Parameters
Parameter list
r1298
CO: Vdc controller output (V/f) / Vdc_ctrl output
VECTOR
Can be changed: -
Data type: Floating Point
P-Group: Functions
Min
- [1/min]
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
p1300[0...n]
Open-loop/closed-loop control operating mode / Control mode
VECTOR
Can be changed: C2, T
Data type: Integer16
P-Group: V/f control
Min
0
Description:
Sets the open and closed loop control type of a drive.
Values:
0:
1:
2:
3:
5:
6:
19:
20:
21:
22:
23:
Dependency:
Closed-loop speed control can be selected if, as operating mode (refer to p0108), at least closed-loop speed control
was selected.
Closed-loop torque control can only be selected if, as operating mode, at least the closed-loop torque/force control
was selected.
Only operation with V/f characteristic is possible if the rated motor speed is not entered (p0311).
Closed-loop speed or torque control (with encoder) cannot be selected if the encoder type is not entered (p0400).
For vector drives (refer to p0107):
A synchronous motor can only be operated in a V/f control mode (p1300 < 20).
Refer to: r0108, p0300, p0311, p0400, p1501
Note:
Closed-loop speed or torque control (with encoder) cannot be selected if the encoder type is not entered (p0400).
The closed-loop torque control can only be changed over in operation (p1300 = 20 or 21) by selecting the closed-
loop speed control (p1501). At the changeover, the setting of p1300 does not change. In this case, the actual state
is displayed in r1407, bit 2 and bit 3.
In the servo control mode the following applies:
Only p1300 = 20, 21, 23 can be set.
For closed-loop vector control, the following applies:
Closed-loop speed control can be selected if, as operating mode (p0108), at least closed-loop speed control was
selected.
Closed-loop torque control can be selected if, as operating mode, at least the closed-loop torque/force control was
selected.
Only operation with V/f characteristic is possible if the rated motor speed is not entered (p0311).
A synchronous motor can only be operated in a V/f control mode (p1300 < 20).
During operation (the pulses enabled) the open-loop/closed-loop control mode cannot be changed by changing-
over drive data sets.
1-172
V/f control with linear characteristic
V/f control with linear characteristic and FCC
V/f control with parabolic characteristic
V/f control with parameterizable characteristic
V/f control for drives requiring a precise frequency (e.g. textiles)
V/f control for drives requiring a precise frequency with FCC
V/f control with independent voltage setpoint
Speed control (sensorless)
Speed control (with encoder)
Torque control (sensorless)
Torque control (with encoder)
Data set: -
Units group: SPEED_ROT
Max
- [1/min]
Data set: DDS
Units group: -
Max
23
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Access level: 3
Function diagram: 6320
Unit selection: -
Factory setting
- [1/min]
Access level: 2
Function diagram: 1590,
1690, 5060, 6300
Unit selection: -
Factory setting
21