurred between the control unit and the controller extension involved. Fault value (r0949, hexadecimal): 0B: Synchronization error during alternating cyclic data transfer. Remedy: - carry-out a POWER ON. See also: p9915 3-673 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 674
Faults and Alarms List of faults and alarms 3-674 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 675
Connector Output/Binector Output COB-ID CAN object identification CAN object identification Mittelkontakt eines Wechselkontaktes Mid-position contact of a changeover contact Kommunikationsprozessor Communications Processor Zentralbaugruppe Central Processing Unit Abbreviations-675 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 676
Firmware Global-Control-Telegramm (Broadcast-Tele- Global Control telegram (broadcast tele- gramm) gram) Gerätestammdatei: beschreibt die Merkmale Device master file: describes the features of eines PROFIBUS-Slaves a PROFIBUS slave Abbreviations-676 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 677
(Klasse 1) und Slave N. C. Nicht angeschlossen Not Connected N... No report or internal report No Report Öffner Normally Closed contact Numerische Steuerung Numerical Control Abbreviations-677 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 678
Serielle Schnittstelle Serial Interface RS485 Norm. Beschreibt die Physik einer digitalen Standard Describes the physical characteris- seriellen Schnittstelle. tics of a digital serial interface. Dauerbetrieb Continuous operation Abbreviations-678 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 679
Voltage Sensing Module Voltage Sensing Module Werkzeugmaschine Machine tool Erweiterbare Auszeichnungssprache (Stan- Extensible Markup Language dardsprache für Web-Publishing und Doku- mentenmanagement) Zwischenkreis DC link PROFIBUS Zustandswort PROFIBUS statusword Abbreviations-679 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 680
List of Abbreviations Abbreviations-680 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 681
SIMATIC Components for Totally Integrated Automation, Catalog ST70 Ordering Information Order number: E86060-K4670-A111-A9 Edition: 10.2004 /PM10/ SIMOTION Motion Control System, Catalog PM10 Ordering Information Order number: E86060-K4910-A101-A4 Edition: 04.2003 References-681 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 682
SINAMICS S120 Equipment Manual for Chassis Power Modules Order number: 6SL3097-2AE00-0BP0 Edition: 12.2004 /GH4/ SINAMICS S120 Equipment Manual Power Modules Booksize Cold-Plate Order number: 6SL3097-2AJ00-0BP1 Edition: 12.2004 References-682 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 683
SINAMICS S List Manual Order number: 6SL3097-2AP00-0BP2 Edition: 12.2004 Further Supplementary Documentation Drive ES Basic V5.1 Function description Engineering System for drives from the SIEMENS A&D product range Order number: 6SW1700-0JA00-0AA0 Edition: 08.2001 SIMOTION Engineering System Handling Order number: 6AU1900-1AB31-0AA0 Edition: 01.2004...
Page 684
Order number: 4.071 /P3/ Distributed Layouts using PROFIBUS-DP Architecture and Fundamentals, configuration and Use of PROFIBUS-DP with SIMATIC S7 SIEMENS; Publicis MCD Verlag; Josef Weigmann, Gerhard Kilian Order number: A19100-L531-B714 ISBN 3-89578-074-X /P4/ Manual for PROFIBUS Networks, SIEMENS Order number:...
Page 685
Directive 98/37/EEC of the European Parliament and Council Machine Directive Bundesanzeiger-Verlags GmbH Edition: 22.06.1998 /SIAH/ Safety Integrated Application Manual Order number: 6ZB5000-0AA01-0BA0 4th Edition /SICD/ Safety Integrated CD-ROM Order number: E20001-D10-M103-X-7400 Edition: 09.2004 References-685 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 686
References References-686 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 687
BICO (p0922 = 999), 2-409 2130 2501 Digital inputs/outputs bidirectional Control word sequence control, 2-411 (DI/DO 8 ... DI/DO 9), 2-394 2503 Status word sequence control, 2-412 Index-687 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 688
Motorized potentiometer, 2-437 6492 3030 Control status word 1, 2-459 Main/supplementary setpoint, setpoint 6493 scaling, jogging, 2-438 Control status word 3, 2-460 6630 Upper/lower torque limit, 2-461 Index-688 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 689
Alarm value, 3-511 9100 Analog inputs Electrically isolated digital inputs Terminal Board 30 (TB30), 2-488 (DI 0 ... DI 3), 2-489 Terminal Module 31 (TM31), 2-493 Index-689 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 690
Command Data Set, CDS, 1-17 Drive Data Set, DDS, 1-17 Encoder Data Set, EDS, 1-17 Motor Data Set, MDS, 1-17 Power Module Data Set, PDS, 1-17 Index-690 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 691
Vector Encoder evaluation functions (po- (DI/DO 14 ... DI/DO 15), 2-397 sition, speed, temperature), 2-384 Digital inputs/outputs bidirectional Vector V/f-control, 2-385 (DI/DO 8 ... DI/DO 9), 2-394 Index-691 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 692
Function diagrams test sockets scaling, jogging, 2-438 Test sockets, 2-484 Motorized potentiometer, 2-437 Ramp-function generator selection, status word, tracking, 2-443 Suppression bandwidth and speed limi- ting, 2-440 Index-692 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 693
Explanation of the symbols (Part 3), 2-377 Fault, 3-510 Handling BICO-Technology, 2-378 Parameter, 1-13 Warning, 3-510 Numerical Range Holdingbrake, 2-425 Parameter, 1-21 Hotline, Preface-7 Object, 1-14 Index-693 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 694
Terminal Board 30 (TB30), 2-488 Safe brake control (SBC), 2-430 Terminal Module 31 (TM31), 2-493 Safe standstill (SH), 2-430 Test sockets, 2-483 Safety Guidelines (parameters), 1-20 Thermal monitoring, 2-472 Index-694 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 695
Speed control configuration, 2-457 Speed control with/without encoder, 2-449 Torque setpoint, 2-451 V/f characteristic, 2-453 V/f control status word 1, 2-456 Vdc_max controller and Vdc_min control- ler, 2-455 Index-695 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 696
Index Index-696 Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 697
Instrumentation and control Transportation Mechanical engineering Other _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Petrochemicals Siemens AG 2004 All Rights Reserved SINAMICS G List Manual, Edition 12.2004...
Page 698
Comments/suggestions Your comments and suggestions help us to improve the quality and usability of our documenta- tion. Please complete the questionnaire and return it by mail or fax to Siemens. Name of manual: SINAMICS G List Manual Please answer the following questions, giving each one a mark between 1 = good to 5 = poor.
Page 699
Overview of SINAMICS Documentation (12.2004) General Documentation/Catalogs SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS G110 G130 S120 S120 S150 G150 D21.1 D21.2 D11.1 D21.3 Vector Control Servo Control Converter Chassis Units Converter Chassis Units Vector Control Cabinet Units Drive System Drive System 0.12–3 kW Converter Cabinet Units 75–1200 kW...