Bit field:
Bit
Signal name
00
Enc test active
01
Saturation characteristic identification
02
Moment of inertia identification
03
Recalculates the speed controller parame-
ters
04
Speed controller vibration test
Dependency:
Refer to: A07988
Note:
The encoder is only tested if the speed controller optimization with encoder is selected (p1960 = 2).
The following parameters are influenced for the individual optimization steps:
Bit 00: None
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1460, p1462, p1462, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1: p1400.0, p1458, p1459, p1470, p1472, p1496
p1960 = 2: p1458, p1459, p1460, p1461, p1462, p1463, p1496
p1960
Speed controller optimization selection / n_opt selection
VECTOR
Can be changed: T
Data type: Integer16
P-Group: Motor identification
Min
0
Description:
Sets the speed controller optimization.
After the next power-on command, the speed/velocity controller is automatically optimized.
The setting possibilities of the parameter depend on the open-loop/closed-loop control mode (p1300):
p1300 < 20 (V/f control): It is not possible to select the speed controller optimization routine.
p1300 = 20, 22 (sensorless operation): Only speed controller optimization can be selected in the sensorless mode.
p1300 = 21, 23 (operation with encoder): Both versions (sensorless and with encoder) of the speed controller opti-
mization routine can be selected.
Values:
0:
1:
2:
Dependency:
Refer to: p1300, p1900, p1959
Refer to: A07987
Notice:
In order to permanently accept the determined settings they must be saved in a non-volatile fashion (p0971,
p0977).
Note:
When the speed controller optimization is activated, it is not possible to save the parameters (p0971, p0977).
p1961
Saturation characteristic speed to determine / Sat_char n determ
VECTOR (n/M)
Can be changed: U, T
Data type: Floating Point
P-Group: Motor identification
Min
26 [%]
Description:
Sets the speed to determine the saturation characteristic and the encoder test.
The percentage value is referred to p0310 (rated motor frequency).
Dependency:
Refer to: p0310, p1959
Refer to: A07983
Note:
The saturation characteristics should be determined at an operating point with the lowest possible load.
 Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Inhibited
Speed controller optimization for sensorless operation
Speed controller optimization with encoder
0 signal
No
No
No
No
No
Data set: -
Units group: -
Max
2
Data set: -
Units group: PERCENT
Max
75 [%]
Parameters
Parameter list
1 signal
FP
Yes
-
Yes
-
Yes
-
Yes
-
Yes
-
Access level: 2
Function diagram: -
Unit selection: -
Factory setting
0
Access level: 3
Function diagram: -
Unit selection: -
Factory setting
30 [%]
1-227