Siemens SINAMICS G List Manual page 552

Table of Contents

Advertisement

Faults and Alarms
List of faults and alarms
Remedy:
Stop the trace and, if necessary, start again.
A02055
Trace: Recording time too short
Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace duration is too short.
The minimum is twice the value of the trace clock cycle.
Remedy:
Check the selected recording time and, if necessary, adjust.
A02056
Trace: Recording cycle too low
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected recording cycle is shorter than the selected basis clock cycle 0 (p0110[0]).
Remedy:
Increase the value for the trace cycle.
A02057
Trace: Invalid time slice clock cycle
Reaction:
NONE
Acknowledge:
NONE
Cause:
The time slice cycle selected does not match any of the existing time slices.
Remedy:
Input an existing time slice cycle. The existing time slices can be read out via p7901.
A02060
Trace: Signal to be recorded is missing
Reaction:
NONE
Acknowledge:
NONE
Cause:
- a signal to be traced was not specified.
- the specified signals are not valid.
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02061
Trace: Invalid signal
Reaction:
NONE
Acknowledge:
NONE
Cause:
- the specified signal does not exist.
- the specified signal can no longer be traced (recorded).
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
A02062
Trace: Trigger signal invalid
Reaction:
NONE
Acknowledge:
NONE
Cause:
- a trigger signal was not specified.
- the specified signal does not exist.
- the specified signal is not a fixed-point signal.
- the specified signal cannot be used as trigger signal for the trace.
Remedy:
Specify a valid trigger signal.
A02063
Trace: Invalid data type
Reaction:
NONE
Acknowledge:
NONE
Cause:
The specified data type to select a signal using a physical address is invalid.
Remedy:
Use a valid data type.
A02070
Trace: Parameter cannot be changed
Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace parameter settings cannot be changed when the trace is active.