Siemens SINAMICS G List Manual page 121

Table of Contents

Advertisement

p0848[0...n]
BI: 1. OFF3 / 1. OFF3
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Commands
Min
-
Description:
Sets the signal source for the 1st OC/OFF3.
The AND logic operation of the 1st OC/OFF3 and 2nd OC/OFF3 results in control word 1, bit 2 (OC/OFF3).
Note:
Bit 2 = 0: OFF3 (braking along the OFF3 ramp (p1135), then pulse cancellation and power-on inhibit)
Bit 2 = 1: No OFF3 (enable is possible)
OC: Operating condition
p0849[0...n]
BI: 2. OFF3 / 2. OFF3
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Commands
Min
-
Description:
Sets the signal source for the 2nd OC/OFF3.
The AND logic operation of the 1st OC/OFF3 and 2nd OC/OFF3 results in control word 1, bit 2 (OC/OFF3).
Note:
Bit 2 = 0: OFF3 (braking along the OFF3 ramp (p1135), then pulse cancellation and power-on inhibit)
Bit 2 = 1: No OFF3 (enable is possible)
OC: Operating condition
p0852[0...n]
BI: Enable operation / Enable operation
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Commands
Min
-
Description:
Sets the signal source for control word 1 bit 3 (enable operation)
Note:
Bit 3 = 0: Inhibit operation (cancel pulses)
Bit 3 = 1: Enable operation (pulses can be enabled)
p0854[0...n]
BI: Master ctrl by PLC / Master ctrl by PLC
VECTOR
Can be changed: T
Data type: Unsigned32
P-Group: Commands
Min
-
Description:
Sets the signal source for control word 1 bit 10 (PLC control).
Note:
Bit 10 = 0: PLC has no master control
Bit 10 = 1: Master ctrl by PLC
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Data set: CDS
Units group: -
Max
-
Parameters
Parameter list
Access level: 3
Function diagram: 2501
Unit selection: -
Factory setting
1
Access level: 3
Function diagram: 2501
Unit selection: -
Factory setting
1
Access level: 3
Function diagram: 2442,
2443, 2501, 8920
Unit selection: -
Factory setting
1
Access level: 3
Function diagram: 2501,
2442, 2443, 8920
Unit selection: -
Factory setting
1